6.6 - Number of passes
30XW-V/30XWHV
580
630
810
880
1150
1280
1470
1570
1710
Evaporator
Standard
2
2
2
2
2
2
2
2
2
Option 100C
1
1
1
1
1
1
1
1
1
Condenser
Standard
2
2
2
2
2
2
2
2
2
Option 102C
1
1
1
1
1
1
1
1
1
6.7 -
Evaporator and condenser water flow rates
These below values are given for standard units. For options 100C and 102C, please refer to the unit selection program.
30XW-V/30XWHV
580
630
810
880
1150
1280
1470
1570
1710
Evaporator water flow rate, l/s
Minimum
10
10
13
13
25
25
25
25
25
Maximum
54
54
76
76
170
170
170
170
170
Condenser water flow rate, l/s
Minimum
6
6
8
8
15
15
15
15
15
Maximum
52
52
74
74
170
170
170
170
170
Notes
- Minimum evaporator flow rate based on a water velocity of 0,5 m/s.
- Minimum condenser flow rate based on a water velocity of 0,3 m/s.
6.8 - Minimum temperature difference
The maximum flow rates recommended by Carrier limit unit operation with a ∆T (entering - leaving) of 3 K in the sections shown below:
30XW-V 1570
15
20
25
30
35
40
45
50
0
5
10
15
20
30XW 1570
Evaporator leaving water temperature, °C
Condenser leaving water temperature, °C
30XW-V 1570
15
20
25
30
35
40
45
50
55
0
5
10
15
20
30XW 1710
Evaporator leaving water temperature, °C
Condenser leaving water temperature, °C
Delta_T > 3 K at the condenser
Delta_T > 3 K at the evaporator and the condenser
To achieve a temperature difference of 3 K at the condenser, Carrier recommends the installation of option 102C.
To achieve a temperature difference of 3 K at the evaporator, Carrier recommends the installation of option 100C.
6 - APPLICATION DATA
18