12
4 - PHYSICAL AND ELECTRICAL DATA
4.1 -
Physical data
30XW-VZE/30XWHVZE
451
501
601
651
851
1001
1101
1201
1301
Sound levels - standard unit
Sound power level
(1)
dB(A)
103
103
103
103
104
104
104
104
104
Sound pressure level at 1 m
(2)
dB(A)
85
85
85
85
85
85
85
85
85
Sound levels - standard unit + option 257
(3)
Sound power level
(1)
dB(A)
100
100
100
100
101
101
101
101
101
Sound pressure level at 1 m
(2)
dB(A)
82
82
82
82
82
82
82
82
82
Dimensions - standard unit
Length
mm
3059
3059
3290
3290
4730
4730
4730
4730
4730
Width
mm
1087
1087
1237
1237
1164
1164
1264
1264
1264
Height
mm
1743
1743
1948
1948
1997
1997
2051
2051
2051
Operating weight
(4)
kg
3223
3261
4263
4267
7477
7553
7731
7932
7970
Compressors
Semi-hermetic 06T screw compressors, 50 r/s
Circuit A
-
1
1
1
1
1
1
1
1
1
Circuit B
-
-
-
-
-
1
1
1
1
1
Refrigerant - standard unit
R1234ze( E )
Circuit A
kg
130
130
180
175
120
120
115
115
110
teq CO
2
0,1
0,1
0,2
0,2
0,1
0,1
0,1
0,1
0,1
Circuit B
kg
-
-
-
-
120
120
120
115
110
teq CO
2
-
-
-
-
0,1
0,1
0,1
0,1
0,1
Refrigerant - option 330
R515B
Circuit A
kg
132
132
183
178
122
122
117
117
112
teq CO
2
38,7
38,7
53,6
52,2
35,7
35,7
34,3
34,3
32,8
Circuit B
kg
-
-
-
-
122
122
122
117
112
teq CO
2
-
-
-
-
35,7
35,7
35,7
34,3
32,8
Oil - standard unit
Circuit A
l
20
20
25
25
20
20
25
25
25
Circuit B
l
-
-
-
-
20
20
20
25
25
Capacity control
SmartVu
TM
, inverter-driven compressor, electronic expansion valve (EXV)
Minimum capcity
%
20
20
20
20
10
10
10
10
10
Evaporator
Multi-pipe flooded type
Water volume
l
106
106
154
154
297
297
297
297
297
Water connections (Victaulic)
in
6
6
8
8
8
8
8
8
8
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
Condenser
Multi-pipe flooded type
Water volume
l
112
112
165
165
340
340
340
340
340
Water connections (Victaulic)
in
6
6
8
8
8
8
8
8
8
Drain and vent connections (NPT)
in
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Max. water-side operating pressure
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
(1) In dB ref=10
-12
W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information,
calculated from the sound power level Lw(A).
(3) Option 257 = Low noise level
(4) Weight shown is guideline only. Please refer to the unit nameplate