Reading and Writing map (Cont.)
Input Register (Function 04) - CHILLER 2
Address
Description
Comment
H0101
Reserve
H0102
Error Code
H0103
Outlet Water Temperature (INT)
H0104
Inlet Water Temperature (INT)
Chiller <2, referring to Chiller unit. Chiller> 2, referring to the system.
H0105
Outdoor Temperature
H0106
Middle Condenser Temperature
H0107
Suction Temperature
H0108
Discharge Temperature Comp.1
H0109
Discharge Temperature Comp.2
H010A
Saturated Suction Temperature
H010B
Reserve
H010C
Reserve
H010D
DIP setting
See in the detailed DIP setting section
H010E
Comp Current 1
Multiply the reading by 0.25
H010F
Comp Current 2
Multiply the reading by 0.25
H0110
Digital Inputs (DI)
Bit5-0 means entries 6-1 (See Table "DI")
H0111
Digital Outputs (DO)
Bit4-0 means outputs 5-1 (See Table "DO")
H0112
Reserve
H0113
Reserve
H0114
Reserve
H0115
Cond. Motor Speed
RPM
H0116
Reserve
H0117
Reserve
H0118
Main Software Version
H0119
Reserve
H011A
Outlet Water Temperature (FRACTION)
H011B
Inlet Water Temperature (FRACTION)