T-334
4--6
SET POINT
PULL DOWN
RISING
TEMPERATURE
-0.5C
(0.9F)
-0.20C
+.20C
HEATING
HEATING
AIR CIRCULATION
+2.5C
(4.5F)
UNLOADED OPERATION
MODULATED
COOLING
UNLOADED
AIR CIRCULATION
SET POINT
+.20C
HEATING
+2.5C
(4.5F)
FALLING
TEMPERATURE
MODULATED
COOLING
UNLOADED
-0.5C
(0.9F)
AIR CIRCULATION
NOTE: TEMPERATURES INDICATIONS ARE ABOVE OR BELOW SET POINT
START UNLOADED,
TRANSITION TO
ECONOMIZED
OPERATION
-0.20C
Figure 4--3 Controller Operation - Perishable Mode
SET POINT
FALLING
TEMPERATURE
RISING
TEMPERATURE
-0.20C
+.20C
COOLING
ECONOMIZED
AIR CIRCULATION
START UNLOADED,
TRANSITION TO
ECONOMIZED
OPERATION
NOTE: TEMPERATURES INDICATIONS ARE ABOVE OR BELOW SET POINT
AIR CIRCULATION
Figure 4--4 Controller Operation - Frozen Mode