background image

CMCT TROUBLESHOOTING GUIDE

The following is a guide to aid in the proper diagnosing
of service problems.

High Head Pressure & High Back Pressure

1. Air in system.

2. Defective fan motor or fan blade dragging on con-

denser shroud.

3. Defrost heater on during refrigeration cycle due to

heater going to ground or defective time clock.

4. Refrigerant over charge.

5. Blocked condenser (dirty)

Low Back Pressure & Low Head Pressure

1. Defective back pressure valve—check for proper

setting as described under “Back Pressure Valve.”

2. Shortage of refrigerant—place a temperature indicat-

ing device on outlet of top coil (lower lefthand side of
coil). Temperature should read within 3 to 4 degrees of
low side pressure taken at the compressor suction
service valve. Add gas slowly until these conditions
are obtained or remove charge with certified recovery
equipment, and recharge with correct charge.

3. Cap tube plugged due to moisture or dirt.

Pressures Normal – Cabinet Warm

1. Top coil blocked with frost—see corrective mea-

sures under “Coil Block With Frost.”

2. Refrigerant under charge. Due to the fact that it

takes a considerable amount of under charge before
it has any great effect on pressures and inaccuracy
of gauges it is possible to have normal pressures
and yet have an under charge of refrigerant. This
under charge will “starve” the top coil and seriously
affect cabinet temperature. To determine correct
charge see #2 under “Low Back Pressure … .”

Coil Blocked With Frost

1. Bad timer or timer motor.

2. Bad drafts in store caused by heating or air condi-

tioning fans; cabinet located too close to door.

3. Defective defrost heater.

4. Defective defrost terminating thermostat, safety

thermostat or defective solenoid in time clock.

4.

Either of these (#4) can keep the cabinet from going
through a defrost cycle. The defrost thermostat (see
wiring diagram) should be in open position between
terminals 1 & 2 when the cabinet goes into defrost.

4.

After the coil reaches 76°F, it closes, energizing a
solenoid in the time clock which in turn trips the time
clock mechanism off defrost. Should this thermostat
be in the closed position when the clock trips into
the defrost cycle, it will immediately trip it off again.
(NOTE: Switch between terminals 1 & 2 will not
open until thermostat drops below 59°F).

4.

If the solenoid in the clock is stuck closed (plunger
up), it will have the same effect. To determine which
is at fault, remove the wire from X on the clock and
turn clock dial into defrost cycle; if cabinet goes into
defrost, it is the defrost thermostat that is bad. If it
still does not go into defrost, remove clock and
inspect the plunger of the solenoid coil.

5. Defective safety thermostat.

5.

This thermostat has a SPDT switch with one side
wired in series with the defrost heater. Contacts
between terminals 2 & 3 should be in the closed
position during the refrigeration cycle. Its only pur-
pose is, in case of failure of the defrost timer during
the defrost cycle, it will open the heater circuit when
the coil reaches 76°F, preventing any over heating of
the defrost heater.

5.

If this thermostat is in the open position when the
cabinet goes into the defrost cycle, the heater will
remain off. For access to thermostat connections to
check continuity, refer to wiring diagram. Disconnect
this thermostat and check with ohmmeter.

5.

If for any reason the temperature termination feature
is inoperative, the fail safe settings on the timer
should be set for 30 minutes defrost time.

Defrost Cycle Too Long – Terminating On
Fail Safe (Heater On)

1. Bad solenoid in time clock (opening winding).

1.

If there is an open circuit in the coil of this solenoid,
it will not trip the time clock off defrost when the ther-
mostat closes. The cabinet will stay on defrost for
the length of time the fail-safe lever on the time clock
is set. (Factory set at 40 minutes.)

2. Defrost terminating thermostat not closing when coil

reaches 76°F.

To  determine which is at fault, turn clock into defrost,
place jumper across X and N on clock. If solenoid is
good, this will trip the clock off defrost indicating that it
is the defrost thermostat that is at fault.

Be certain that the defrost thermostat has
reached 76°F before determining that either

the solenoid coil or the thermostat is defective.

NOTE:

38

MAINTENANCE & REPAIR

Summary of Contents for 52-2038-01

Page 1: ...SERVICE INSTALLATION MANUAL CARRIER COMMERCIAL REFRIGERATION INC Providing BEVERAGE AIR FRIGIDAIRE KELVINATOR UNIVERSAL NOLIN Products Services Frozen Food Ice Cream Merchandisers CMCT 2 03 51 1021 01...

Page 2: ...ned in this manual which should be retained in a convenient location for future reference All data and information in this manual is subject to change without notice MODEL DESIGNATION INFORMATION 115V...

Page 3: ...SECTION I Introduction...

Page 4: ...length Operating ambients range from 70 F to 85 F with cavity temperatures at load line between 0 F to 20 F Except for routine cleaning these cabinets will require little maintenance In the unusual ev...

Page 5: ...Models 4 6 8 Export 14 Lamp Wiring Detail Upper Raceway 15 MAINTENANCE REPAIR Cabinet Temperature Control 19 Electrical Box Layout 20 Defrost Timer Layout 21 Cabinet Electrical Supply 22 Condensing U...

Page 6: ...vity Coil Cold Wall Fin Tube Gravity Coil Cold Wall Fin Tube Gravity Coil Cold Wall Fin Tube Gravity Coil Cold Wall Refrigerant Type R404A R 404A R 404A R 404A Refrigerant Control Capillary Capillary...

Page 7: ...minimum clearance behind for proper air circulation The cabinet must be installed on a sturdy solid level floor The cabinet must be located so it can be plugged or wired into a properly grounded thre...

Page 8: ...s utilizing 404A refrigerant 1 2 HP on the CMCT 4 and CMCT 6 3 4 HP on the CMCT 8 1 HP on the CMCT 10 A back pressure valve is used to protect the compres sor against excessive pressures during initia...

Page 9: ...is wired in series with the defrost heater This thermostat will also open the heater circuit when the top coil reaches 76 F should any malfunction of the defrost thermostat occur Any time the system...

Page 10: ...d Breaker Heater behind 960 15 12 120 each End Breaker Glass Heater around 134 107 89 120 Front Glass CMCT 6 OHMS WATTS AMPS VOLTS Def Heater on Bottom side 15 9 904 7 5 120 of Top Coil Control Bellow...

Page 11: ...RIG OZ TUBE SUCT DISCH SETTING TEMP CMCT 4 8 0 115V 6 8 115V 404A 22 8 x 042 ID 2 225 No 7 22 F CMCT 6 8 0 115V 8 4 115V 404A 23 8 x 042 ID 5 223 No 7 19 F CMCT 8 12 0 115V 12 0 115V 404A 27 7 x 049 I...

Page 12: ...t Glass Heated Glass Lid 41 3 14 58 24 each ECMCT 6 OHMS WATTS AMPS VOLTS Def Heater on Bottom side 51 904 4 2 215 of Top Coil Control Bellows Heater below 5375 9 04 215 Def Controls End Breaker Heate...

Page 13: ...12 INTRODUCTION WIRING DIAGRAM 00 1667 00 CMCT 4 6 8...

Page 14: ...INTRODUCTION 13 WIRING DIAGRAM 00 1670 00 CMCT 10...

Page 15: ...14 INTRODUCTION WIRING DIAGRAM 00 1934 00 ECMCT 4 6 8 Export Models...

Page 16: ...INTRODUCTION 15 LAMP WIRING DETAIL Upper Raceway Typical...

Page 17: ...SECTION II Maintenance Repair...

Page 18: ...apillary is inserted in a copper bulb well just to the right of the control The well is approximate ly 20 long and is secured to the cold wall evaporator The control reacts to the evaporator temperatu...

Page 19: ...n be pulled out for component troubleshooting The following components are located within the box CAUTION 1 Defrost Timer 1 24 Hours 5 Main Terminal Board 2 Run Capacitor 6 115V Power Supply Switch 11...

Page 20: ...t time of day by turning the inner knob counterclockwise until the correct time is opposite the time indicator on the clock The time clock is set to go into defrost once every 24 hours This defrost oc...

Page 21: ...must be on a dedicated cir cuit unto themselves Failure to do so could result in loss of product Wiring and connections in power supply system must meet all applica ble local and national electrical c...

Page 22: ...to aid service personnel in the event service is needed Disconnect the power supply before servicing the cabinet 1 Remove front grill 2 Remove two 2 hold down bolts that are located in the front base...

Page 23: ...CONDENSING UNIT LAYOUT 24 MAINTENANCE REPAIR...

Page 24: ...IT COMPARTMENT REAR CMCT 10 models still use fin and tube condensers NOTE 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 1 Accordian Coil 2 Process Tube Evaporator 3 Suction Line 4 Cap Tube Inlet MAINTENANCE REPAIR...

Page 25: ...n the top left back wall NOTE EVAPORATOR TANK WRAP RIGHTHAND REAR OF CABINET Capillary tube and heat exchange are foamed in place Three lines exit the cabinet shell 11 1 4 Process Line 12 Capillary Tu...

Page 26: ...s used are polyol esters Special consideration must be made when handling these oils Processing procedures must be more rigorous to avoid absorbing moisture Also P O E s are better solvents which mean...

Page 27: ...SIG and should not be changed To check this setting it is necessary that the pressure on the inlet side or evaporator side of the valve be above 10 PSIG Put cabinet into defrost cycle to obtain high l...

Page 28: ...cal box is connected via a wiring harness to the upper lighting channel which houses the following components CAUTION 1 Product Reflector 4 Light Ballast 2 Defrost Termination Control 5 Lamp Receptabl...

Page 29: ...st behind the light fixture at the warm air intake to coil The baffle can be accessed by removing screws located at the bottom edge of V baffle The heater is attached at the back side of the V baffle...

Page 30: ...ews in the end panel breaker A and pull breaker down and out 2 Disconnect heater leads from end panel breaker heater A and pull end panel breaker out 3 To remove end panel breaker heater remove tape C...

Page 31: ...abinet 1 Disconnect the defrost heater leads located on the lower right hand side of the lamp channel Figure 1 2 Remove the air diverter shown as Figure 2 This will expose the defrost heater rack whic...

Page 32: ...UPPER CROSS SECTION CMCT Models...

Page 33: ...ws in end track B Pull track forward and lift up Typical both ends Not necessary for glass removal 5 Remove two 2 screws in the front of center track G and swing center track from dotted line position...

Page 34: ...in order to service various interior components as shown below 1 Product Reflector 4 Upper Electrical Component Housing 2 Defrost Heater Plug 5 Righthand Arm Heater Leads 3 Lamp MAINTENANCE REPAIR 35...

Page 35: ...bulb well Lift the sub top up and out of the cabinet CAUTION 1 Defrost Termination High Limit Control 3 Defrost Heater Receptacle 2 Defrost Termination Bulb Well 4 Sub Top G Lift the insulation up and...

Page 36: ...connections on the lefthand end of the cabi net Take care when reinstalling the coil housing cover Reseal areas where moisture could migrate down into the coil area This coil area runs at a temperatu...

Page 37: ...ck mechanism off defrost Should this thermostat be in the closed position when the clock trips into the defrost cycle it will immediately trip it off again NOTE Switch between terminals 1 2 will not o...

Page 38: ...SECTION III Parts List...

Page 39: ...ertical Trim Post RH 6 Center Track 11 Nameplate 2 End Track LH 7 Glass Lid 12 Front Bumper 3 Countertop 8 Glass Rail 13 Bumper Trim 4 End Trim 9 Front Glass 14 Front Trim Panel Upper 5 Lighted Sign 1...

Page 40: ...19 0458 00 19 0458 00 19 0458 00 19 0458 00 Ballast Lamp 20 Watt 19 0146 00 Lamp Fluorescent 30 Watt 19 0150 00 19 0150 00 19 0150 00 19 0150 00 Lamp Fluorescent 20 Watt 19 0149 00 Lamp Fluorescent 34...

Page 41: ...9 0911 00 19 0911 00 Ballast Lamp 20 Watt 19 0912 00 22 0200 Lamp Fluorescent 30 Watt 19 0150 00 19 0150 00 19 0150 00 Lamp Fluorescent 20 Watt 19 0149 00 Lamp Fluorescent 34 Watt 19 0151 00 Lampholde...

Reviews: