background image

6

Circulation Air Blower Data -- 58HDV060

Cooling Adjustment

Heating Rise Adjustment

DIP Switch

(OFF = 0

ON = 1)

High Cool @ .50

in wc(125 Pa)

Low Cool (80%

of High Cool)

** Adjust

Jumper

Setting

DIP Switch

(OFF = 0

ON = 1)

High Heat

Rise

Change @

0.20 in wc

(50 Pa)

Low Heat

Rise

Change at

Resultant

Static

5 & 6

CFM

L/s

CFM

L/s

3 & 4

00

1377

650

1102

650

+

00

--3

--3

*00

1239

585

991

585

*NOM

*00

0

0

00

1097

518

878

518

--

00

3

3

01

1165

550

932

550

+

01

1

2

01

1044

493

835

493

NOM

01

4

4

01

889

420

711

420

--

01

8

8

10

966

456

773

456

+

10

--1

0

10

848

400

678

400

NOM

10

2

2

10

715

337

572

337

--

10

7

7

11

74

353

599

353

+

11

--5

--4

11

650

307

520

307

NOM

11

--2

--2

11

523

247

418

247

--

11

1

1

Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is

present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory

default settings.

Table 2

Airflow

DIP Switch

(OFF = 0 / ON = 1)

Continuous Fan @

0.10 in wc (25 Pa) ESP

1 & 2

CFM

L/s

*00

612

475

01

1096

822

10

1403

1040

11

1403

1040

* Factory Setting

Table 3

SW2 DIP Assignments

DIP Switch

Blower Parameter

1 & 2

Cont Fan Adj

3 & 4

Heat Speed Adj

5 & 6

Cool Speed Adj

7 & 8

Cool On/Off Delay

Table 4

Cooling Delay Options (SW2 -- 7, 8)

ON DELAY

OFF DELAY

DIP SW2 -- 7/8

(OFF = 0 / ON = 1)

Timed ON (sec)

Airflow during on

delay

Timer OFF (sec)

Airflow during off

delay

*00

5

OFF

90

100%

01

5

OFF

0

OFF

10

30

50%

30

100%

11

30

50%

180

50%

Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting

MAX CFM’s for Factory Washable Filters

Filter Size (in/mm)

CFM

L/s

14

X 25

/ 356 x 635

1400

661

16

X 25

/ 406 x 635

1600

755

20

X 25

/ 508 x 635

2000

944

24

X 25

/ 610 x 635

2500

1180

Max CFM based on 600 FPM (3.0 M/s)

NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s).

These filters only allow half the airflow when compared to 600 FPM (3.0

M/s) filters.

EXAMPLE (approx.):

20in X 25in @ 600 FPM = 2000 CFM, @ 300 FPM = 1000 CFM

508mm x 635mm @ 3.0 M/s = 944 L/s, @ 1.5 M/s = 472 L/s

58H

D

V

Summary of Contents for 58HDV040

Page 1: ... DC motor S Two stage Induced draft blower S In shot burners S California NOx approved QUALITY S Stainless steel heat exchanger S Stainless steel secondary heat exchanger S High temperature limit control prevents overheating S Direct ignition with Silicon Nitride igniton S Flame roll out sensors standard S External filter rack with permanent filters UNIT OPERATION HAZARD Failure to follow this war...

Page 2: ...INTAKE VENT H G E F TOP AIR INTAKE KO ALTERNATE LEFT SIDE VENT 7 21 4 611 16 11 4 ELECTRICAL 413 16 11 16 111 16 17 5 16 24 1 16 19 13 16 28 3 4 29 7 8 TRAP KO UPFLOW HORIZONTAL 17 8 21 5 8 24 13 1 4 47 8 TRAP KO COUNTERFLOW 13 11 16 31 11 16 13 8 THERMOSTAT GAS A FRONT B D 23 1 8 C BOTTOM 37 8 AIR INTAKE KO ALTERNATE RIGHT SIDE VENT KO 7 11 4 ELECTRICAL KO 28 1 2 TRAP KO UPFLOW HORIZONTAL TRAP KO...

Page 3: ...CVT 2 51 mm Concentric vent kit allows single wall penetration for 2 pipe direct vent applications 90 58HDV060 58HDV080 58HDV100 KGAHA6101PSW High Altitude Pressure Switch Kit 58HDV040 KGAHA6201PSW High Altitude Pressure Switch Kit 58HDV060 KGAHA6301PSW High Altitude Pressure Switch Kit 58HDV080 KGAHA6401PSW High Altitude Pressure Switch Kit 58HDV100 KGASB0301P01 KGASB0401P02 KGASB0801P06 Combusti...

Page 4: ...P is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 592 279 01 1021 482 10 1346 635 11 1346 635 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Speed Adj ...

Page 5: ... 1000 1200 1400 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Low Cool Airflow 0 200 400 600 800 1000 1200 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 58HDV ...

Page 6: ... decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 612 475 01 1096 822 10 1403 1040 11 1403 1040 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Speed Adj 5 ...

Page 7: ...0 600 800 1000 1200 1400 1600 1800 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 ESP inchesof wc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 LowCoolAirflowchart 0 200 400 600 800 1000 1200 1400 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 ESP inchesofwc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 58HDV ...

Page 8: ...at ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 1007 475 01 1742 822 10 2204 1040 11 2204 1040 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Sp...

Page 9: ...000 2400 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inches of wc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 LowCoolAirflow 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inchesofwc CFM 00 00NOM 00 01 01NOM 01 10 10NOM 10 11 11NOM 11 58HDV ...

Page 10: ...ESP is decrease in rise Note 4 High and low heat rise values are approximate air temperature change from return air temperature when at factory default settings Table 2 Airflow DIP Switch OFF 0 ON 1 Continuous Fan 0 10 in wc 25 Pa ESP 1 2 CFM L s 00 1032 487 01 1778 839 10 2178 1028 11 2178 1028 Factory Setting Table 3 SW2 DIP Assignments DIP Switch Blower Parameter 1 2 Cont Fan Adj 3 4 Heat Speed...

Page 11: ...400 1800 2200 2600 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 ESP inchesofwc CFM 00 00 NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 Low Cool Airflow 0 200 400 600 800 1000 1200 1400 1600 1800 2000 0 0 0 2 0 4 0 6 0 8 1 0 ESP inches of wc CFM 00 00NOM 00 01 01 NOM 01 10 10 NOM 10 11 11 NOM 11 58HDV ...

Page 12: ...42 Copyright 2009 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 04 09 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 58HDV 01PD Replaces NEW 58HDV ...

Reviews: