13
TYPICAL WIRING SCHEMATIC
A02186
ELECTRICAL DATA
58STA/STX
UNIT SIZE
VOLTS HERTZ
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH
FT (M)‡
MAXIMUM
FUSE OR CKT
BKR AMPS†
MINIMUM
WIRE GAGE
Maximum*
Minimum*
045-08
115-60-1
127
104
5.4
49 (14.9)
15
14
045-12
115-60-1
127
104
7.0
39 (11.8)
15
14
070-08
115-60-1
127
104
5.0
52 (15.8)
15
14
070-12
115-60-1
127
104
6.8
40 (12.1)
15
14
070-16
115-60-1
127
104
9.5
29 (8.8)
15
14
090-14
115-60-1
127
104
8.2
34 (10.3)
15
14
090-16
115-60-1
127
104
10.0
28 (8.5)
15
14
090-20
115-60-1
127
104
13.6
32 (9.7)
20
12
110-12
115-60-1
127
104
8.2
34 (10.3)
15
14
110-16
115-60-1
127
104
10.1
28 (8.5)
15
14
110-22
115-60-1
127
104
14.8
30 (9.1)
20
12
135-16
115-60-1
127
104
10.2
27 (8.2)
15
14
135-22
115-60-1
127
104
14.4
30 (9.1)
20
12
155-20
115-60-1
127
104
15.0
29 (8.8)
20
12
* Permissible limits of the voltage range at which unit operates satisfactorily.
† Time---delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.