background image

8

Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground

level installations. Install a field--supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that

the outlet of the trap is at least 1 in. (25 mm) lower than the

drain--pan condensate connection to prevent the pan from
overflowing. See Fig. 9. Prime the trap with water. When using a

gravel apron, make sure it slopes away from the unit.
If the installation requires draining the condensate water away from

the unit, install a 2--in. (51 mm) trap using a 3/4 --in. OD tubing or

pipe. See Fig. 9

.

Make sure that the outlet of the trap is at least 1 in.

(25 mm) lower than the unit drain--pan condensate connection to

prevent the pan from overflowing. Prime the trap with water.
Connect a drain tube using a minimum of 3/4 --in. PVC, 3/4 --in.

CPVC, or 3/4 --in. copper pipe (all field supplied). Do not

undersize the tube. Pitch the drain tube downward at a slope of at
least 1 in. (25 mm) for every 10 ft (3 m) of horizontal run. Be sure

to check the drain tube for leaks. Prime trap at the beginning of the
cooling season start--up. Allowable glues for condensate trap

connection are: Standard ABS, CPVC, or PVC cement.

Step 7 — Install Electrical Connections

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
The unit cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of personal

injury if an electrical fault should occur. This ground may

consist of an electrical wire connected to the unit ground

screw in the control compartment, or conduit approved for

electrical ground when installed in accordance with NEC,

ANSI/NFPA 70 American National Standards Institute/

National Fire Protection Association (latest edition) (in

Canada, Canadian Electrical Code CSA C22.1) and local

electrical codes.

!

WARNING

UNIT COMPONENT DAMAGE HAZARD

Failure to follow this caution may result in damage to the

unit being installed.

1. Make all electrical connections in accordance with NEC

ANSI/NFPA 70 (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical

connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit. DO

NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within

operating voltage range indicated on unit rating plate. On

3--phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of

improper voltage and/or phase imbalance.

4. Do not damage internal components when drilling

through any panel to mount electrical hardware, conduit,
etc.

!

CAUTION

HIGH--VOLTAGE CONNECTIONS — The unit must have a
separate electrical service with a field--supplied, waterproof

disconnect switch mounted at, or within sight from the unit. Refer

to the unit rating plate for maximum fuse/circuit breaker size and
minimum circuit amps (ampacity) for wire sizing.

The field--supplied disconnect may be mounted on the unit over
the high--voltage inlet hole. See Fig. 2--4.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
ROUTING POWER LEADS INTO UNIT — Use only copper

wire between disconnect and unit. The high--voltage leads should
be in a conduit until they enter the unit; conduit termination at the

unit must be watertight. Run the high--voltage leads through the
hole on the control box side of the unit (see Fig. 10 for location).

When the leads are inside the unit, run leads to the control box

(Fig. 11). For single--phase units, connect leads to the black and
yellow wires; for 3--phase units, connect the leads to the black,

yellow, and blue wires (see Fig. 12).
CONNECTING GROUND LEAD TO UNIT GROUND — Refer

to Fig. 11 and 12. Connect the ground lead to the chassis using the

unit ground lug in the control box.

GROUND
LUG

INDOOR
FAN
RELAY

OUTDOOR FAN MOTOR
AND COMPRESSOR
START CAPACITOR

HIGH
VOLTAGE
LEADS

A10019

Fig. 11 -- Control Box Wiring

3-PHASE

CONNECTIONS

TO DISCONNECT

PER NEC

SINGLE-PHASE

CONNECTIONS

TO DISCONNECT

PER NEC

GROUND

LEAD

UNIT GROUND

BLK

YEL

BLU

L

L

L

C00012

Fig. 12 -- Line Power Connections

R

G

Y

W1

W2

RED

GRN

YEL

UNIT CONTROL BOX

THERMOSTAT

AND SUBBASE

C00013

Fig. 13 -- Control Connections

50Z

P

Summary of Contents for 50ZP024

Page 1: ...gency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing C00001 Fig 1 50ZP Size 036...

Page 2: ...E OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE W...

Page 3: ...DUCT SIDE OF UNIT 0 SIDE OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT...

Page 4: ...T 0 DUCT SIDE OF UNIT 0 SIDE OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 U...

Page 5: ...the unit where water ice or snow from an overhang or roof will damage or flood the unit The unit may be installed on wood flooring or on Class A B or C roof covering materials Step 4 Place Unit Unit...

Page 6: ...arge ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance operations on the system turn off main power to unit and i...

Page 7: ...ive 10x8 254 x 203 800 550 1000 3 Low 1 4 10x8 254 x 203 1000 550 1000 3 Med 1 4 10x8 254 x 203 1200 800 1050 3 Low 1 2 10x9 254 x 229 1400 800 1050 3 Med 1 2 10x9 254 x 229 1600 1000 1100 2 Low 3 4 1...

Page 8: ...local electrical codes governing such wiring In Canada all electrical connections must be in accordance with CSA standard C22 1 Canadian Electrical Code Part 1 and applicable local codes Refer to uni...

Page 9: ...rigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrige...

Page 10: ...rging charts are different from the type normally used Charts are based on charging the units to the correct superheat for the various operating conditions Accurate pressure gage and temperature sensi...

Page 11: ...46 45 7 55 13 65 18 75 24 95 35 105 41 85 29 C00016 Fig 15 Cooling Charging Chart 50ZP030 Units OUTDOOR TEMP F C 115 46 45 7 55 13 65 18 75 24 95 35 105 41 85 29 C00017 Fig 16 Cooling Charging Chart 5...

Page 12: ...als of the thermostat On units with a compressor time delay relay there is a 5 minute 45 sec delay between compressor starts Energizing the compressor contactor supplies power to the compressor and th...

Page 13: ...d result in personal injury or death Disconnect electrical power and install lockout tag to the unit before cleaning and lubricating the blower motor and wheel WARNING To clean the blower wheel 1 Acce...

Page 14: ...proper operation If discrepancies are observed in operating cycle or if a suspected malfunction has occurred check each electrical component with the proper electrical instrumentation Refer to the un...

Page 15: ...25 1960 1901 1855 1752 1468 1121 High Watts 1073 1038 1001 958 896 840 800 691 575 Cfm 2230 2202 2160 2122 2052 1926 1791 1588 1202 060 3 Speed Low Watts 1058 1008 942 891 860 828 750 700 630 Cfm 2384...

Page 16: ...16 A10093 Fig 21 50ZP 208 230 1 Wiring Diagram 50ZP...

Page 17: ...17 A10094 Fig 22 50ZP 208 230 3 Wiring Diagram 50ZP...

Page 18: ...Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate re...

Page 19: ...at unit installation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 __________ L2 L3 __________ L3 L1 __________ Compressor Am...

Page 20: ...W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 02 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: