![Carrier AQUASNAP JUNIOR 30RHV Installation Manual Download Page 3](http://html1.mh-extra.com/html/carrier/aquasnap-junior-30rhv/aquasnap-junior-30rhv_installation-manual_2561852003.webp)
30RHV
GB - 2
Dimensions and weight
Unit capacities and power input (compressor and
conventional pump watts) are based on:
Cooling:
outdoor air temperature 35
°
C d.b.; 24
°
C w.b., /
water temperature - leaving 7
°
C / entering 12
°
C
Eurovent 6/C/003-1998, CEN/TC113/WG5 N 4
Heating:
outdoor air temperature 7
°
C d.b.; 6
°
C w.b., /
entering water temperature 40
°
C,
leaving water temperature 45
°
C
Eurovent 6/C/003-1998
E
E
D
B
C
F
A
E
E
D
B
C
F
A
G
H
G
H
*
*
Mod. 30RHV 006 - 008
Mod. 30RHV011
Mod.
30RHV
006
008
011
A
mm
800
800
800
B
mm
803
803
1264
C
mm
300
300
300
D
mm
508
508
508
E
mm
146
146
146
F
mm
330
330
330
G
mm
97
97
97
H
mm
157
157
157
kg
kg
85
88
112
*
Electrical cables inlet
Table II: Technical data
Unit
30RHV
006
008
011---7
011---9
Power input
Cooling
kW
2.0
2.6
3.4
3.3
Heating
kW
2.4
2.6
3.5
3.6
Compressor type
SCROLL
Propeller fan motor - diameter
No./mm
1/370
1/370
2/370
2/370
Speed
rpm
1050
1200
1050
1050
Heat exchanger
WELDED PLATES
Water content
l
0.85
0.94
1.22
1.22
Expansion device
#
5
6
8
8