2

FURNACE SPECIFICATIONS

Model Number

58HDV040

58HDV060

58HDV080

58HDV100

{

INPUT

HIGH HEAT(BTUH)

LOW HEAT (BTUH)

40,000

28,000

60,000

42,000

80,000

56,000

100,000

70,000

{

HTG. CAPACITY HIGH HEAT(BTUH)

LOW HEAT (BTUH)

38,000

27,000

58,000

41,000

77,000

54,000

96,000

67,000

TEMP. RISE RANGE

HIGH HEAT (

o

F/

o

C)

LOW HEAT(

o

F/

o

C)

25--55/14--31

25--55/14--31

30--60/17--33

30--60/17--33

30--60/17--33

30--60/17--33

30--60/17--33

30--60/17--33

VENT SIZE^ in(mm)

2

(51) OD

2

-- 3

(51 -- 76) OD

3

(76) OD

3

(76) OD

VOLTS/HZ/PH

115/60/1

115/60/1

115/60/1

115/60/1

RATING PLATE AMPS.

9.5

11.4

14.6

14.6

MIN./MAX. VOLTAGE

104/127

104/127

104/127

104/127

TRANSFORMER (V.A.)

40

40

40

40

GAS PIPE SIZE -- inches(mm)

1/2 (12.7)

1/2 (12.7)

1/2 (12.7)

1/2 (12.7)

COOLING CAP. (TONS)

3.0

3.5

5.0

5.0

HIGH ALTITUDE PRESSURE SWITCH

1177766

1177767

1177768

1177769

FILTER SIZE -- inches(mm) (qty)

16X25X1

(406x635x25) (1)

16X25X1

(406x635x25) (1)

16X25X1

(406x635x25) (2)

16X25X1

(406x635x25) (2)

DIMENSIONS -- WxDxH inches(mm)

19

1

/

8

x29x40

(486x737x1016)

19

1

/

8

x29x40

(486x737x1016)

22

3

/

4

x29x40

(486x737x1016)

24

1

/

2

x29x40

(622x737x1016)

WEIGHT -- Lbs(kg)

150 (68)

168 (76)

187 (85)

203 (92)

^ Vent size may vary depending on length, number of elbows, standard vent or direct vent. See Installation Instructions.

{

Gas input ratings are certified for elevations to 2000 ft. (610 M).

In USA for elevations above 2000 ft. (610 M), ratings must be derated 2% (natural gas) or 4% (propane gas) for each 1000 ft. (305 M) above sea level.

In Canada for altitudes of 2000 ft. (610 M) to 4500 ft. (1372 M) ratings must be derated 5% (natural gas) and 10% (propane gas).

AIR INTAKE

VENT

H

G

E

F

TOP

AIR INTAKE (KO)
(ALTERNATE)

LEFT SIDE

VENT

7

2

1

/

4

6

11

/

16

1

1

/

4

ELECTRICAL

4

13

/

16

1

1

/

16

1

11

/

16

17

5

/

16

24

1

/

16

19

13

/

16

28

3

/

4

29

7

/

8

TRAP (KO)
UPFLOW/HORIZONTAL

1

7

/

8

21

5

/

8

24

13

1

/

4

4

7

/

8

TRAP (KO) (COUNTERFLOW)

13

11

/

16

31

11

/

16

1

3

/

8

THERMOSTAT

GAS

A

FRONT

B

D

23

1

/

8

C

BOTTOM

3

7

/

8

AIR INTAKE (KO)
(ALTERNATE)

RIGHT SIDE

VENT (KO)

7

1

1

/

4

ELECTRICAL (KO)

28

1

/

2

TRAP (KO)
UPFLOW/HORIZONTAL

TRAP (KO)
(COUNTERFLOW)

1

3

/

16

THERMOSTAT

GAS (KO)

18

1

/

2

3

/

4

TYPE

2

7

/

8

4

5

/

16

40

2

3

/

8

1

1

/

16

4

13

/

16

1

1

/

16

1

11

/

16

17

5

/

16

21

5

/

8

2

1

/

4

13

1

/

4

24

4

7

/

8

21

5

/

8

1

7

/

8

29

7

/

8

27

3

/

16

9

13

/

16

33

11

/

16

NOTE: Evaporator “A” coil drain pan dimensions may
vary from furnace duct opening size. Always consult
evaporator specifications for duct size requirements.
Furnace is designed for bottom return or side return.
Return air through back of furnace is NOT allowed.

(KO)

(KO)

KO = KnockOut

ALL DIMENSIONS: in (mm)

(34.9)

(503.2)

(347.7)

(804.9)

(758.8)

(730.3)

(611.2)

(439.7)

(42.9)

(123.8)

(609.6)

(549.3)

(47.6 )

(336.6)

(57.2)

(122.2)

(27)

(318)

(177.5)

(609.6)

(30.2)

(249.2)

(177.8)

(31.7)

(73)

(549.3)

(27)

(109.5)

(122.2)

(758.8)

(690.6)

(549.3)

(855.7)

(439.7)

(42.9)

(123.8)

(177.8)

(47.6)

(469.9)

(723.9)

(57.2)

(336.6)

(60.3 )

(27)

(1016)

(19.1)

(587.4)

(98.4)

Cabinet to Combustible Clearances -- in(mm)

TOP

BOT

RH

LH

BACK

FRNT

FLUE

1 (25.4)

0

0

0

0

3(76.2)

0

MINIMUM CLEARANCES TO COMBUSTIBLE

MATERIALS FOR ALL UNITS -- in (mm)

REAR

0

FRONT (combustion air openings in
furnace and in structure)

3“ (76.2)

Required For Service

*

24” (609.6)

ALL SIDES Of SUPPLY PLENUM

1” (25.4)

SIDES

0

VENT

0

TOP OF FURNACE

1” (25.4)

*30 “ (762mm) clearance recommended for furnace removal.

Horizontal position: Line contact is permissible only between lines
formed by intersections of top and two sides of furnace jacket, and
building joists, studs or framing.

A09241

58H

D

V

Summary of Contents for 58HDV040

Page 1: ... DC motor S Two stage Induced draft blower S In shot burners S California NOx approved QUALITY S Stainless steel heat exchanger S Stainless steel secondary heat exchanger S High temperature limit control prevents overheating S Direct ignition with Silicon Nitride igniton S Flame roll out sensors standard S External filter rack with permanent filters UNIT OPERATION HAZARD Failure to follow this war...

Page 2: ...INTAKE VENT H G E F TOP AIR INTAKE KO ALTERNATE LEFT SIDE VENT 7 21 4 611 16 11 4 ELECTRICAL 413 16 11 16 111 16 17 5 16 24 1 16 19 13 16 28 3 4 29 7 8 TRAP KO UPFLOW HORIZONTAL 17 8 21 5 8 24 13 1 4 47 8 TRAP KO COUNTERFLOW 13 11 16 31 11 16 13 8 THERMOSTAT GAS A FRONT B D 23 1 8 C BOTTOM 37 8 AIR INTAKE KO ALTERNATE RIGHT SIDE VENT KO 7 11 4 ELECTRICAL KO 28 1 2 TRAP KO UPFLOW HORIZONTAL TRAP KO...

Page 3: ...CVT 2 51 mm Concentric vent kit allows single wall penetration for 2 pipe direct vent applications 90 58HDV060 58HDV080 58HDV100 KGAHA6101PSW High Altitude Pressure Switch Kit 58HDV040 KGAHA6201PSW High Altitude Pressure Switch Kit 58HDV060 KGAHA6301PSW High Altitude Pressure Switch Kit 58HDV080 KGAHA6401PSW High Altitude Pressure Switch Kit 58HDV100 KGASB0301P01 KGASB0401P02 KGASB0801P06 Combusti...

Page 4: ...P is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 592 279 01 1021 482 10 1346 635 11 1346 635 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Speed Adj ...

Page 5: ... 1000 1200 1400 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Low Cool Airflow 0 200 400 600 800 1000 1200 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 58HDV ...

Page 6: ... decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 612 475 01 1096 822 10 1403 1040 11 1403 1040 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Speed Adj 5 ...

Page 7: ...0 600 800 1000 1200 1400 1600 1800 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP inchesof wc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 LowCoolAirflowchart 0 200 400 600 800 1000 1200 1400 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 ESP inchesofwc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 58HDV ...

Page 8: ...at ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 1007 475 01 1742 822 10 2204 1040 11 2204 1040 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Sp...

Page 9: ...000 2400 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 LowCoolAirflow 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inchesofwc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 58HDV ...

Page 10: ...ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 1032 487 01 1778 839 10 2178 1028 11 2178 1028 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Speed...

Page 11: ...400 1800 2200 2600 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inchesofwc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Low Cool Airflow 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 0 0 2 0 4 0 6 0 8 1 0 ESP inches of wc CFM 00 00NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 58HDV ...

Page 12: ...42 Copyright 2009 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 04 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 58HDV 01PD Replaces NEW 58HDV ...

Reviews: