15
S
Secure mounting plastic to wall using two screws and anchors provided.
S
Adjust length and routing of each wire to reach each wire entry on the
connector backplate. Strip 1/4--in (6.4 mm) of insulation from each wire.
S
Match and connect thermostat wires to proper terminals on control backplate.
d
See wiring diagrams in Section 8.0.
S
Push any excess wire into the wall. Seal hole in wall to prevent any air leaks.
Air leaking from behind the wall can affect measured temperature and
humidity, and can affect operation.
S
Attach Infinity System Control to the mounting plastic by lining up the plastic
guides on the back of the control with the opening on the mounting plastic and
push on.
S
Perform installation of all other system equipment (i.e. dampers, humidifier,
ventilator, UV lights, etc.). See the equipment and device installation
instructions for details.
S
Turn on power to equipment.