background image

39

15.5 - leak detection

Never use oxygen or dry air, as this would cause a risk of 
fire or explosion.
• 

Carry out a leak detection test on the whole system 
using the following methods: pressure test using 
dehydrated nitrogen or a mixture of nitrogen and 
refrigerant used for the system, helium leak test. 

• 

Connect the compressor to the system by opening the 
valves.

•   The duration of the test must be sufficient to guaran-

tee the absence of very small leaks in the circuit.

•   Use specific tools, designed for leak detection.
• 

The low-pressure side test pressure must not exceed 
pressure Ps indicated on the compressor and unit 
name plates.

•   If there is a leak, repair it and carry out the leak 

detec-tion test again.

15.6 - Evacuation 

To evacuate the system, observe the following recommen-
dations:

Connect the vacuum pump to the high (HP) and low-
pressure (LP) side for evacuation of the complete circuit.

All units are equipped with valves with 3/8” SAE connec-
tions on the suction and liquid lines, permitting the connec-
tion of large-diameter flexible pipes limiting the pressure 
drops for the evacuation.
1.  The vacuum level achieved must be 0.67 mbar (500 µm 

Hg).

2.  Wait 30 minutes.
3.  If the pressure increases rapidly, the system ist not 

leak-tight. Localise and repair the leaks.

 

Restart the evacuation procedure and repeat steps 1, 2 
etc.

4.  If the pressure increeases slowly, this indicates that 

moisture is present inside the system. Break the vacuum 
with nitrogen and restart the evacuation procedure 
(steps 1, 2 etc.).

5.  Repeat the evacuation procedure (steps 1, 2); a vacuum 

level of 0.67 mbar (500 µm Hg) must be achieved and 
maintained for four hours. 

 

This vacuum level must be measured at one of the system 
connections and not at the vacuum pump pressure 
gauge.

ATTENTION: Do not use a megohmmeter and do not 
place any stress on the compressor motor when the system 
has been ecacuated. There is a risk of internal short circuits 
between the motor windings.

Do not use additives for leak detection. Do not use CFCs/
hCFCs as tracer fluids for leak detection.

15.7 - Recharging liquid refrigerant

CAUTION: 30RW units are charged with liquid hFC-
407C refrigerant.

This non-azeotropic refrigerant blend consists of 23% R-32, 
25% of R-125 and 52% R-134a, and is characterised by 
the fact that at the time of the change in state the tempera-
ture of the liquid/vapour mixture is not constant, as with 
azeotropic refrigerants. All checks must be pressure tests, 
and the appropriate pressure/temperature ratio table must 
be used to determine the corresponding saturated tempe-
ratures (saturated bubble point curve or saturated dew 
point curve).

Leak detection is especially important for units charged 
with refrigerant R-407C. Depending on whether the leak 
occurs in the liquid or in the vapour phase, the proportion 
of the different components in the remaining liquid is not 
the same.

NOTE: Regularly carry out leak checks and immediately 
repair any leak found.

15.8 - Characteristics of R-407C

See the table on the next page.
Saturated bubble point temperatures (bubble point curve)
Saturated dew point temperatures (dew point curve)

15.9 - Electrical maintenance

When working on the unit comply with all safety precau-
tions described in section 1.3. 

It is strongly recommended to change the unit fuses every 
15000 operating hours or every three years.

It is recommended to verify that all electrical connections 
are tight:
• 

after the unit has been received at the moment of 
installation and before the first start-up, 

• 

one month after the first start-up,when the electrical 
components have reached their nominal operating 
temperatures,

• 

then regularly once a year.

Summary of Contents for Aquasnap 30RW

Page 1: ...30RW RWA Water Cooled Condenserless Liquid Chillers with Integrated Hydronic Modules Nominal cooling capacity 20 310 kW 50 Hz Installation operation and maintenance instructions...

Page 2: ...5 5 3 Operating range 30RWA 16 5 4 Minimum chilled water flow 16 5 5 Maximum chilled water flow 16 5 6 Variable flow evaporator 16 5 7 Evaporator flow rate 16 5 8 Condenser water flow rate l s 16 5 9...

Page 3: ...enser model used in the installation 31 12 6 Possible fan arrangements based on the air cooled condenser type used in the installation 32 13 START UP 34 13 1 Preliminary checks 34 13 2 Actual start up...

Page 4: ...erally made of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust buil...

Page 5: ...ituated on the liquid line before the filter drier box Any intervention on the refrigerant circuit including changing of drier blocks is only permitted after the complete removal of the refrigerant ch...

Page 6: ...ant on skin or splashing it into the eyes Use safety goggles and safety gloves Wash any spills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush...

Page 7: ...ersons 2 2 Moving and siting the unit 2 2 1 Moving See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there...

Page 8: ...its B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning o...

Page 9: ...let for 30RW units B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For th...

Page 10: ...ts B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning of...

Page 11: ...ed by frequency converter 48 3 r s Power input kW 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 5 0 5 0 5 0 5 0 5 0 5 0 6 7 6 7 6 7 6 7 Expansion tank volume condenser loop l 8 8 8 8 8 12 12 12 25 25 25 25 25 3...

Page 12: ...r and the pumps the control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable local codes The Carrier 30RW and 30R...

Page 13: ...pumps 30RW 30RWA option 116C No Description 30RW 30RWA 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1...

Page 14: ...variable speed pump No Description 30RW 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1 87 6 87 6 87 6...

Page 15: ...low leaving water temperature and use of antifreeze is required 2 30RW units without hydronic module operating below 20 C entering condenser water temperature require the use of a three way valve cont...

Page 16: ...r units without hydronic module that have a fixed condenser flow rate Units with a hydronic module have a variable flow rate and no minimum fixed flow rate The minimum flow rate is optimised by unit c...

Page 17: ...er mixing of the liquid water or brine Refer to the examples below Bad Bad Good Good 5 10 Maximum water loop volume evaporator and condenser side Units with hydronic module incorporate an expansion ta...

Page 18: ...er flow rate l s Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30RW 045 5 30RW 060 6 30RW 070 7 30RW 080 8 30RW 090 9 30RW 110 10 30RW 120 11 30RW 135 12 30RW 150 13 30RW 160 185 14 30RW 210 245 15 30...

Page 19: ...at the main disconnect switch Before connecting electric power cables it is imperative to check the correct order of the 3 phases L1 L2 L3 Non certified drawings Refer to the certified dimensional dr...

Page 20: ...switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables For the design the following standar...

Page 21: ...0 Ohm m are desirable A neutral environment favours maximum specific resistance values For electric conductivity values in the order of 20 60 mS m can be recommended 10 pH Ideal case pH neutral at 20...

Page 22: ...y Damage due to freezing is not covered by the warranty IMPORTANT Depending on the climatic conditions in your area you must Add ethylene glycol with an adequate concentration to protect the installat...

Page 23: ...Pressure gauge to measure the plate heat exchanger pressure drop to be isolated with valve No 5 if not used 7 Plate heat exchanger Legend Components of unit and hydronic module 1 Victaulic screen filt...

Page 24: ...The air cooled condenser must always be used with a subcooler normally with 8 K subcooling 8 2 General Refrigerant pipe sizing must be carried out taking account of the following constraints Oil retur...

Page 25: ...a saturated suction temperature of 4 C and 8 K subcooling Table 3 shows the correction factors to be applied to the values from Table 2 if the operating conditions are different from those previously...

Page 26: ...ing temperature C Outside pipe diameter inch 1 2 5 8 3 4 7 8 1 1 8 1 3 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 27 0 81 1 48 2 39 3 66 7 14 12 06 18 64 37 21 63 94 99 81 145 60 201 98 32 0 84 1 51 2 46 3...

Page 27: ...the forced start command refer to the controls manual and let the pump run for two con secutive hours to clean the hydronic circuit of the system presence of solid contaminants Read the plate heat ex...

Page 28: ...300 1 2 3 4 0 25 50 75 100 125 150 175 200 2 4 6 8 10 50 100 150 200 250 0 5 10 15 20 25 2 1 4 3 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 9 3 Available static system pressure evaporator side Sing...

Page 29: ...0 50 100 150 200 250 0 5 10 15 20 25 30 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 10 2 Available static system pressure condenser side Single pump Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30R...

Page 30: ...st efficiency with variation of the water flow rate and the number of fans required for any thermal load and outside temperature conditions The electronic board AUX1 integrated in the control box of t...

Page 31: ...This is the first fan to start in each circuit and the last fan to stop A fan configuration with fixed speed fans permits year round system operation down to 0 C outside temperature A fan configurati...

Page 32: ...B from fan 2 of each circuit If fans 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH4 for circuit A and CH5 to CH8 for circuit B from fan 1 Single circuit condenser Circuit Possibl...

Page 33: ...its A and B If fan 1 has variable speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 2 If fan 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 1 Dual circuit...

Page 34: ...at all safety devices are operational especially that the high pressure switches are switched on and that the alarms are acknowledged 13 3 Operation of two units in master slave mode The control of a...

Page 35: ...relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 14 Major system components and operation data 14 1 Compressors 30...

Page 36: ...ow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If there are no regulations or to compl...

Page 37: ...onents that do not comply must be changed Test pressures above the respective component design pressure must not be applied annex B and D After repair or significant modifications or significant syste...

Page 38: ...expansion device must be between 12 and 14 C This corresponds to an actual subcooling temperature of between 6 and 8 K at the condenser outlet depending on the unit type Actual subcooling is equal the...

Page 39: ...the vacuum pump pressure gauge ATTENTION Do not use a megohmmeter and do not place any stress on the compressor motor when the system has been ecacuated There is a risk of internal short circuits bet...

Page 40: ...02 5 23 14 33 89 39 16 23 5 54 64 59 07 4 75 0 34 6 57 14 25 34 54 39 79 23 75 55 1 59 5 5 1 66 7 86 14 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 1...

Page 41: ...tions contactors disconnect switch and transformer Check the status of the contactors and fuses Carry out a quick test refer to the 30RW RWA Pro Dialog Plus controls manual Mechanical checks Verify th...

Page 42: ...ment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has b...

Page 43: ...loop volume litres Calculated volume litres 3 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 020 045 2 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 060 300 Pr...

Page 44: ...tor LWT Condenser EWT Condenser LWT Circuit A suction pressure Circuit B suction pressure Circuit A discharge pressure Circuit B discharge pressure Circuit A suction temperature Circuit B suction temp...

Reviews: