Table of minimum and maximum wire sections for connection to 61AF units
61AF
Disconnect
switch
Connectable wire
Max.
connectable
section
Min. wire section
Max. wire section
Section
(mm
2
)
Section (mm
2
)
Max. length (m)
Wire type
Section (mm
2
)
Max. length (m)
Wire type
022
1 x 10
1 x 6
100
XLPE Cu
1 x 10
210
PVC Cu
030
1 x 10
1 x 6
100
XLPE Cu
1 x 10
245
PVC Cu
035
1 x 10
1 x 10
130
XLPE Cu
1 x 10
245
PVC Cu
045
1 x 16
1 x 10
130
XLPE Cu
1 x 16
245
PVC Cu
055
1 x 16
1 x 10
130
XLPE Cu
1 x 16
245
PVC Cu
075
1 x 16
1 x 16
220
XLPE Cu
1 x 16
245
PVC Cu
105
1 x 35
1 x 35
220
XLPE Cu
1 x 35
220
PVC Cu
Note: Power supply cable section (see the diagram in the chapter “Electrical connection”).