Carrier 58STX Product Data Download Page 16

16

GUIDE SPECIFICATIONS

Gas Furnace

58STA/STX

General

SYSTEM DESCRIPTION

Furnish a _________________ fixed capacity gas--fired

furnace for use with natural gas or propane (factory

authorized conversion kit required for propane); furnish

cold air return plenum; furnish external medial cabinet for

use with accessory media filter or standard filter.

QUALITY ASSURANCE

Unit will be designed, tested and constructed to the

current ANSI Z 21.47/CSA 2.3 design standard for

gas--fired central furnaces.

Unit will be 3rd party certified by CSA to the current

ANSI Z 21.47/CSA 2.3 design standard for gas--fired

central furnaces.

Unit will carry the CSA Blue Star

R

and Blue Flame

R

labels.

Unit efficiency testing will be performed per the current

DOE test procedure as listed in the Federal Register.

Unit will be certified for capacity and efficiency and

listed in the latest GAMA Consumer’s Directory of

Certified Efficiency Ratings.

Unit shall carry the current Federal Trade Commission

Energy Guide efficiency label.

DELIVERY, STORAGE AND HANDLING

Unit shall be shipped as single package only and is

stored

and

handled

per

unit

manufacturer’s

recommendations.

WARRANTY (for inclusion by specifying engineer)

U.S. and Canada only. Warranty certificate available

upon request.

Products

EQUIPMENT

Components shall include: slow--opening gas valve to

reduce ignition noise, regulate gas flow, with electric

switch gas shut--off; flame proving sensor, hot surface

igniter, pressure switch assembly, flame rollout switch,

blower and inducer assembly, 40va transformer;

low--voltage (heating) (heating/cooling) thermostat.

Blower Wheel and Blower Motor

Galvanized blower wheel shall be centrifugal type,

statically and dynamically balanced. Blower motor of PSC

type shall be permanently lubricated with sealed bearings,

of _______hp, and shall be multiple--speed direct drive.

Blower motor shall be soft mounted to the blower scroll to

reduce vibration transmission.

Filters

Furnace may have reusable--type filters. Filter shall be

_______ in. (mm) (x) _______in. (mm). An accessory

high efficiency Media Filter is available as an option.

_______________ Media Filter.

Casing

Casing shall be of .030 in. (.76) thickness minimum,

pre--painted galvanized steel.

Inducer Motor

Inducer motor shall be soft mounted to reduce vibration

transmission.

Draft Safeguard Switch

Draft Safeguard Switch (blocked vent safeguard) shall

be factory installed to reduce the possibility of vent gas

infiltration due to a blocked or restricted vent pipe.

Heat Exchangers

Heat exchangers shall be a 4-Pass 20 gage aluminized

steel of fold--and--crimp sectional design when applied

operating under negative pressure.

Controls

Control shall include a micro--processor based

integrated electronic control board with at least 11 service

troubleshooting codes displayed via diagnostic flashing

LED light on the control, a self--test feature that checks all

major functions of the furnace within one minute, and a

replaceable automotive--type circuit protection fuse.

Multiple operational settings available including, separate

blower speeds for heating, cooling and continuous fan.

Continuous fan speed may be adjusted from the

thermostat. Cooling airflow will be selectable between 350

or 400 CFM per ton of air conditioning.

OPERATING CHARACTERISTICS

Heating Capacity shall be ________ Btuh input;

________ Btuh output capacity.

Fuel Gas Efficiency shall be 80% AFUE. Air delivery

shall be ___________ cfm minimum at 0.50 in. wc

external static pressure.

Dimensions shall be: depth __________ in. (mm);

width _________ in. (mm); height_________in. (mm)

(casing only). Height shall be_________in. (mm) with

A/C coil and _____________in. (mm) overall with

plenum.

ELECTRICAL REQUIREMENTS

Electrical supply shall be 115 volts, 60 Hz,

single--phase (nominal). Minimum wire size shall

be_________AWG; maximum fuse size or circuit breaker

shall be __________Amps.

SPECIAL FEATURES

Refer to section of the product data sheet identifying

accessories and descriptions for specific features and

available enhancements.

Copyright 2009 Carrier Corp.

D

7310 W. Morris St.

D

Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 02/09

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No: 58ST---6PD

Replaces: 58ST--- 5PD

58ST

A

/S

TX

Summary of Contents for 58STX

Page 1: ...naces are approved for use with natural or propane gas and the 58STX is approved for use in Low NOx Air Management Districts STANDARD FEATURES QuieTecht noise reduction system Microprocessor based control center LED diagnostics and self test feature Adjustable heating air temperature rise Adjustable cooling airflow 4 way Multipoise furnace 13 vent applications Compact design only 33 1 3 in 847 mm ...

Page 2: ...TA 4 Way Multipoise Nominal Cooling Size 58STX Low NOx version Airflow at 5 e s p 400 CFM per 12 000 Btuh 08 800 CFM 12 1200 CFM 14 1400 CFM 16 1600 CFM Input Capacity 20 2000 CFM 045 44 000 Btuh 110 110 000 Btuh 22 2200 CFM 070 66 000 Btuh 135 132 000 Btuh 090 88 000 Btuh 155 154 000 Btuh Series Number 58STA STX ...

Page 3: ...BLOWER AND MOTOR RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS MANIFOLD GAS BURNER BLOWER DOOR SAFETY SWITCH FLAME SENSOR Elbow may be turned to a different position depending on type of installation A04138 NOTE The 58STA STX Furnaces are factory shipped for use with natural gas These furnaces can be field converted for propane gas with a factory authorized and listed accessory conversion kit ...

Page 4: ...ON PROGRAMMABLE For use with 1 speed Air Conditioner deg F C Auto Changeover TP NAC TC NAC For use with 1 speed Heat Pump deg F C Auto Changeover TP NHP TC NHP For use with 2 speed Air Conditioner deg F C Auto Changeover TP NRH For use with multi use stage configurations deg F C Auto Changeover Temperature and Humidity Control TP PRH THERMOSTAT PROGRAMMABLE For use with 1 speed Air Conditioner deg...

Page 5: ...AWF1506UFR X X Flue Extension KGAFE0112UPH X X X X X X X X X X X X X X Twinning Kit KGATW0601HSI X X X X X X X X X X X X X X Combustible Floor Base KGASB0201ALL X X X X X X X X X X X X X X Downflow Vent Guard KGAVG0101DFG X X X X X X X X X X X X X X Vent Extension Kit KGAVE0101DNH X X X X X X X X X X X X X X Chimney Adapter Kit KGACA02014FC X X X X X X X X X X X KGACA02015FC X X X Natural to Propa...

Page 6: ... White Rodgers Minimum Inlet Pressure In wc 4 5 Natural Gas Maximum Inlet Pressure In wc 13 6 Natural Gas IGNITION DEVICE Hot Surface Gas input ratings are certified for elevations to 2000 ft 610 M In USA for elevations above 2000 ft 605 M reduce ratings 4 percent for each 1000 ft 305 M above sea level In Canada derate the unit 10 percent for elevations 2000 to 4500 ft 610 to 1372 M above sea leve...

Page 7: ... 5 Natural Gas Maximum Inlet Pressure In wc 13 6 Natural Gas IGNITION DEVICE Hot Surface Gas input ratings are certified for elevations to 2000 ft 610 M In USA for elevations above 2000 ft 610 M reduce ratings 4 percent for each 1000 ft 305 M above sea level In Canada derate the unit 10 percent for elevations 2000 to 4500 ft 610 to 1372 M above sea level Refer to National Fuel Gas Code NFPA 54 ANS...

Page 8: ...installations must use Type B vent immediately after exiting the furnace except when KGAVG0101DFG is used in downflow position 4 Type B vent where required refer to Note 1 5 4 in 102 mm single wall vent must be used inside furnace casing and the KGAVG0101DFG Downflow Vent Guard Kit 6 Accessory Downflow Vent Guard Kit KGAVG0101DFG required in downflow installations with bottom vent configuration 7 ...

Page 9: ...E NOTES 1 2 4 7 8 9 A02069 HORIZONTAL RIGHT SEE NOTES 1 2 4 5 7 8 9 A02070 HORIZONTAL LEFT SEE NOTES 1 2 4 7 8 9 A02064 HORIZONTAL LEFT SEE NOTES 1 2 4 5 7 8 9 A02065 HORIZONTAL LEFT SEE NOTES 1 2 4 5 7 8 9 A02066 HORIZONTAL LEFT SEE NOTES 1 2 4 5 7 8 9 A02067 58STA STX ...

Page 10: ...1250 1355 1285 1180 1260 1185 1100 1165 1070 985 990 890 810 785 725 110 16 Bottom or 1 Side High Med High Med Low 2035 1745 1530 1965 1710 1515 1880 1650 1470 1790 1560 1400 1680 1450 1310 1495 1340 1215 1365 1205 1095 1215 1090 990 1075 955 830 875 750 670 110 22 Bottom Only High Med High Med Low 2530 2230 1920 2470 2205 1900 2400 2165 1880 2320 2110 1845 2220 2035 1795 2115 1950 1730 2000 1855 ...

Page 11: ...rature for specific use of single side inlets The use of both side inlets a combination of 1 side and the bottom or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM FURNACE SIZE A CABINET WIDTH IN mm D SUPPLY AIR WIDTH IN mm E RETURN AIR WIDTH IN mm F CENTER LINE TOP AND BOTTOM FLUE COLLAR IN mm FLUE COLLAR IN mm SHIP WEIGHT LB KG 045 08 14 3 16 360 ...

Page 12: ...FICIENCY RATING CERTIFIED MEETS DOE RESIDENTIAL CONSERVATION SERVICES PROGRAM STANDARDS Before purchasing this appliance read important energy cost and efficiency information available from your retailer 58STA STX ...

Page 13: ... 8 15 14 090 14 115 60 1 127 104 8 2 34 10 3 15 14 090 16 115 60 1 127 104 10 0 28 8 5 15 14 090 20 115 60 1 127 104 13 6 32 9 7 20 12 110 12 115 60 1 127 104 8 2 34 10 3 15 14 110 16 115 60 1 127 104 10 1 28 8 5 15 14 110 22 115 60 1 127 104 14 8 30 9 1 20 12 135 16 115 60 1 127 104 10 2 27 8 2 15 14 135 22 115 60 1 127 104 14 4 30 9 1 20 12 155 20 115 60 1 127 104 15 0 29 8 8 20 12 Permissible l...

Page 14: ...14 TYPICAL INSTALLATION CONDENSING UNIT AIRFLOW ELECTRONIC AIR CLEANER GAS FIRED WATER HEATER HUMIDIFIER A02184 58STA STX ...

Page 15: ...15 58STA STX ...

Page 16: ...ry high efficiency Media Filter is available as an option _______________ Media Filter Casing Casing shall be of 030 in 76 thickness minimum pre painted galvanized steel Inducer Motor Inducer motor shall be soft mounted to reduce vibration transmission Draft Safeguard Switch Draft Safeguard Switch blocked vent safeguard shall be factory installed to reduce the possibility of vent gas infiltration ...