background image

5

1 - INTRODUCTION

The 61XWH units are designed to cool and heat water (or brine) 

for the air conditioning and heating of buildings and industrial 

processes.
Prior to the initial start-up of the 61XWH units, the people involved 

in the on-site installation, start-up, operation, and maintenance of 

this unit must be thoroughly familiar with these instructions and the 

specific project data for the installation site (Machine room, etc).

They are designed for an operating life of 15 years by assuming 

a 75% utilisation factor; that is approximately 100,000 operating 

hours.
This manual provides the necessary information to familiarize 

yourself with the control system before performing start-up 

procedures. The procedures in this manual are arranged in the 

sequence required for machine installation, start-up, operation 

and maintenance.
Always ensure that all required safety measures are followed, 

including those in this document, such as: wearing protective 

clothing (gloves, safety glasses and shoes) using appropriate tools, 

employing qualified and skilled technicians (electricians, refrigeration 

engineers) fully trained in the use of flammable refrigerants and 

following local regulations (see annexe E in EN 378 -4 - Guidelines 

for repairs of equipment using flammable refrigerants).
To  find  out,  if  these  products  comply  with  European  directives 

(machine safety, low voltage, electromagnetic compatibility, 

equipment under pressure etc.) check the declarations of 

conformity for these products. 

According to ISO-817, R1234ze(E) is classified in safety group 

A2L:  lower  flammability.  One  of  the  characteristic  of  this 

refrigerant is the absence of flammable mixture with air under 

21°C  of  ambiance  and  controlled  humidity  conditions. 

However when humidity or temperature goes up, this 

refrigerant  can  become  flammable  and  can  represent  a 

potential  danger  if  flammability  risks  are  not  properly 

mitigated within the machine room installation.

Local building codes and safety standards shall be followed. 

In absence of local codes and standards, please refer to EN-378 

(2012) (Safety requirements for substances classified A2) or to 

ISO-5149  (2014)  (for  substances  classified A2L)  as  a  guide. 

Customer  shall  obtain  approval  from  the  local  building 

authorities.
Carrier also provides additional guidelines for the safe use 

of  R1234ze(E)  refrigerant  that  should  be  added  to  the 

requirements of safety standards and building codes to insure 

that the risks are minimised to acceptable levels. 

Refer to paragraph 2 “additional guidelines for safe use of 

R1234ze(E) refrigerant in machinery rooms”

For  further  details  on  physical  properties,  flammability  & 

toxicity  characteristics,  hazards  Identification,  installation 

safety requirements, etc, refer to standards such as: 

• ASHRAE 34, EN 378, ISO-817 and ISO-5149

• 

Safety  Data  Sheet  (SDS)  supplied  by  the  refrigerant 

manufacturer

• 

European  union’s  REACH  database  (Registration, 

Evaluation, Authorisation and Restriction of Chemicals)

1.1 - Installation safety considerations

The 61XWH heat pumps are classified as “indirect heat exchange 

system” and are designated to be installed in a special machinery 

room (Class C as per ISO-5149 and EN-378) where 

only 

authorized personnel 

have access, who are acquainted with 

general and special safety precautions of the establishment and 

are  qualified  and  trained  in  monitoring  and  maintenance.  The 

access limitation device must be installed by the customer (e.g. 

cut-off, enclosure). 
The refrigerant R1234ze(E) falls into refrigerant safety group A2L 

in accordance to ISO-5149 and A2 in accordance to EN-378. No 

Charge limitations apply for the level of occupancy is ‘C’. Please 

refer to these standards for further details. This level needs to be 

confirmed by the customer.

Refer also to paragraph 2 for “Additional guidelines for safe use 

of R1234ze(E) refrigerant in machinery rooms”
After the unit has been received, when it is ready to be installed 

or reinstalled, and before it is started up, it must be inspected for 

damage. Check that the refrigerant circuit(s) is (are) intact, 

especially that no components or pipes have shifted (e.g. following 

a shock). If in doubt, carry out a leak tightness check and verify 

with the manufacturer that the circuit integrity has not been 

impaired. If damage is detected upon receipt, immediately fill a 

claim with the shipping company.
Carrier strongly recommends employing a specialised company 

to unload the machine.
It is compulsory to wear personal protection equipment.

Do not remove the skid or the packaging until the unit is in its final 

position. These units can be moved with a fork lift truck, as long 

as the forks are positioned in the right place and direction on the 

unit. 
The units can also be lifted with slings, using only the designated 

lifting points marked on the unit.
Use slings or lifting beams with the correct capacity, and always 

follow the lifting instructions on the certified drawings supplied with 

the unit. Do not tilt the unit more than 15°.
Safety is only guaranteed, if these instructions are carefully 

followed. If this is not the case, there is a risk of material 

deterioration and injuries to personnel.

Never cover any protection devices.
This applies to the relief valves in the refrigerant or heat transfer 

medium circuits, and the pressure switches.
Ensure that the valves are correctly installed, before operating the 

unit.
DO NOT OBSTRUCT ANY PROTECTIVE DEVICES:

This applies to any fusible plugs, rupture disks and valves fitted 

on the refrigerant or heat transfer fluid circuits. Check whether the 

original protection plugs are still present at the valve outlets. These 

plugs are generally made of plastic and should not be used. If they 

are still present, please remove them. Fit devices at the valve or 

discharge piping outlets to prevent the penetration of foreign 

bodies (dust, building debris, etc.) and atmospheric agents (water 

can form rust or ice). These devices, as well as the discharge 

piping, must not impair operation or lead to a pressure drop that 

is higher than 10% of the set pressure.
CLASSIFICATION AND CONTROL:
In accordance with the Pressure Equipment Directive and national 

usage monitoring regulations in the European Union, the protective 

devices fitted to these machines are classified as follows:

Safety 

device

(1)

Device for damage 

limitation in the event of an 

external fire

(2)

Refrigerant Side

High pressure safety loop

(3)

X

External relief valve

(4)

X

Rupture disk

X

Heat transfer fuid side

External relief valve

(5)

(5)

(1)  Classified for protection in normal service situations.
(2)  Classified for protection in abnormal service situations. These accessories are 

sized for fires with a thermal flow of 10kW/m². No combustible matter should be 

placed within 6.5m of the unit.

(3)  High pressure safety loop = SRMCR as described in component section of this 

manual and in electrical diagram.

(4)  The instantaneous overpressure limitation of 10% of the operating pressure 

does not apply to this abnormal service situation.

 

The control pressure can be higher than the service pressure. In this case, either

 

the design temperature or the high pressure switch ensures that the service 
pressure is not exceeded in normal service situations.

(5)  The selection of these relief valves must be made by the personnel responsible
 

for completing the hydraulic installation.

Summary of Contents for AquaForce PUREtec 61XWH-ZE 03

Page 1: ...erature water source heat pump AquaForce PUREtec with R1234ze E 61XWHLZE 03 17 61XWH ZE 03 17 61XWHHZE 03 10 15 I N S T A L L A T I O N O P E R A T I O N A N D M A I N T E N A N C E M A N U A L Original document ...

Page 2: ...2 ...

Page 3: ...8 6 1 Operating limits 18 6 2 Minimum chilled water flow 18 6 3 Maximum chilled water flow 18 6 4 Condenser water flow rate 18 6 5 Standard and optional number of water passes 18 6 6 Evaporator and condenser water flow rates 18 6 7 Variable flow evaporator 19 6 8 System minimum water volume 19 6 9 Evaporator pressure drop curves 20 6 10 Condenser pressure drop curves 20 7 WATER CONNECTIONS 21 7 1 ...

Page 4: ...RD MAINTENANCE 27 11 1 Level 1 maintenance 27 11 2 Level 2 maintenance 27 11 3 Level 3 or higher maintenance 27 11 4 Tightening of the electrical connections 28 11 5 Tightening torques for the main bolts and screws 29 11 6 Evaporator and condenser maintenance 29 11 7 Compressor maintenance 29 11 8 Expansion valves maintenance 29 11 9 High pressure safety loop periodic test 30 12 FINAL SHUTDOWN 31 ...

Page 5: ...ance to EN 378 No Charge limitations apply for the level of occupancy is C Please refer to these standards for further details This level needs to be confirmed by the customer Refer also to paragraph 2 for Additional guidelines for safe use of R1234ze E refrigerant in machinery rooms After the unit has been received when it is ready to be installed or reinstalled and before it is started up it mus...

Page 6: ...ns forexample those of European standards EN 378 These standards include a sizing method and examples for configuration and calculation Under certain conditions they permit connection of several valves to the same discharge pipe Carrier recommends using flexible hose to connect the relief valves to discharge pipe Special care shall be taken so that coupling to discharge pipe is not creating mechan...

Page 7: ...on device This valve is situated on the liquid line before the filter drier In case of presence of a shut off valve on the suction line between evaporator and compressor factory option n 92 never close at the same time the shut off valve situated on the discharge line between compressor and condenser One exception can be made in case of compressor removal from the refrigerant circuit As a conseque...

Page 8: ...ernal walls and on non protected steel surfaces 1 4 Repair safety considerations Equip the engineers that work on the unit with the protections described in section 1 3 above It is compulsory to wear personal protection equipment and a detector of explosive atmospheres The insulation must be removed and warming up must be limited by using a wet cloth Before opening the unit always ensure that the ...

Page 9: ...ir recovery Do not incinerate ATTENTION Only use refrigerant R1234ze E in accordance withAHRI 700 2014 Air conditioning Heating and Refrigeration Institute The use of any other refrigerant may expose users and operators to unexpected risks Do not attempt to remove refrigerant circuit components or fittings while the machine is under pressure or while it is running Be sure pressure is at 0 kPa and ...

Page 10: ...permitted loading at the site is adequate or that appropriate strenghtening measures have been taken the unit is installed level on an even surface maximum tolerance is 5 mm in both axes there is adequate space above the unit for air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAU...

Page 11: ... supplied with the unit or available on request For the positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings 61XWHLZE 61XWH ZE 61XWHHZE A B C D E F G H Model Dimensions in mm 3 1594 723 981 2724 982 141 3 141 3 2600 5 1745 891 1041 3059 1039 168 3 168 3 2900 7 1968 1007 1079 3290 1170 219 1 219 1 3100 Legend All dimensions ...

Page 12: ... points weight distribution and centre of gravity coordinates please refer to the dimensional drawings 61XWHLZE 61XWH ZE A B C D E F G H Model Dimensions in mm 10 2002 1432 1124 4730 1124 219 1 219 1 4500 14 2070 1432 1148 4730 1237 219 1 219 1 4500 15 2305 1458 1399 4790 1264 219 1 219 1 4500 17 2305 1458 1399 4790 1264 219 1 219 1 4500 61XWHHZE A B C D E F G H Model Dimensions in mm 10 2002 1432...

Page 13: ...g 88 138 195 140 195 teq CO2 0 6 1 0 1 4 1 0 1 4 Circuit B kg 140 195 teq CO2 1 0 1 4 Oil standard unit HATCOL4496 Circuit A l 20 20 25 20 25 25 25 Circuit B l 20 25 25 25 Capacity control Touch Pilot electronic expansion valves EXV Unit minimum stage 50 50 50 25 25 25 25 Evaporator Multi pipe flooded type Water volume l 61 101 154 293 321 354 354 Water connections Victaulic in 5 6 8 8 8 8 8 Drain...

Page 14: ...rrent drawn Un 10 2 Circuit A A 240 356 546 356 546 546 527 Circuit B A 356 546 546 527 Option 81 A 712 1092 1092 1054 61XWHHZE Model 3 5 7 10 14 15 17 Maximum start up current Standard unit 1 Circuit A A 1210 1828 1919 1828 1919 Circuit B A 1828 1919 Option 81 A 2188 Maximum start up current Star delta start option 2 Circuit A A 388 587 587 Circuit B A 587 Transient 150ms A 1210 1828 1828 Option ...

Page 15: ...on minimum requirements for improving the safety and health protection of workers potentially at risk from explosive atmospheres The electrical equipment is not designed for compliance to 2014 34 EUdirectiveforequipmentandprotectivesystemsintendedforuseinpotentially explosiveatmospheres Thecomplianceofthebuildinginstallationwitharticle3Prevention of and protection against explosions shall be achie...

Page 16: ...ermissible 2 and is therefore acceptable AB 406 400 6 BC 400 399 1 A 400 394 6 5 3 Power connection disconnect switch Units connection points 61XWH 3 to 7 1 per unit 61XWH 10 to 17 1 for circuit A 1 for circuit B 5 4 Recommended wire sections Wire sizing is the responsibility of the installer and depends on the characteristics and regulations applicable to each installation site The following is o...

Page 17: ...the selection Note The currents considered are given for a machine equipped with a hydronic kit operating at maximum current 5 5 Power cable entry The power cables can enter the unit control box from above the unit A removable aluminium plate on the upper part of the control box face allows introduction of the cables Refer to the certified dimensional drawing for the unit The plate fixing on the e...

Page 18: ...If the system flow is less than the minimum unit flow rate the evaporator flow can be recirculated as shown in the diagram For minimum chiller flow rate 1 2 Legend 1 Evaporator 2 Recirculation 6 3 Maximum chilled water flow The maximum chilled water flow is limited by the permitted pressure drop in the evaporator It is provided in the table in chapter 7 6 Bypass the evaporator as shown in the diag...

Page 19: ...hichever the system the water loop minimum volume is given by the formula Volume Cap kW x N litres Application N Normal air conditioning 3 25 Process type cooling 6 5 where Cap is the nominal system heating capacity kW at the nominal operating conditions of the installation This volume is necessary for stable operation It is often necessary to add a buffer water tank to the circuit in order to ach...

Page 20: ...120 Pressure drop kPa Water flow rate l s Legend 1 Model 3 4 Model 10 2 Model 5 5 Model 14 3 Model 7 6 Model15 17 6 10 Condenser pressure drop curves Units with two condenser passes standard 1 2 3 4 5 6 10 20 30 40 50 60 70 80 90 100 110 120 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure drop kPa Water flow rate l s Legend 1 Model 3 4 Model 10 2 Model 5 5 Model 14 3 Model 7 6 Model15 17 Units w...

Page 21: ...pper with a risk of perforations by corrosion by puncture If possible keep below 125 mg l SO4 2 sulphate ions can cause perforating corrosion if their content is above 30 mg l No fluoride ions 0 1 mg l No Fe2 and Fe3 ions with non negligible levels of dissolved oxygen must be present Dissolved iron 5 mg l with dissolved oxygen 5 mg l Dissolved silicon silicon is an acid element of water and can al...

Page 22: ...t size M 16 171 210 Nm 7 5 Operation of two units in master slave mode The control of a master slave assembly is in the entering water and does not require any additional sensors standard configuration It can also be located in the leaving water In this case two additional sensors must be added on the common piping All parameters required for the master slave function must be configured using the ...

Page 23: ...e qualification re testing and re testing dispensation Follow the regulations on monitoring pressurised equipment It is normally required that the user or operator sets up and maintains a monitoring and maintenance file If no regulations exist or to complement regulations follow the control programmes of EN 378 If they exist follow local professional recommendations Regularly inspect the condition...

Page 24: ...ices At the condenser outlet a part of the liquid is expanded via the secondary EXV in one of the heat exchanger circuits and then returns as a gas This expansion permits increase of the liquid sub cooling of the rest of the flow that penetrates the evaporator via the principal EXV This permits increasing the cooling capacity of the system as well as its efficiency 9 3 Detection of the air pressur...

Page 25: ...oil the main contactor opens which causes the compressor to lose power and stop The operation of this safety loop is electromechanical it is not based on software or an electronic component 9 8 3 Restart after high pressure detection After detecting the overpressure it is necessary to manually reset the switched HPS s Using a dull tool with a diameter of less than 6 mm if the PZHH HPS is deactivat...

Page 26: ...r side service pressure to 21 bar standard 10 bar Covers applications with a high water column evaporator side typically high buildings 3 17 21 bar condenser 104A Reinforced condenser for extension of the maximum water side service pressure to 21 bar standard 10 bar Covers applications with a high water column condenser side typically high buildings 3 17 Reversed evaporator water connections 107 E...

Page 27: ...quired Check the filter condition Check the good operation of the air pressurization detection function of the electrical cabinet Check the presence and the condition of the electrical protection devices Replace the fuses every 3 years or every 15000 hours age hardening Replace the control box fan every five years Check that control box ventilation system is not obstructed this shall include the f...

Page 28: ...ions for the compressor power terminals These precautions must be applied during an intervention that requires the removal of the power conductors connected to the compressor supply terminals The tightening nut of terminal 6 supporting the isolator 7 must never be loosened as ist ensures terminal tightness and compressor leak tightness The tightening of phase lug 4 must apply the torque between co...

Page 29: ...pproximately 0 4 bar which should be subtracted from the two oil pressure measurements to give the oil filter pressure drop 11 7 2 Compressor rotation control Correct compressor rotation is one of the most critical application considerations Reverse rotation even for a very short duration damages the compressor and can even destroy it The reverse rotation protection scheme must be capable of deter...

Page 30: ...ure part of the circuit compressor discharge 2 Reset all activated alarms 3 Activate the HP test mode for the corresponding circuit via the control interface Enable Quick Test Mode Quick Test Menu QCK_TEST parameter active Activate the high pressure test for the desired circuit Menu Quick Test parameter HP_TEST to 0 for circuit A or 1 for the B circuit The corresponding circuit starts to perform t...

Page 31: ...part of the unit can be recycled for another purpose 12 3 Fluids to be recovered for treatment Refrigerant Energy transfer fluid depending on the installation water brine etc Compressor oil 12 4 Materials to be recovered for recycling Steel Copper Aluminium Plastics Polyurethane foam insulation 12 5 Waste electrical and electronic equipment WEEE At the end of its life this equipment must be disass...

Page 32: ...trical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chilled water valves are open All chilled water piping is connected properly All air has been vented from the chilled water circuit The unit is switched off again after the pump test has been completed Chille...

Page 33: ... your local electricity supplier at once and ensure that the unit is not switched on until corrective measures have been taken Check cooler water loop Water loop volume litres Calculated volume litres 3 25 litres nominal kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop f...

Page 34: ...34 ...

Page 35: ...35 ...

Page 36: ... No 10190 11 2020 Supersedes order No 10190 06 2018 Manufacturedby CarrierSCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union ...

Reviews: