Options
No. Description
Advantages
Use for 30XW-V
range
Dual relief valves on 3-way
valve
194 Three-way valve upstream of dual relief valves
on the evaporator and the oil separator
Valve replacement and inspection
facilitated without refrigerant loss.
Comforms to European standard EN378/
BGVD4
580-1710
Compliance with Swiss
regulations
197
Additional tests on the water heat exchangers.
Additional supply of PED documents,
supplementary certificates and test certificates.
Conformance with Swiss regulations
580-1710
Compliance with Russian
regulations
199
EAC certification
Conformance with Russian regulations
580-1710
Compliance with Australian
regulations
200 Unit approved to Australian code
Conformance with Australian regulations
580-1710
Low noise level
257 Evaporator piping sound insulation
3 dB(A) quiter than standard unit
580-1710
Welded evaporator water
connection kit
266
Victaulic piping connections with welded joints.
Easy installation
580-1710
Welded condenser water
connection kit
267
Victaulic piping connections with welded joints.
Easy installation
580-1710
Flanged evaporator water
connection kit
268
Victaulic piping connections with flanged joints.
Easy installation
580-1710
Flanged condenser water
connection kit
269
Victaulic piping connections with flanged joints.
Easy installation
580-1710
Thermal compressor
insulation
271 The compressor is covered with a thermal
insulation layer
Prevents air humidity to condensate on the
compressor surface
580-1710
EMC classification C2, as per
EN 61800-3
282
Additional RFI filters on the unit power line
Reduces electromagnetic interferences.
Increase the variable frequency drive
(VFD) immunity level according to first
environment (so called, residential
environment) requirements and allow its
compliancy with emissions level required in
category C2
580-1710
Compliance with UAE
regulation
318
Additional label on the unit with rated power
input, rated current and EER following AHRI
550/590
Compliance with ESMA standard UAE.S
5010-5:2019.
580-1710
Compliance with Morocco
regulation
327
Specifics documents according Morroco
regulation
Conformance with Morocco regulations
580-1710
10 - OPTIONS
27