13
4 - PHYSICAL AND ELECTRICAL DATA
4.1 - Physical data
61XWHLZE/61XWH-ZE/61XWHHZE
Model
3
5
7
10
14
15
17
Sound levels - standard unit
Sound power level
(1)
dB(A)
93
97
100
100
103
103
103
Sound pressure level at 1m
(2)
dB(A)
76
80
82
81
84
84
84
Sound levels - option 257
(3)
Sound power level
(1)
dB(A)
-
94
98
97
101
101
101
Sound pressure level at 1m
(2)
dB(A)
-
76
80
78
82
82
82
Dimensions - 61XWHLZE/61XWH-ZE
Length
mm
2724
3059
3290
4730
4730
4790
4790
Width
mm
981
1041
1079
1125
1148
1399
1399
Height
mm
1594
1745
1968
2002
2070
2305
2305
Dimensions - 61XWHHZE
Length
mm
2724
3059
3290
4730
-
4790
-
Width
mm
981
1041
1079
1125
-
1417
-
Height
mm
1594
1745
1968
2002
-
2305
-
Operating weight
(4)
kg
2054
2942
4147
7265
8031
9519
9519
Compressors
Semi-hermetic 06T screw compressors, 50 r/s
Circuit A
-
1
1
1
1
1
1
1
Circuit B
-
-
-
-
1
1
1
1
Refrigerant - 61XWHLZE
(5)
R1234ze
Circuit A
kg
107
168
237
154
176
237
226
teq CO
2
0,7
1,2
1,7
1,1
1,2
1,7
1,6
Circuit B
kg
-
-
-
154
187
237
231
teq CO
2
-
-
-
1,1
1,3
1,7
1,6
Refrigerant - 61XWH-ZE
(5)
R1234ze
Circuit A
kg
97
153
215
140
160
215
205
teq CO
2
0,7
1,1
1,5
1,0
1,1
1,5
1,4
Circuit B
kg
-
-
-
140
170
215
210
teq CO
2
-
-
-
1,0
1,2
1,5
1,5
Refrigerant - 61XWHHZE
(5)
R1234ze
Circuit A
kg
88
138
195
140
-
195
-
teq CO
2
0,6
1,0
1,4
1,0
-
1,4
-
Circuit B
kg
-
-
-
140
-
195
-
teq CO
2
-
-
-
1,0
-
1,4
-
Oil - standard unit
HATCOL4496
Circuit A
l
20
20
25
20
25
25
25
Circuit B
l
-
-
-
20
25
25
25
Capacity control
Touch Pilot, electronic expansion valves (EXV)
Unit minimum stage
%
50
50
50
25
25
25
25
Evaporator
Multi-pipe flooded type
Water volume
l
61
101
154
293
321
354
354
Water connections (Victaulic)
in
5
6
8
8
8
8
8
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
Condenser
Multi-pipe flooded type
Water volume
l
55
103
148
316
340
426
426
Water connections (Victaulic)
in
5
6
8
8
8
8
8
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
(1) In dB ref=10
-12
W, (A) weighting. Dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance
with ISO 9614-1.
(2) In dB ref 20µPa, (A) weighting. Dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated
from the sound power level Lw(A).
(3) Option 257 = Low noise level
(4) Weight shown is guideline only. Please refer to the unit nameplate
(5) Refrigerant charge shown is guideline only. Charge may differ according to options. Please refer to the unit nameplate