4 - PHYSICAL DATA
61AF
022
030
035
045
055
075
105
Operating weight(1)
Standard unit without hydraulic module
kg
340
396
411
500
523
900
1020
Standard unit + optional hydraulic module
kg
352
408
425
564
588
956
1076
Sound levels
Sound power level
(2)
dB(A)
77
78
83
82
84
84
85
Sound pressure level at 10 m
(3)
dB(A)
46
46
51
51
53
52
53
Dimensions
Lenght
mm
1110
1110
1110
1114
1114
2273
2273
Depth
mm
1327
1327
1327
2100
2100
2100
2100
Height
mm
1330
1330
1330
1330
1330
1330
1330
Compressors
Hermetic scroll compressor 48,3 r/s
Quantity
1
1
1
1
1
2
2
No. of capacity steps
1
1
1
1
1
2
2
Refrigerant
R407C GWP = 1800 following AR4
Charge
kg
8
8,8
9,7
10
13,2
22
26,5
teq CO
2
14,2
15,6
17,2
17,7
23,4
39,0
47,0
Oil
POE - EMKARATE RL32-3 MAF
Charge
l
1,9
4,1
4,1
4,1
4,1
8,2
8,2
Capacity control
SmartVu
TM
Minimum capacity
%
100
100
100
100
100
50
50
Condensers
Direct-expansion welded plate heat exchanger
Water volume
l
4,9
6,4
8,2
9,6
12,1
16,4
22,7
Max. water-side operating pressure without hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
Max. water-side operating pressure with hydraulic module
kPa
400
400
400
400
400
400
400
Fans
Axial Flying Bird 4 fans with rotating shroud
Quantity
1
1
1
1
1
2
2
Maximum total air flow
l/s
3770
3748
3736
4035
4036
7479
8072
Max speed, standard unit
tr/s
12
12
12
12
12
12
12
Max speed, unit with option 11
tr/s
-
-
16
16
16
16
16
Evaporator
Grooved copper tubes, aluminium fins
Hydraulic module (option)
Variable speed pump
Pump, Victaulic screen filter, relief valve, water + air purge
valves cavitation pressure sensors
Water connections (with and without hydraulic module)
Victaulic
Connections
(4)
inch
1″1/4
1″1/4
1″1/2
1″1/2
1″1/2
2
2
Outside tube diameter
mm
42,4
42,4
48,3
48,3
48,3
60,3
60,3
Chassis paint colour
Colour code RAL 7035
(1) Weight shown is a guideline only. Please refer to the unit nameplate
(2) In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-2dB(A)). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(3) In dB ref 20 μPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-2dB(A)). For information,
calculated from the sound power level Lw(A).
(4) Units 61AF 022 and 61AF 030 include two sleeves for a 1-1/4’’ Victaulic to 1-1/4’’ screw connection as standard.
Summary of Contents for AquaSnap 61AF 022