30RHX
GB - 1
ENGLISH
Air-cooled water refrigerating unit assembly
Table I
Heat pump models
Power supply
30RHX006
230 V ~ 50 Hz
30RHX008
230 V ~ 50 Hz
30RHX011
230 V ~ 50 Hz
30RHX011-9
400 V 3N ~ 50 Hz
30RHX015-9
400 V 3N ~ 50 Hz
Unit size
Oil type
Quantity
Drier already installed on
l
liquid line of the unit
006
POE
1,12
YES
008
POE
1,12
YES
011
POE
1,25
YES
015
POE
1,85
YES
For operation and maintenance instructions of this unit as well as installation
instructions of the indoor unit, refer to the relevant manuals.
Contents
Page
Dimensions and weight .................................................................................................................
2
Technical data ................................................................................................................................
2
Minimum clearances ......................................................................................................................
3
Electrical data ................................................................................................................................
3
Data ...............................................................................................................................................
4
General information .......................................................................................................................
5
Warnings: avoid .............................................................................................................................
6
Water connections .........................................................................................................................
7
Connections and water circuits .....................................................................................................
8
Electrical connections ...................................................................................................................
8/10
Water-refrigerant heat exchanger .................................................................................................
11
Check the refrigerant charge .........................................................................................................
12
Unit maintenance ...........................................................................................................................
12
Control and safety devices ............................................................................................................
12
Diagnostics ....................................................................................................................................
13
Troubleshooting and guide for the owner .......................................................................................
14
ATTENTION INSTALLERS AND SERVICE TECHNICIANS!
AIR CONDITIONER WITH R-410A REFRIGERANT
• R-410A refrigerant operates at 50%-70% higher pressures than R-22. Be sure that servicing
equipment and replacement components are designed to operate with R-410A.
• R-410A refrigerant cylinders are pink in colour.
• R-410A refrigerant cylinders have a dip tube which allows liquid to flow out of the cylinder in upright
position.
• The R-410A units must be charged with refrigerant in a liquid state. Use a commercial type metering
device in the manifold hose in order to vaporize the liquid refrigerant before it enters in the unit.
• R-410A, as other HFCs, is only compatible with the following oils selected by the compressor
manufacturer.
• The vacuum pump is not sufficient to remove moisture from the oil.
• POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
• Never open unit to atmosphere while it is under a vacuum.
• When unit must be opened for service, break vacuum with dry nitrogen and replace filter dryer.
• Do not vent R-410A into the atmosphere.