4.3 -
Short-circuit stability current
451
501
601
651
851
1001
1101
1201
1301
Value with unspecified upstream protection
Short-term current at 1s-Icw-kA rms
5,0
6,0
6,0
6,0
5,0
6,0
6,0
6,0
6,0
Admissible peak current - Ipk-kA pk
7,1
8,5
8,5
8,5
7,1
8,5
8,5
8,5
8,5
Max. value with upstream protection (circuit breaker)
Conditional short-circuit current Icc-kA rms
50
50
50
50
50
50
50
50
50
Reference number
(1)
NSX400-
630-
NSX630- NSX630- NSX630- NSX400-
630-
NSX630- NSX630- NSX630- NSX630-
(1) Earthing system type
(2) If another current limitation protection system is used, its time-current and thermal constraints (l²t) trip characteristics must be at least equivalent to those of the
recommended Schneider circuit breaker.
The short circuit stability current values above are suitable with TN system.
4.4 -
Compressor electrical data
Compressor nominal voltage/frequency: 380V/60Hz
Compressor
I Nom (A)
(1)
I Max (A)
(2)
MHA (A)
LRDA (A)
Cosine phi
nom
(1)
Cosine phi
max
(2)
06TUX483
134
227
240
1537
0,88
0,90
06TUX554
154
265
280
1537
0,88
0,90
06TVX680
184
304
322
2179
0,88
0,90
06TVX753
195
336
356
2179
0,88
0,90
(1) Value at standard Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
(2) Value at maximum capacity and nominal voltage.
Legend
MHA - Maximum compressor operating current, limited by the unit (current given for maximum capacity at 342 V)
LRDA - Locked rotor current for delta connection
4.5 -
Compressor usage per circuit (A, B)
30XW-VZE/30XWHVZE
451
501
601
651
851
1001
1101
1201
1301
06TUX483
A
-
-
-
AB
-
-
-
-
06TUX554
-
A
-
-
-
AB
B
-
-
06TVX680
-
-
A
-
-
-
A
AB
-
06TVX753
-
-
-
A
-
-
-
-
AB
4 - PHYSICAL AND ELECTRICAL DATA