background image

38

15.2 - general unit maintenance

• 

Keep the unit itself and the space around it clean and 
free of obstructions. Remove all rubbish such as packing 
materials, as soon as the installation is completed.

• 

Regularly clean the exposed pipework to remove all 
dust and dirt. This makes detection of water leaks 
easier, and they can be repaired before more serious 
faults develop.

• 

Confirm that all screwed and bolted connections and 
joints are secure.

• 

Secure connections prevent leaks and vibration from 
developing. 

• 

Check that all foam insulation joints on the heat 
exchanger piping are in good condition. 

15.3 - Refrigerant charge

15.3.1 - Undercharge
If there is not enough refrigerant in the system, this is 
indicated by gas bubbles in the moisture sight glass.

If the undercharge is significant, large bubbles appear in 
the moisture sight glass, and the suction pressure drops. 
The compressor suction superheat is also high. The machine 
must be recharged after the leak has been repaired.

Find the leak and completely drain the system with a 
refrigerant recovery unit. Carry out the repair, leak test 
and then recharge the system.

IMPORTANT: After the leak has been repaired, the circuit 
must be tested, without exceeding the maximum low-side 
operating pressure shown on the unit name plate.

The refrigerant must always be recharged in the liquid phase 
into the liquid line. The refrigerant cylinder must always 
contain at least 10% of its initial charge. For the refrigerant 
quantity per circuit, refer to the data on the unit name plate.

15.3.2 - Verification of the charge

CAUTION: The 30RW units are supplied with a precise 
refrigerant charge (see Physical Data table).

To verify the correct system charge prodeed as follows:
Ensure that no bubbles appear in the sight-glass, when 
ope-rating the unit at full load for a while. Use a saturated 
con-densing temperature between 45 and 50°C. Under 
these conditions the apparent subcooling which is equal to 
the saturated condensing temperature (1 - on the saturated 
dew point curve) minus the liquid refrigerant temperature 
(3) ahead of the expansion device must be between 12 and 
14°C. This corresponds to an actual subcooling temperature 
of between 6 and 8 K at the condenser outlet, depending on 
the unit type. Actual subcooling is equal the saturated 
liquid temperature (2 - on the saturated bubble point curve) 
minus the liquid refrigerant temperature (3) ahead of the 
expansion device. Use the pressure tap supplied on the liquid 
piping to charge refrigerant and to find out the pressure of 
the liquid refrigerant. If the subcooling value is not correct, 
i.e. lower than the specified values, a leak detection test must 
be carried out on the unit, as it no longer contains its original 
charge.

WARNINg: To ensure proper operation of 30RW units 
there must be at least 12 K of subcooling as the liquid 
refrigerant enters the expansion valve.

The 30RW units use refrigerant. For your information, we 
are reproducing here some extracts from the official 
publi-cation dealing with the design, installation, 
operation and maintenance of air conditioning and 
refrigeration systems and the training of people involved 
in these activities, agreed by the air conditioning and 
refrigeration industry.

Apparent and actual subcooling

Pr

essur

e

Enthalpy

legend

Saturated condensing temperature at the dew point

Saturated liquid temperature at the bubble point

Liquid refrigerant temperature

Saturation curve at the dew point

Saturation curbe at the bubble point

Isotherms

Apparent subcooling (1 - 3)

Real subcooling (2 - 3)

Liquid

L + V   vapour

Vapour

15.4 - Refrigerant guidelines 

Refrigeration installations must be inspected and maintained 
regularly and rigorously by specialists. Their activities must 
be overseen and checked by properly trained people. To 
minimise discharge to the atmosphere, refrigerants and 
lubricating oil must be transferred using methods which 
reduce leaks and losses to a minimum.
• 

Leaks must be repaired immediately.

• 

If the residual pressure is too low to make the transfer 
alone, a purpose-built refrigerant recovery unit must 
be used.

• 

Compressor lubricating oil contains refrigerant. Any 
oil drained  from a system during maintenance must 
therefore be handled and stored accordingly.

• 

Refrigerant under pressure must never be discharged 
to the atmosphere.

3

4

5

1

6

2

L

L + V

V

Summary of Contents for Aquasnap 30RW

Page 1: ...30RW RWA Water Cooled Condenserless Liquid Chillers with Integrated Hydronic Modules Nominal cooling capacity 20 310 kW 50 Hz Installation operation and maintenance instructions...

Page 2: ...5 5 3 Operating range 30RWA 16 5 4 Minimum chilled water flow 16 5 5 Maximum chilled water flow 16 5 6 Variable flow evaporator 16 5 7 Evaporator flow rate 16 5 8 Condenser water flow rate l s 16 5 9...

Page 3: ...enser model used in the installation 31 12 6 Possible fan arrangements based on the air cooled condenser type used in the installation 32 13 START UP 34 13 1 Preliminary checks 34 13 2 Actual start up...

Page 4: ...erally made of plastic and should not be used If they are still present please remove them Install devices at the valve outlets or drain piping that prevent the penetration of foreign bodies dust buil...

Page 5: ...ituated on the liquid line before the filter drier box Any intervention on the refrigerant circuit including changing of drier blocks is only permitted after the complete removal of the refrigerant ch...

Page 6: ...ant on skin or splashing it into the eyes Use safety goggles and safety gloves Wash any spills from the skin with soap and water If liquid refrigerant enters the eyes immediately and abundantly flush...

Page 7: ...ersons 2 2 Moving and siting the unit 2 2 1 Moving See chapter 1 1 Installation safety considerations 2 2 2 Siting the unit Always refer to the chapter Dimensions and clearances to confirm that there...

Page 8: ...its B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning o...

Page 9: ...let for 30RW units B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For th...

Page 10: ...ts B Evaporator C Refrigerant inlet outlet 30RW only 1 Clearances required for maintenance Power supply NOTE Non contractual drawings Refer to the certified dimensional drawings For the positioning of...

Page 11: ...ed by frequency converter 48 3 r s Power input kW 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 2 5 5 0 5 0 5 0 5 0 5 0 5 0 6 7 6 7 6 7 6 7 Expansion tank volume condenser loop l 8 8 8 8 8 12 12 12 25 25 25 25 25 3...

Page 12: ...r and the pumps the control devices Field connections All connections to the system and the electrical installations must be in full accordance with all applicable local codes The Carrier 30RW and 30R...

Page 13: ...pumps 30RW 30RWA option 116C No Description 30RW 30RWA 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1...

Page 14: ...variable speed pump No Description 30RW 060 070 080 090 110 120 135 150 160 185 210 245 275 300 1 Nominal efficiency at full load and nominal voltage 83 2 83 2 83 2 83 2 86 1 86 1 86 1 87 6 87 6 87 6...

Page 15: ...low leaving water temperature and use of antifreeze is required 2 30RW units without hydronic module operating below 20 C entering condenser water temperature require the use of a three way valve cont...

Page 16: ...r units without hydronic module that have a fixed condenser flow rate Units with a hydronic module have a variable flow rate and no minimum fixed flow rate The minimum flow rate is optimised by unit c...

Page 17: ...er mixing of the liquid water or brine Refer to the examples below Bad Bad Good Good 5 10 Maximum water loop volume evaporator and condenser side Units with hydronic module incorporate an expansion ta...

Page 18: ...er flow rate l s Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30RW 045 5 30RW 060 6 30RW 070 7 30RW 080 8 30RW 090 9 30RW 110 10 30RW 120 11 30RW 135 12 30RW 150 13 30RW 160 185 14 30RW 210 245 15 30...

Page 19: ...at the main disconnect switch Before connecting electric power cables it is imperative to check the correct order of the 3 phases L1 L2 L3 Non certified drawings Refer to the certified dimensional dr...

Page 20: ...switch are designed for the number and type of wires listed in the table below The calculations are based on the maximum machine current see electrical data tables For the design the following standar...

Page 21: ...0 Ohm m are desirable A neutral environment favours maximum specific resistance values For electric conductivity values in the order of 20 60 mS m can be recommended 10 pH Ideal case pH neutral at 20...

Page 22: ...y Damage due to freezing is not covered by the warranty IMPORTANT Depending on the climatic conditions in your area you must Add ethylene glycol with an adequate concentration to protect the installat...

Page 23: ...Pressure gauge to measure the plate heat exchanger pressure drop to be isolated with valve No 5 if not used 7 Plate heat exchanger Legend Components of unit and hydronic module 1 Victaulic screen filt...

Page 24: ...The air cooled condenser must always be used with a subcooler normally with 8 K subcooling 8 2 General Refrigerant pipe sizing must be carried out taking account of the following constraints Oil retur...

Page 25: ...a saturated suction temperature of 4 C and 8 K subcooling Table 3 shows the correction factors to be applied to the values from Table 2 if the operating conditions are different from those previously...

Page 26: ...ing temperature C Outside pipe diameter inch 1 2 5 8 3 4 7 8 1 1 8 1 3 8 1 5 8 2 1 8 2 5 8 3 1 8 3 5 8 4 1 8 27 0 81 1 48 2 39 3 66 7 14 12 06 18 64 37 21 63 94 99 81 145 60 201 98 32 0 84 1 51 2 46 3...

Page 27: ...the forced start command refer to the controls manual and let the pump run for two con secutive hours to clean the hydronic circuit of the system presence of solid contaminants Read the plate heat ex...

Page 28: ...300 1 2 3 4 0 25 50 75 100 125 150 175 200 2 4 6 8 10 50 100 150 200 250 0 5 10 15 20 25 2 1 4 3 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 9 3 Available static system pressure evaporator side Sing...

Page 29: ...0 50 100 150 200 250 0 5 10 15 20 25 30 0 50 100 150 200 250 0 5 10 15 20 25 30 2 1 3 10 2 Available static system pressure condenser side Single pump Legend 1 30RW 020 2 30RW 025 030 3 30RW 040 4 30R...

Page 30: ...st efficiency with variation of the water flow rate and the number of fans required for any thermal load and outside temperature conditions The electronic board AUX1 integrated in the control box of t...

Page 31: ...This is the first fan to start in each circuit and the last fan to stop A fan configuration with fixed speed fans permits year round system operation down to 0 C outside temperature A fan configurati...

Page 32: ...B from fan 2 of each circuit If fans 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH4 for circuit A and CH5 to CH8 for circuit B from fan 1 Single circuit condenser Circuit Possibl...

Page 33: ...its A and B If fan 1 has variable speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 2 If fan 1 has fixed speed the outputs assigned to board AUX1 are CH1 to CH8 from fan 1 Dual circuit...

Page 34: ...at all safety devices are operational especially that the high pressure switches are switched on and that the alarms are acknowledged 13 3 Operation of two units in master slave mode The control of a...

Page 35: ...relation to the materials and coatings to which they are applied This is also the case for the products originally supplied by Carrier 14 Major system components and operation data 14 1 Compressors 30...

Page 36: ...ow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If there are no regulations or to compl...

Page 37: ...onents that do not comply must be changed Test pressures above the respective component design pressure must not be applied annex B and D After repair or significant modifications or significant syste...

Page 38: ...expansion device must be between 12 and 14 C This corresponds to an actual subcooling temperature of between 6 and 8 K at the condenser outlet depending on the unit type Actual subcooling is equal the...

Page 39: ...the vacuum pump pressure gauge ATTENTION Do not use a megohmmeter and do not place any stress on the compressor motor when the system has been ecacuated There is a risk of internal short circuits bet...

Page 40: ...02 5 23 14 33 89 39 16 23 5 54 64 59 07 4 75 0 34 6 57 14 25 34 54 39 79 23 75 55 1 59 5 5 1 66 7 86 14 5 35 19 40 41 24 55 55 59 94 5 25 2 94 9 11 14 75 35 83 41 03 24 25 56 01 60 37 5 5 4 19 10 33 1...

Page 41: ...tions contactors disconnect switch and transformer Check the status of the contactors and fuses Carry out a quick test refer to the 30RW RWA Pro Dialog Plus controls manual Mechanical checks Verify th...

Page 42: ...ment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Electrical circuit wiring has b...

Page 43: ...loop volume litres Calculated volume litres 3 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 020 045 2 5 liters nominal kW capacity for air conditioning units 30RW 30RWA 060 300 Pr...

Page 44: ...tor LWT Condenser EWT Condenser LWT Circuit A suction pressure Circuit B suction pressure Circuit A discharge pressure Circuit B discharge pressure Circuit A suction temperature Circuit B suction temp...

Reviews: