background image

6. Remove burner box pressure tube from gas valve regulator

fitting.

7. Remove screws that secure manifold to burner box. (See Fig.

5.)

NOTE:

Do not remove burner box from cell panel.

8. Remove manifold, orifices, and gas valve as 1 assembly.

9. Remove screws attaching burner assembly in burner box.

10. Remove burner assembly from burner box.

NOTE:

All burners are attached to burner bracket and can be

removed as 1 assembly.

11. Clean burners with soft brush and vacuum.

12. Reinstall manifold, orifice, and gas valve assembly in burner

box. Ensure manifold seal grommet is installed properly and
burners fit over orifices.

13. Reconnect wires to gas valve. Refer to furnace wiring diagram

for proper wire location.

14. Reinstall burner box pressure tube to gas valve regulator

fitting.

15. Reinstall gas supply pipe to furnace gas control valve using

backup wrench on gas valve to prevent rotation and improper
orientation.

NOTE:

Use propane gas resistant pipe dope to prevent gas leaks.

DO NOT use Teflon tape.

Gas valve switch MUST be facing forward or tilted upward.
Failure to follow this warning could result in property
damage, personal injury, or death.

16. Replace burner box cover.

17. Turn on gas and electrical supplies to furnace.

FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death, or property damage.
Never test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the
detection of leaks to check all connections. A fire or explo-
sion may result causing property damage, personal injury, or
loss of life.

18. Check for gas leaks.

19. Replace main furnace door.

Step 4—Cleaning Heat Exchangers

The following items should be performed by a qualified service
technician.

PRIMARY HEAT EXCHANGERS

If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:

NOTE:

If the heat exchangers get a heavy accumulation of soot

and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.

1. Turn off gas and electrical supplies to furnace.

2. Remove main furnace door.

Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and hazardous opera-
tion.

3. Disconnect wires or connectors to flame rollout switch, gas

valve, igniter, and flame sensor.

4. Disconnect combustion-air intake pipe from intake housing.

5. Remove the pressure switch tube from intake housing.

6. Remove screws attaching intake housing to burner box, and

rotate intake housing away from burner box for removal.

7. Using backup wrench, disconnect gas supply pipe from

furnace gas control valve.

8. Disconnect pressure tubing from gas valve.

9. Remove 2 screws attaching top filler panel and rotate upwards

to gain access to screws attaching burner box to cell panel.

10. Remove screws attaching burner box to cell panel. (See Fig.

5.)

NOTE:

Burner box cover, manifold, gas valve, and burner

assembly should be removed as 1 assembly.

11. Clean heat exchanger openings with a vacuum and a soft

brush. (See Fig. 6.)

NOTE:

After cleaning, inspect the heat exchangers to ensure they

are free of all foreign objects that may restrict flow of combustion
products.

12. Reverse items 4 through 10 for reassembly.

Fig. 5—Burner Box Assembly

A96304

MANIFOLD
MOUNTING
SCREW

MANIFOLD

GAS VALVE
REGULATOR
FITTING

GAS VALVE

CELL

PANEL

5

Summary of Contents for 58MTA Series

Page 1: ...g Collector Box and Drainage System 6 Servicing Hot Surface Igniter 7 Electrical Controls and Wiring 8 Checking Heat Tape Operation If Applicable 8 Winterizing 9 WIRING DIAGRAM 10 TROUBLESHOOTING 10 Status Codes 10 Component Test 11 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to t...

Page 2: ...e to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for example DO NOT move or shuffle your feet DO NOT touch ungrounded objects etc 4 If you touch ungrounded objects recharge your body with ...

Page 3: ...ectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory authorized filte...

Page 4: ... assembly on blower shelf 12 Reinstall condensate trap and tubing if previously removed a Reinstall condensate trap in hole in blower shelf b Connect condensate trap drain tubes See Fig 8 or tubing diagram on main furnace door for proper tube location 1 Connect 1 tube blue or blue and white striped from collector box 2 Connect 1 tube violet or unmarked from inducer housing 3 Connect 1 tube relief ...

Page 5: ...rs get an accumulation of light dirt or dust on the inside they may be cleaned by the following procedure NOTE If the heat exchangers get a heavy accumulation of soot and carbon both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design A build up of soot and carbon indicates that a problem exists which needs to be co...

Page 6: ...s can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removing inducer assembly Step 5 Flushing Collector Box and Drainage System 1 Turn off gas and electrical supplies to furnace 2 Remove main furnace door 3 Disconnect inducer motor and pressure switch wires or connectors 4 Disconnect pressure switch tubes 5 Disconnect vent pipe ...

Page 7: ...e Trap on LEFT Side Optional CAP COLLECTOR BOX DRAIN TUBE BLUE PLUGGEDEND COLLECTORBOX DRAIN TUBE BLUE WHITE STRIPED COLLECTOR BOX TUBE GREEN COLLECTOR BOX TUBE PINK COLLECTOR BOX EXTENSIONTUBE CONDENSA TE TRAP INDUCERHOUSINGDRAINTUBE VIOLET COLLECTOR BOX EXTENSIONTUBE Condensate Trap on RIGHT Side PLUG CAP COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED CONDENSA TE TRAP COLLECTOR BOX EXTENSIONTUBE CO...

Page 8: ...tion NOTE If the polarity is not correct the STATUS LED on the furnace control board will flash rapidly and prevent the furnace from operating The control system also requires an earth ground for proper operation of the furnace control board and flame sensor The 24 v circuit contains an automotive type 3 amp fuse located on the control See Fig 12 Any direct shorts of the 24 v wiring during install...

Page 9: ...GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2 Y Y2 G NOTES 1 Connect Y terminal as shown for proper operation 2 Some thermostats require a C terminal connection as shown 3 If any of the original wire as supplied must be replaced use same type or equivalent wire 115 V FUSE...

Page 10: ... and all blower off delays must be completed to view previous codes To retrieve previous codes remove 1 of the red main limit or flame rollout switch wires 1 to 4 sec until the LED light goes out then reconnect it Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exists and will respond with blower operation This places the contro...

Page 11: ...R lead from furnace control 3 Manually close blower door switch 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in quick connect terminal on control until LED turns off Remove jumper from termi nals See Fig 12 NOTE If TEST TWIN and COM 24v terminals are jumpered loner than 2 sec LED will flash rapidly and ignore status code retrieval request Component t...

Page 12: ... EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 12 CIRCUIT PCB CONNECTOR PL2 3 CIRCUIT PCB HSI IDM CONNECTOR PL3 6 CIRCUIT ICM MOTOR CONNECTOR NOT SHOWN PL4 4 CIRCUIT IDM CONNECTOR PL5 2 CIRCUIT HSI...

Page 13: ...ITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry If opens during blower on delay period blower will come on for the selected blower off delay Check for Excessive wind Restricted vent Defective inducer motor Low inlet gas pressure if LGPS used Defective pressure switch Low inducer voltage 115 VAC Inadequate combustion air supply Proper ve...

Page 14: ...ducer will run for the entire component test The HSI blower motor LO HEAT speed HI HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on When the blower motor is turned OFF the inducer will be switched to low speed for 10 seconds Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch ...

Page 15: ...ION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow w...

Page 16: ...31 58mta4sm Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 535 80098 Printed in U S A Form 58MTA 4SM Pg 16 11 02 Replaces 58MTA 3SM ...

Reviews: