T-364
3.11 CONTROLLER PRE
−
TRIP TEST CODES
Table 3
−
7 Controller Pre-trip Test Codes (Sheet 1 of 6)
NOTE
“Auto” or “Auto1” menu includes the: P0, P1, P2, P3, P4, P5, P6 and rSLts. “Auto2” menu in-
cludes P0, P1, P2, P3, P4, P5, P6, P7, P8, P9, P10 and rSLts. “Auto3” menu includes P0, P1,
P2, P3, P4, P5, P6, P7 and P8.
P0-0
Pre-Trip Initiated:
Configuration
Display, Indicator
Lamps, LEDs, and
Displays
Container identifier code, Cd18 Software Revision Number, Cd20 Container Unit
Model Number, & configuration database identifier CFMMYYDD are displayed in
sequence.
Next the unit will indicate the presence or non-presence of an RMU according to
whether any RMU inquiry messages have been received since the unit was
booted.
Units equipped with Autoslide Enabled (Cnf44) will cause the vent to seek to its
closed position, followed by two sequences of opening to 100% and returning to
the closed position. No other autoslide mode of operation will be available until
the two cycles of opening and closing have completed.
Since the system cannot recognize lights and display failures, there are no test
codes or results associated with this phase of Pretrip. To know if the test passes
the operator must observe that the LCD display elements and the indicator lights
behave as described below.
P1 Tests - Heaters Current Draw:
Heater is turned on, then off. Current draw must fall within specified range.
No other system components will change state during this test.
P1-0
Heaters Turned On
Heater starts in the off condition, current draw is measured, and then the heater
is turned on. After 15 seconds, the current draw is measured again. The
change in current draw is then recorded.
Test passes if the change in current draw test is in the range specified.
P1-1
Heaters Turned Off
Heater starts in the off condition, current draw is measured, and then the heater
is turned on. After 15 seconds, the current draw is measured again. The
change in current draw is then recorded.
Test passes if the change in current draw test is in the range specified.
P2 Tests - Condenser Fan Current Draw:
Condenser fan is turned on, then off. Current draw must fall within
specified range. No other system components will change state during this test.
P2-0
Condenser Fan On
Condenser fan starts in the off condition, current draw is measured, and con-
denser fan is then turned on. After 15 seconds the current draw is measured
again. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P2-1
Condenser Fan Off
Condenser fan is then turned off. After 10 seconds the current draw is meas-
ured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P3 Tests - Low Speed Evaporator Fan Current Draw:
Low speed evaporator fan is turned on, then off. Cur-
rent draw must fall within specified range. No other system components will change state during this test.
P3-0
Low Speed
Evaporator Fan
Motors On
High speed evaporator fans will be turned on for 20 seconds, the fans will be
turned off for 4 seconds, current draw is measured, and then the low speed
evaporator fans are turned on. After 60 seconds the current draw is measured
again. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
P3-1
Low Speed
Evaporator Fan
Motors Off
Low speed evaporator fans are then turned off. After 10 seconds the current
draw is measured. The change in current draw is then recorded.
Test passes if change in current draw test is in the specified range.
Summary of Contents for 69NT40-561-201
Page 2: ......
Page 11: ......
Page 15: ......
Page 29: ......
Page 81: ......
Page 108: ...7 2 T 364 Based on Drawing 62 11753 Figure 7 2 SCHEMATIC DIAGRAM ...
Page 109: ...7 3 T 364 Based on Drawing 62 11753 Figure 7 3 UNIT WIRING DIAGRAM Sheet 1 of 2 ...
Page 110: ...7 4 T 364 Based on Drawing 62 11753 Figure 7 3 UNIT WIRING DIAGRAM Sheet 2 of 2 ...
Page 111: ......
Page 115: ......
Page 116: ......