2. Remove main furnace door and blower access door.

3. Disconnect blower motor wires from furnace control. Field

thermostat connections may need to be disconnected depend-
ing on their length and routing.

4. Remove control box mounting screws and position control

box, transformer, and door switch assembly to right side of
furnace casing.

5. If condensate trap is located in left- or right-hand side of

furnace casing, proceed to item 6, otherwise remove trap and
tubing as described below (See Fig. 8, top left) :

a. Disconnect field drain connection from condensate trap.

b. Disconnect drain and relief port tubes from condensate

trap.

c. Remove condensate trap from blower shelf.

6. Remove screws securing blower assembly to blower shelf and

slide blower assembly out of furnace.

7. Clean blower wheel and motor by using a vacuum with soft

brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades as
balance will be affected.

8. If greasy residue is present on blower wheel, remove wheel

from the blower housing and wash it with an appropriate
degreaser. To remove wheel:

a. Mark blower wheel location on shaft before disassembly to

ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor shaft.

NOTE:

Mark blower mounting arms and blower housing so each

arm is positioned at the same hole location during reassembly.

c. Mark blower wheel orientation and cutoff plate location to

ensure proper reassembly.

d. Remove screws securing cutoff plate and remove cutoff

plate from housing.

e. Remove bolts holding motor mounts to blower housing and

slide motor and mounts out of housing. Disconnect capaci-
tor and ground wire attached to blower housing before
removing motor. Motor mounts do not need to be removed
from motor.

f. Remove blower wheel from housing.

The blower wheel should not be dropped or bent as balance
will be affected.

g. Clean wheel per instructions on degreaser cleaner. Do not

get degreaser in motor.

9. Reassemble motor and blower wheel by reversing items 8b

through 8f. Ensure wheel is positioned for proper rotation.
Tighten setscrew to between 140-160 in.-lb torque.

10. Reinstall blower assembly in furnace.

11. Reinstall control box, transformer, and door switch assembly

on blower shelf.

12. Reinstall condensate trap and tubing if previously removed.

a. Reinstall condensate trap in hole in blower shelf.

b. Connect condensate trap drain tubes. See Fig. 8 or tubing

diagram on main furnace door for proper tube location.

(1.) Connect 1 tube (blue or blue and white striped) from

collector box.

(2.) Connect 1 tube (violet or unmarked) from inducer

housing.

(3.) Connect 1 tube (relief port, green or pink) from

collector box.

NOTE:

Ensure tubes are not kinked or pinched, as this will affect

operation.

c. Connect field drain to condensate trap.

13. Reconnect wires.

Refer to furnace wiring diagram and connect thermostat leads if
previously disconnected. (See Fig. 16.)

NOTE:

Refer to Table 1 for motor speed lead reconnection if

leads were not identified before disconnection.

Heating air speed selection MUST be adjusted to provide
proper temperature rise as specified on the rating plate.
Failure to adjust the heating speed may shorten heat ex-
changer life.

Blower access door switch opens 115-v power to furnace
control. No component operation can occur. Caution must be
taken when manually closing this switch for service purposes.
Failure to follow this warning could result in personal injury
or death.

14. Turn on electrical supply. Manually close blower access door

switch. Use a piece of tape to hold switch closed. Check for
proper rotation and speed changes by performing a component
self-test as shown at the bottom of Service label. (See Fig. 17.)

15. If furnace is operating properly, remove tape to release blower

access door switch, replace blower access door, and replace
main furnace door.

Step 3—Cleaning Burners

The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:

1. Turn off gas and electrical supplies to furnace.

2. Remove main furnace door.

3. Remove burner box cover.

4. Using backup wrench, disconnect gas supply pipe from

furnace gas control valve.

Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and dangerous
operation.

5. Remove wires from gas valve. Note location for reassembly.

Table 1—Speed Selection

COLOR

SPEED

AS SHIPPED

White

Common

C

OM

Black

High

Cool

Yellow

Med-High

SPARE

Orange†

Med

High-Gas Heat

Blue

Med-Low

Spare/High-Gas Heat

Red

Low*

Low-Gas Heat

* Continuous blower speed.
† Available on 5-speed blowers only.

4

Summary of Contents for 58MTA Series

Page 1: ...g Collector Box and Drainage System 6 Servicing Hot Surface Igniter 7 Electrical Controls and Wiring 8 Checking Heat Tape Operation If Applicable 8 Winterizing 9 WIRING DIAGRAM 10 TROUBLESHOOTING 10 Status Codes 10 Component Test 11 SAFETY CONSIDERATIONS Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be alert to t...

Page 2: ...e to the control Tools held in a person s hand during grounding will be satisfactorily discharged 3 After touching the chassis you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity for example DO NOT move or shuffle your feet DO NOT touch ungrounded objects etc 4 If you touch ungrounded objects recharge your body with ...

Page 3: ...ectrical supply to furnace 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable filter clean filter by spraying cold tap water through filter in opposite direction of airflow Rinse filter and let dry Oiling or coating of the filter is not recommended 5 If equipped with factory specified disposable media filter replace only with a factory authorized filte...

Page 4: ... assembly on blower shelf 12 Reinstall condensate trap and tubing if previously removed a Reinstall condensate trap in hole in blower shelf b Connect condensate trap drain tubes See Fig 8 or tubing diagram on main furnace door for proper tube location 1 Connect 1 tube blue or blue and white striped from collector box 2 Connect 1 tube violet or unmarked from inducer housing 3 Connect 1 tube relief ...

Page 5: ...rs get an accumulation of light dirt or dust on the inside they may be cleaned by the following procedure NOTE If the heat exchangers get a heavy accumulation of soot and carbon both the primary and secondary heat exchangers should be replaced rather than trying to clean them thoroughly due to their intricate design A build up of soot and carbon indicates that a problem exists which needs to be co...

Page 6: ...s can be inspected by removing the inducer assembly See Flushing Collector Box and Drainage System section for details on removing inducer assembly Step 5 Flushing Collector Box and Drainage System 1 Turn off gas and electrical supplies to furnace 2 Remove main furnace door 3 Disconnect inducer motor and pressure switch wires or connectors 4 Disconnect pressure switch tubes 5 Disconnect vent pipe ...

Page 7: ...e Trap on LEFT Side Optional CAP COLLECTOR BOX DRAIN TUBE BLUE PLUGGEDEND COLLECTORBOX DRAIN TUBE BLUE WHITE STRIPED COLLECTOR BOX TUBE GREEN COLLECTOR BOX TUBE PINK COLLECTOR BOX EXTENSIONTUBE CONDENSA TE TRAP INDUCERHOUSINGDRAINTUBE VIOLET COLLECTOR BOX EXTENSIONTUBE Condensate Trap on RIGHT Side PLUG CAP COLLECTOR BOX DRAIN TUBE BLUE WHITE STRIPED CONDENSA TE TRAP COLLECTOR BOX EXTENSIONTUBE CO...

Page 8: ...tion NOTE If the polarity is not correct the STATUS LED on the furnace control board will flash rapidly and prevent the furnace from operating The control system also requires an earth ground for proper operation of the furnace control board and flame sensor The 24 v circuit contains an automotive type 3 amp fuse located on the control See Fig 12 Any direct shorts of the 24 v wiring during install...

Page 9: ...GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE WHT BLK WHT BLK W W1 W2 Y Y2 G NOTES 1 Connect Y terminal as shown for proper operation 2 Some thermostats require a C terminal connection as shown 3 If any of the original wire as supplied must be replaced use same type or equivalent wire 115 V FUSE...

Page 10: ... and all blower off delays must be completed to view previous codes To retrieve previous codes remove 1 of the red main limit or flame rollout switch wires 1 to 4 sec until the LED light goes out then reconnect it Do not leave red wire disconnected for longer periods of time as the control will assume an overtemperature condition exists and will respond with blower operation This places the contro...

Page 11: ...R lead from furnace control 3 Manually close blower door switch 4 For approximately 2 sec short jumper the COM 24v terminal on control to the TEST TWIN 3 16 in quick connect terminal on control until LED turns off Remove jumper from termi nals See Fig 12 NOTE If TEST TWIN and COM 24v terminals are jumpered loner than 2 sec LED will flash rapidly and ignore status code retrieval request Component t...

Page 12: ... EMITTING DIODE FOR STATUS CODES AMBER LGPS LOW GAS PRESSURE SWITCH SPST N O LPS LOW HEAT PRESSURE SWITCH SPST N O LS LIMIT SWITCH AUTO RESET SPST N C OL AUTO RESET INTERNAL MOTOR OVERLOAD TEMPERATURE SWITCH N C PCB PRINTED CIRCUIT BOARD CONTROL PL1 12 CIRCUIT PCB CONNECTOR PL2 3 CIRCUIT PCB HSI IDM CONNECTOR PL3 6 CIRCUIT ICM MOTOR CONNECTOR NOT SHOWN PL4 4 CIRCUIT IDM CONNECTOR PL5 2 CIRCUIT HSI...

Page 13: ...ITCH DID NOT CLOSE OR REOPENED If open longer than five minutes inducer shuts off for 15 minutes before retry If opens during blower on delay period blower will come on for the selected blower off delay Check for Excessive wind Restricted vent Defective inducer motor Low inlet gas pressure if LGPS used Defective pressure switch Low inducer voltage 115 VAC Inadequate combustion air supply Proper ve...

Page 14: ...ducer will run for the entire component test The HSI blower motor LO HEAT speed HI HEAT speed and COOL speed will run for 10 15 seconds each Gas valve and humidifier will not be turned on When the blower motor is turned OFF the inducer will be switched to low speed for 10 seconds Was there a previous status code other than 11 Is door switch closed Is there 115V going to switch Replace door switch ...

Page 15: ...ION PROVING FAILURE If flame is not sensed during the trial for ignition period the control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before proceeding to the next step Gas valve turned off Manual shut off valve Green Yellow w...