Carrier 58TUA Installation, Start-Up, And Operating Instructions Manual Download Page 11

This furnace is equipped with a manual reset limit switch in
the gas control area. The switch will open and shut off power
to the gas valve if a flame rollout or overheating condition
occurs in the gas control area. DO NOT bypass the switch.
Correct inadequate combustion-air supply, component fail-
ure, or restricted flue gas passageway before resetting the
switch.

Before operating furnace, check each manual reset switch for
continuity. If necessary, press and release button to reset switch.

SEQUENCE OF OPERATION

Using schematic diagram in Fig. 13, follow the sequence of
operation through the different modes. Read and follow diagram
very carefully.

NOTE:

If power interruption occurs during "call for heat" (W/W1

or W/W1 and W2) and if the thermostat is still calling for gas
heating, the control will start a 90-sec blower only on period 2 sec
after power is restored. The red LED will flash code 12 during
90-sec period, after which the LED will be on continuously as long
as no faults are detected. After 90-sec period, furnace will respond
to the thermostat normally.

The blower door must be installed for power to be conducted
through blower door interlock switch ILK to furnace control CPU,
transformer TRAN, inducer motor IDM, blower motor BLWM,
hot surface ignitor HSI, and gas valve GV.

1. Adaptive Heating Mode—Single-Stage Thermostat with

2-Stage Heating

(See Fig. 9 for thermostat connections.)

NOTE:

With high-heat-only switch SW-1 off, low-heat-only

switch SW-2 selects either the low-heat-only operation mode when
on (see item 2 below), or adaptive heating mode when off in
response to a call for heat. (See Fig. 11.) When high-heat-only
switch (SW-1) is in ON position, it always causes high-gas-heat
operation when R-W/W1 circuit is closed, regardless of setting of
low-heat-only switch (SW-2).

This furnace can operate as a 2-stage furnace with a single-
stage thermostat because furnace control CPU includes a
programmed adaptive sequence of controlled operation, which

selects low-gas-heat or high-gas-heat operation. This selection
is based upon the stored history of the length of previous gas
heating on/off periods of the single-stage thermostat.

The furnace will start up in either low- or high-gas heat. If the
furnace starts up in low-gas heat, the control CPU determines
the low-gas heat on time (from 0 to 16 minutes) which is
permitted before switching to high-gas heat.

If power is interrupted, the stored history is erased. When this
happens, the control CPU selects low-gas heat for up to 16
minutes and then switches to high-gas heat, as long as the
thermostat continues to call for heat. Subsequent selection is
based on stored history of thermostat cycle times.

When wall thermostat "calls for heat", R-W/W1 circuit closes.
The furnace control performs a self check, verifies the
low-heat and high-heat pressure switch contacts LPS and HPS
are open, and starts inducer motor IDM in low speed or high
speed as appropriate.

a. Inducer prepurge period—As inducer motor IDM comes up

to low speed or high speed, the low-heat pressure switch
contacts LPS (or LPS and HPS) close to begin a 15 sec
prepurge period.

b. Ignitor warm-up—At end of prepurge period, the hot

surface ignitor HSI is energized for a 17-sec ignitor
warm-up period.

c. Trial-for-ignition sequence—When ignitor warm-up period

is completed, the main gas valve relay contacts MGVR-1
and -2 close to energize the low-heat gas valve solenoid
GV. The gas valve opens, and 24-v power is supplied for a
field-installed humidifier at terminals HUM and C

OM

. The

low-heat gas valve solenoid GV permits gas flow to the
burners where it is ignited. After 5 sec, the ignitor HSI is
de-energized, and a 2-sec flame-proving period begins.

If high-heat gas valve solenoid GV is also energized after
normally closed high-heat pressure switch relay HPSR
closes and after inducer motor IDM goes to high speed and
provides sufficient pressure to close high-heat pressure
switch HPS. HPSR is open while furnace is powered in
standby mode. If high-heat pressure switch HPS fails to
close and low-heat pressure switch LPS closes, furnace
operates at low-heat gas flow rate until high-heat pressure
switch closes.

d. Flame-proving—When burner flame is proved at flame-

proving sensor electrode FSE, the control CPU begins
blower on delay period and continues to hold gas valve GV
open. If burner flame is not proved within 2 sec, the control
CPU closes gas valve GV, and the control CPU repeats the
ignition sequence for up to 3 more trials-for-ignition before
going to ignition lockout. LOCKOUT IS RESET AUTO-
MATICALLY after 3 hr, or by momentarily interrupting
115-v power to furnace, or by interrupting 24-v power at

Table 6—Setup Switch Description

SETUP

SWITCH NO.

NORMAL

POSITION

DESCRIPTION

OF USE

SW-1

Only High-Gas Heat

OFF (Staged Gas

Heat)

Turn switch on to obtain only high-gas-heat operation on any call
for heat regardless of whether R-W/W1, or R-W/W1, -W2 is
closed. SW-1 overrides SW-2.

SW-2

Low-Gas Heat (Adaptive Mode)

OFF (Single-Stage Thermostat)

Turn switch off for installations with single-stage thermostats; con-
trol selects low-gas-heat or high-gas-heat operation based on pre-
vious cycles. Turn switch on for installations with 2-stage thermo-
stats to permit only low-gas-heat operation in response to closing
R-W/W1. High-gas heat is supplied only when R to W/W1 and W2
are closed.

SW-3 and SW4

ON, OFF

Switches control gas heating mode blower off delay. (See Table
7.)

Table 7—Blower Off Delay Setup

Switch (SW) Position

DESIRED HEATING

MODE BLOWER OFF

DELAY (SEC)

SETUP SWITCH

SW-3

SW-4

90

OFF

OFF

135

OFF

ON

180

ON

OFF

225

ON

ON

11

Summary of Contents for 58TUA

Page 1: ...and other safety precautions that may apply Follow all safety codes In the United States refer to the National Fuel Gas Code NFGC NFPA No 54 1996 ANSI Z223 1 1996 In Canada refer to the current edition of the National Standard of Canada CAN CGA B149 1 and 2 M95 Natural Gas and Propane Installation Codes NSCNGPIC and Amendment No 1 Wear safety glasses and work gloves Have fire extinguisher availabl...

Page 2: ...8 in dia holes are located in the top plate 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufacturer s recommendations for equivalent diameters a For 800 CFM 16 in round or 141 2 x 12 in rectangle b For 1200 CFM 20 in round or 141 2 x 191 2 in rectangle c For 1600 CFM 22 in round or 141 2 x 231 4 in rectangle d For airflow requirements above 1800...

Page 3: ... for installation in mobile homes recreation vehicles or outdoors Before installing the furnace refer to the current edition of the NFGC and the NFPA 90B Canadian installations must be installed in accordance NSCNGPIC and all authorities having jurisdiction For a copy of the NFGC NFPA54 Z223 1 contact International Approval Services U S Inc 8501 E Pleasant Valley Road Cleveland OH 44131 or Nationa...

Page 4: ...ry air to areas outside the space containing the furnace return air must also be handled by a duct s sealed to the furnace casing and terminating outside the space containing the furnace Provide ample space for servicing and cleaning Always comply with minimum fire protection clearances shown on unit clearance label This furnace shall not be installed directly on carpeting tile or any combustible ...

Page 5: ...ned space as defined below Return air must not be taken from the room unless an equal or greater amount of air is supplied to the room CONFINED SPACE A confined space is defined as a space whose volume is less than 50 cu ft per 1000 Btuh of total input ratings of all appliances installed in that space A confined space MUST have provisions for supplying air for combustion ventilation and dilution o...

Page 6: ...actors National Association SMACNA or American Society of Heating Refrigerating and Air Conditioning Engineers ASHRAE Or consult factory The Air Systems Design Guidelines reference tables available from your local distributor The duct system should be sized to handle the required system design CFM at the design static pressure When a furnace is installed so that the supply ducts carry air to areas...

Page 7: ...e has been removed Rotate filter supports 180 so filter will rest on support and reinstall Do not reinstall in 17 1 2 in casing Install small U shaped end of filter retaining rod in rear bracket and front of filter retainer rod as shown in Fig 6 Two sets of hardware are needed for furnaces in 24 1 2 in casings using 2 filters for bottom return All hardware is provided for filter installation Never...

Page 8: ...ser leading to furnace The trap can be installed by connecting a tee to riser leading from the furnace Connect a capped nipple into lower end of the tee The capped nipple should extend below level of gas controls See Fig 8 Apply joint compound pipe dope sparingly and only to male threads of each joint The compound must be resistant to action of propane gas Install an accessible manual shutoff valv...

Page 9: ...ervice or maintenance could cause this fuse to blow If fuse replacement is required use ONLY a 3 amp fuse The control will flash code 24 when fuse needs replacement ACCESSORIES 1 Electronic air cleaner EAC A terminal block EAC 1 hot and EAC 2 neutral is provided for EAC connection See Fig 11 The terminals are energized with 115v 1 amp maximum during blower motor operation 2 Humidifier HUM Screw te...

Page 10: ...Wiring Diagram 1 Stage Thermostat and Condensing Unit A99071 115 V FUSED DISCONNECT SWITCH WHEN REQUIRED JUNCTION BOX CONTROL BOX 24 V TERMINAL BLOCK TWO WIRE HEATING ONLY FIVE WIRE 1 STAGE THERMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W Y R G C GND GND GND GND GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208...

Page 11: ...t calls for heat R W W1 circuit closes The furnace control performs a self check verifies the low heat and high heat pressure switch contacts LPS and HPS are open and starts inducer motor IDM in low speed or high speed as appropriate a Inducer prepurge period As inducer motor IDM comes up to low speed or high speed the low heat pressure switch contacts LPS or LPS and HPS close to begin a 15 sec pr...

Page 12: ...gh heat only switch SW 1 is on it always causes high gas heat operation when R W1 circuit is closed regardless of the setting of the low heat only switch SW 2 and regardless of whether R W2 circuit is closed or open When the wall thermostat calls for heat R W W1 circuit closes for low gas heat or R to W1 and W2 circuits close for high gas heat The furnace control performs a self check verifies low...

Page 13: ...witches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RED FRS1 WHEN USED ALS1 DSS ORN LGPS YEL NOTE 8 LPS NOTE 8 WHEN USED RED YEL ORN WHEN USED NOTE 6 ALS2 ORN SWITCH 1 2 HEAT SET UP SWITCH NORM HI HT LO HT ON OFF OFF ON BLOWER OFF DELAY SEC SWITCH 3 4 9...

Page 14: ...l 2 sec on high cool speed before reverting back to continuous blower speed 3 When R G circuit is opened the blower motor BLWM continues operating for an additional 90 sec if no other function requires blower motor BLWM operation 5 Heat Pump Mode NOTE An accessory interface kit is required with single speed heat pumps See interface kit Installation Instructions for single speed heat pump thermosta...

Page 15: ...d water solution to check for leakage A failure to follow this warning can cause a fire explosion personal injury or death 3 To operate furnace follow procedures on operating instruc tions label attached to furnace 4 With furnace operating set thermostat below room tempera ture and observe that furnace goes off Set thermostat above room temperature and observe that furnace restarts ADJUSTMENTS 1 S...

Page 16: ... from 2000 to 4500 ft this furnace must be derated 10 percent by an authorized Gas Conver sion Station or Dealer To determine correct input rate for altitude see example above and use 0 82 as derate multi plier factor b Check that gas valve adjustment caps are in place for proper input to be clocked c Obtain yearly heat value average for local gas supply NOTE Be sure heating value of gas used for ...

Page 17: ... 3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 45 3 8 1 6 44 3 2 1 4 44 3 4 1 4 44 3 5 1 5 or 900 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 44 3 3 1 4 Canada 925 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 Altitudes 950 47 3 7 1 6 45 3...

Page 18: ... 4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6 47 3 4 1 4 47 3 5 1 5 47 3 7 1 5 45 3 2 1 3 to 850 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 47 3 4 1 5 47 3 5 1 5 875 48 3 4 1 4 48 3 5 1 5 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 6000 900 49 3 7 1 6 49 3 8 1 6 48 3...

Page 19: ...d Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 675 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 47 3 5 1 5 47 3 6 1 5 to 700 48 3 3 1 4 48 3 5 1 5 48 3 6 1 5 48 3 7 1 6 48 3 8 1 6 725 49 3 7 1 5 49 3 8 1 6 48 3 3 1 4 48 3 4 1 5 48 3 5 1 5 9000 75...

Page 20: ...e by adjusting blower speed Increase blower speed to reduce temperature rise Decrease blower speed to increase temperature rise For high fire speed selection can be med high med 5 speed blowers only or med low factory setting For low fire speed selection can be low factory setting med low or med 5 speed blowers only Table 10 Gas Rate Cu Ft Hr SECONDS FOR 1 REVOLUTION SIZE OF TEST DIAL SECONDS FOR ...

Page 21: ...ntrol This control shuts off the combustion control system and energizes the circulating air blower motor if furnace over heats The preferred method of checking the limit control is to gradually block off the return air after the furnace has been operating for a period of at least 5 minutes As soon as the limit has shut off burners the return air opening should be unblocked By using this method to...

Page 22: ...stat type SW 1 and SW 2 and blower off delay SW 3 and SW 4 3 Verify manual reset switches have continuity 4 Ensure blower and gas control access doors are properly installed 5 Cycle test furnace with room thermostat 6 Check operation of accessories per manufacturer s instruc tions 7 Review User s Manual with owner 8 Leave literature packet near furnace 22 ...

Page 23: ...23 ...

Page 24: ...ce Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalog CALL FOR FREE CATALOG 1 800 962 9212 Packaged Service Training Classroom Service Training Copyright 1999 CARRIER Corp 7310 W Morris St Indianapolis IN 46231 58tua6si Manufacturer reserves the right...

Reviews: