Carrier 58BLA Installation, Start-Up, And Operating Instructions Manual Download Page 8

3. Disconnect flue pipe.

4. Remove outside flue collar.

5. Remove top rear panel.

NOTE:

Blower removal as described in Blower Oiling and

Removal section may be desired for easier access when cleaning
with duct work attached.

6. Remove inside collar on flue pipe.

7. Remove top partition.

8. Place field-fabricated cardboard on metal tray beneath collec-

tor box to prevent debris from entering blower compartment.

9. Remove flue collector box from secondary heat exchanger

tube flange. This exposes inside surfaces of secondary tubes of
heat exchanger.

10. Clean secondary tubes and flue pipe with a stiff brush and

vacuum cleaner.

11. Remove louvered door.

12. Disconnect limit control wires.

13. Disconnect oil line and remove oil burner from furnace.

14. Remove observation door and collar on observation tube.

15. Remove intermediate panel. Care must be taken not to bend or

damage limit control.

16. Loosen to hand tightness the 3 nuts labeled "A" in Fig. 4.

Remove screws labeled "B" in Fig. 4. Slide combustion
chamber forward out of heat exchanger. Be careful not to
bump combustion chamber as it becomes brittle after having
been fired.

17. Use a stiff brush and vacuum cleaner to clean inside of

primary drum.

Never use incendiary type cleaners (smoke sticks) for clean-
ing!

For all heat exchanger plates that have been removed, the
gaskets MUST be replaced. Failure to replace gaskets could
lead to heat exchanger leakage, sooting, and a hazardous
condition which could lead to bodily harm.

18. Before reassembly, heat exchanger and combustion chamber

should be inspected to determine if replacement is required.
After cleaning, place combustion chamber back into primary
drum and secure with "B" screws. Ensure that cover plate
gasket is in place before tightening screws. Care must be taken
not to damage combustion chamber. The "B" screws should be
tightened to 35-45 lb-in.

19. Tighten "A" nuts to 30 lb-in. of torque (firm, but not overly

tight).

20. Replace intermediate panel, observation tube collar, observa-

tion door, limit wiring, and oil burner.

21. Replace collector box on secondary tube flange, ensuring

proper placement of gasket. Tighten screws to 35-45 lb-in. of
torque.

22. Replace top partition, inside collar on flue pipe, top rear panel,

outside flue collar, and blower door.

23. Reconnect flue pipe and oil line(s).

24. Readjust burner for proper operation. Check limit operation as

outlined in Limit Control Check section.

Step 4—Blower Oiling and Removal

Periodic oiling of blower motor may be necessary. Check for
instructions on inside of blower access door.

If it is ever necessary to remove blower from furnace:

1. Turn off all electrical power to furnace.

2. Remove blower door.

3. Remove screws securing blower legs to blower rails mounted

on bottom panel of furnace.

4. Slide blower forward on rails toward rear of unit until motor

wire connections at terminal block on motor can easily be
reached and disconnected.

5. Disconnect motor wires at terminal block on motor.

6. Remove blower from unit.

7. Reverse items 1 through 6 to reinstall blower. Refer to wiring

diagram (Fig. 7) of these instructions or diagram located on
inside of louvered door to properly rewire unit.

Step 5—Keeping Filters Clean

Never operate unit without a filter or with filter access door
removed. Failure to adhere to this warning could lead to a
hazardous condition which could lead to equipment damage
and bodily harm.

As a homeowner, keeping filters clean is your most important
responsibility. A dirty filter reduces efficiency of your system,
causes erratic performance of controls, and could result in damage
to motor or heating element.

1. Inspect filters at regular intervals depending upon dirt condi-

tions. For new homes, check filters every week for 4 consecu-
tive weeks. In all cases, inspect filters at least every 3 to 4
weeks when system is in constant operation. Replace or clean
filter at least at beginning of each season (heating and cooling)
and thereafter as needed.

2. If a permanent filter is used, it can be cleaned with cold water

and soap.

Be sure that filter is thoroughly dry before installing back into
furnace.

Fig. 4—Removing Combustion Chamber

A96398

A

B

a95103

yyy

yyy

8

Summary of Contents for 58BLA

Page 1: ... BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT For use with grade 2 Fuel Oil maximum Do not use Gasoline Crankcase Oil or any Oil containing Gasoline Failure to follow this warning could lead to sooting fire explosion and or severe bodily harm Never burn garbage or paper in the heating system and never leave rags paper or any fl...

Page 2: ...i nation would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetra chloride cleaning solvents hydrochloric acid water soften ing chemicals and similar chemicals Failure to follow this warning will lead to premature rusting of heat exchanger and possible premature furnace failure and or vent failure which could result in fire hazard and or bodily harm This ...

Page 3: ...urnace operational problems Some of these problems are 1 Excessive oil burner after drip and oil fumes 2 Sooting 3 Melted oil burner couplings and or ignitor relay control 4 A condition where air band or air shutter settings must be more open than normal to achieve proper combustion 5 Lockouts on start up Step 2 Duct Work Recommendations The proper sizing of warm air ducts is necessary to ensure s...

Page 4: ...Never reduce pipe size below minimum certified furnace pipe size as shown in Table 2 4 All pipe should be supported using proper clamps and or straps These supports should be at least every 4 ft 5 All horizontal runs of pipe should have at least 1 4 in per ft of upward slope 6 All runs of pipe should be as short as possible with as few turns as possible 7 Seams should be tightly joined and checked...

Page 5: ...en valve on oil supply line 3 Reset primary control 4 Set thermostat above room temperature 5 Set main electrical switch to ON position Burner should start DO NOT TAMPER WITH UNIT OR CONTROLS CALL YOUR SERVICE TECHNICIAN Step 2 Recommended Installation Practices and Combustion Check In order to obtain optimum performance from oil burner the following setup procedures must be followed 1 A test kit ...

Page 6: ... to be changed to obtain necessary cooling airflow Step 6 Heating The blower speed is factory set to deliver required airflow at normal duct static pressure Step 7 Cooling The blower speed may be field adjusted to deliver required airflow for cooling application See Table 5 Step 8 Constant Blower Switch This furnace is equipped with a constant low speed blower option Whenever room thermostat is no...

Page 7: ...cal supplies upstream of furnace If furnace has been in operation some surfaces may be hot Allow time for unit to cool down 2 Disconnect flue pipe 3 For access to cleanout ports remove blower door and filter The 2 cleanout ports are located in blower compartment They protrude through the partition and are located on the left and right of flue pipe See Fig 2 4 Unscrew wing clamp nuts and remove cle...

Page 8: ...r observa tion door limit wiring and oil burner 21 Replace collector box on secondary tube flange ensuring proper placement of gasket Tighten screws to 35 45 lb in of torque 22 Replace top partition inside collar on flue pipe top rear panel outside flue collar and blower door 23 Reconnect flue pipe and oil line s 24 Readjust burner for proper operation Check limit operation as outlined in Limit Co...

Page 9: ...STATIC PRESSURE IN WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 105 12 High 1795 1735 1675 1605 1550 1485 1425 1350 1275 1220 Medium 1365 1335 1305 1275 1255 1215 1155 1105 1050 985 Low 995 965 945 925 900 870 825 775 725 670 125 16 High 1905 1845 1770 1695 1630 1565 1490 1425 1325 1220 Medium 1750 1675 1620 1560 1500 1440 1370 1305 1235 1130 Low 1390 1350 1305 1260 1220 1180 1120 1060 985 880 155 2...

Page 10: ...Fig 6 Barometric Damper Locations A95117 FIG A FIG G FIG D FIG L FIG B FIG C FIG J FIG H FIG K POOR WRONG WRONG WRONG WRONG WRONG BAROMETRIC DAMPER LOCATIONS GOOD LOCATIONS BAD LOCATIONS 10 ...

Page 11: ... CONFORM TO N E C AND LOCAL CODES IN CANADA WIRING MUST CONFORM TO CURRENT CSA 22 1 CANADIAN ELECTRICAL CODE PART 1 AND OR LOCAL CODES 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C AND BE A MINIMUM OF 16 GA AWG COPPER STRAND WIRE USE COPPER WIRE ONLY FOR FIELD WIRING 4 CONNECT REQUI...

Page 12: ...ructions exactly a fire or explosion may result causing property damage personal injury or loss of life 1 Open all warm air registers and make sure all return air grilles are unobstructed 2 If a humidifier is installed with your system open water supply valve 3 Set thermostat to lowest setting 4 Turn on electric power to furnace 5 Open oil supply valve 6 Check all connections to ensure there are n...

Reviews: