Carrier AQUASNAP JUNIOR 30RHV Installation Manual Download Page 9

GB - 8

30RHV

Remove electric box cover.
Connect the wires to the terminals according to the wiring diagram
and firmly tighten.

• The characteristics of the available power supply must

correspond to the unit nameplate specifications.

 The voltage must be within the limits indicated in the technical

data table.

 The imbalance between voltage phases must always be less

than 2%.

 WARNING:

If the unit operates at a voltage outside the limits given in Table
VIII or with a phase imbalance above 2%, this constitutes
improper use and may affect the warranty.
If the phase imbalance is higher than 2%, contact the local
electricity board immediately.

 Electric wiring must be in accordance with data indicated in this

manual and the wiring diagram and conform to applicable local
and national regulations.

• Ensure that mains supply connection is made through a switch

that disconnects all poles, with contact gap of a least 3 mm.

• The mains supply connecting cable must be H07 RN-F (or

higher) type, synthetic rubber insulation with Neoprene coating,
according to EN 60335-1 codes.

IMPORTANT:
• Make earth connection prior to any other electrical

connections.

• Earthing is required by law.

The installer must earth the unit using the terminal marked
with the international earthing symbol.

• Before connecting the supply cable to the line, locate line

(L), lines (L1-L2-L3) and neutral N. Then make connections,
as indicated in the wiring diagram.
WARNING
:
The supply line of three-phase units must be three-phase plus
neutral. Omission of the neutral N line could damage the single-
phase supplies.

 The wiring diagram for the electrical supply to remote controls/

interlocks is inside the unit, glued under the cover.

• See Table III for cables sizes and dimensions of the electrical

devices.

Power circuit supply

 The power circuit supply (three-phase plus neutral) must be

connected to the correct terminals (see wiring diagram).

 The auxiliary circuit supply is directly taken from one phase and

neutral and it is proteced by fuse "F".

• If the electrical supply cables L1 (R), L2 (S), L3 (T) are

connected in an incorrect sequence, the power supply is
interrupted after a few seconds by the control, which goes into
alarm status preventing the incorrect compressor rotation.

Note:
After connections have been completed, replace electric box
cover.

Electrical connections

Connections and water circuits

Correction factors for ethylene glycol

Ethylene glycol

10%

20%

30%

40%

Freezing
temperature

–4

°

C

–9

°

C

–15

°

C

–23

°

C

Capacity

0.996

0.991

0.983

0.974

Power input

0.990

0.978

0.964

1.008

Water flow rate

1.000

0.979

0.979

1.025

Pressure drop

1.003

1.010

1.020

1.033

Connections and water circuits

 The hydraulic circuit must be designed to ensure a steady water

flow through the evaporator at any time.

 The water pipes in the circuit must be well supported and firmly

fastened to ensure that they do not put a strain on the
connections to the unit.

 Water inlet and outlet are identified by a tag.
 Air purge and water drain are located at the inlet and outlet

connections and are closed by appropriate plugs.

 Pipes must have shut-off valves to permit emptying of the heat

exchanger without draining the whole system, as suggested in
the diagram.

To reduce to minimum system pressure drop it is necessary:
- to reduce number of bends;
- to avoid elbow bends;
- to reduce the system extension to a minimum;
- to use pipes of the correct diameter.

To avoid possible damage due to water freezing, it is
recommended to install the water refill system inside the building.

It is recommend:
- to fit a replaceable filter of at least 10 mesh/cm

2

 in the water

inlet, especially with welded joint iron pipes.
Water changes or additions should be reduced, if possible, as
they contribute to oxidation and to calcium deposit formation.

The control can pilot an external pump with a current input of up to
8 Ampere.

Flow switch
The flow switch in the outlet line to the pump stops the
compressor operation in case of:

• pump failure;

• water circulation cut-off;

• presence of air un the system.

Summary of Contents for AQUASNAP JUNIOR 30RHV

Page 1: ...AQUASNAP JUNIOR 30RHV INSTALLATION MANUAL L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1...

Page 2: ...e with R 410A R 410A refrigerant cylinders are pink in colour R 410A refrigerant cylinders have a dip tube which allows liquid to flow out of the cylinder in upright position The R 410A units must be...

Page 3: ...E D B C F A E E D B C F A G H G H Mod 30RHV 006 008 Mod 30RHV011 Mod 30RHV 006 008 011 A mm 800 800 800 B mm 803 803 1264 C mm 300 300 300 D mm 508 508 508 E mm 146 146 146 F mm 330 330 330 G mm 97 9...

Page 4: ...rotection Compressor Capacitor F V 40 450 50 450 60 450 Fan motor 230 1 50 Current input A 0 82 1 1 1 64 1 64 Capacitor F V 4 450 3 450 4 450 4 450 Compressor crankcase heater 230 1 50 W 25 25 25 25 C...

Page 5: ...ble V Refer to the following example for the buffes tank open closed Refrigerant circuit high pressure switch kPa 4206 2996 Freeze up protection C 2 7 Compressor first start delay sec 60 Compressor st...

Page 6: ...and explain all chiller functions to the owner Leave this manual with the owner for consultation during future periodic maintenance The chiller and its components must be periodically inspected to ch...

Page 7: ...ruction of the unit air outlet and intake or any obstacle that is too close see minimum clearances required Installation on grassy ground or soft surfaces in these cases a solid foundation must be inc...

Page 8: ...ust be located at the highest point of the circuit Pressure drop Pressure drop kPa Water flow rate l h Pressure drop kPa Water flow rate l h Pressure drop kPa Water flow rate l h Legend DP KPa 12 C DP...

Page 9: ...iary circuit supply is directly taken from one phase and neutral and it is proteced by fuse F If the electrical supply cables L1 R L2 S L3 T are connected in an incorrect sequence the power supply is...

Page 10: ...pply N Neutral power supply S1 ON OFF switch S2 HEAT COOL switch NOTE The contact rating must be greater than 20 mA 24 V ac G L N 0 24 5 6 1 2 3 4 S1 S2 Unit electrical panel Terminal blocks Electroni...

Page 11: ...HEAT COOL switch NOTE The contact rating must be greater than 20 mA 24 V ac G L1 L2 L3 N 0 24 5 6 1 2 3 4 S1 S2 Unit electrical panel Terminal blocks Electronic board connectors Power supply 400V 3ph...

Page 12: ...r outlet 11 Reversing valve Refrigerant R 410A Gas Liquid Gas Liquid The unit includes a brazed plate water refrigerant heat exchanger The heat exchanger operates as an evaporator in the summer cycle...

Page 13: ...control setpoint This parameter is regulated by the control and factory set to an entering water temperature of 12 C The second set point default value is 14 C and it can be selected via the Service...

Page 14: ...ducer wire interrupted or transducer fault 13 Low refrigerant pressure Unit stopped Automatic Lack of refrigerant in the circuit blocked in the circuit Manual refrigerant filter or low pressure transd...

Page 15: ...stopped check cause and repair Wrong electrical connections on defrost circuit check electrical connections and repair Discharge pressure too high Coil dirty or obstructed clean or remove obstructions...