background image

5

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate clothing.

!

CAUTION

These instructions cover minimum requirements and conform to

existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,

especially those that may not have kept up with changing
residential construction practices. We require these instructions as a

minimum for a safe installation.
GENERAL — 50ZP cooling units are fully self--contained and

designed for outdoor installation. See Fig. 1. As shown in Fig. 2--4,

units are shipped in a horizontal--discharge configuration for
installation on a ground--level slab. All units can be

field--converted to downflow discharge configurations for rooftop
applications with a field--supplied plenum

RECEIVING AND INSTALLATION

Step 1 — Check Equipment

IDENTIFY UNIT — The unit model number and serial number
are stamped on the unit identification plate. Check this information

against shipping papers.
INSPECT SHIPMENT — Inspect for shipping damage while unit
is still on shipping pallet. If unit appears to be damaged or is torn

loose from its securing points, have it examined by transportation
inspectors before removal. Forward claim papers directly to

transportation company. Manufacturer is not responsible for any

damage incurred in transit.
Check all items against shipping list. Immediately notify the

nearest Carrier Air Conditioning office if any item is missing.
To prevent loss or damage, leave all parts in original packages until

installation.

Step 2 — Provide Unit Support

SLAB MOUNT — Place the unit on a rigid, level surface, suitable
to support the unit weight. The flat surface should extend

approximately 2--in. (51 mm) beyond the unit casing on the 2
sides. The duct connection side and condensate drain connection

sides should be flush with the edge of the flat surface. A concrete

pad or a suitable fiberglass mounting pad is recommended.
A 6--in. (152 mm) wide gravel apron should be used around the

flat surface to prevent airflow blockage by grass or shrubs. Do not
secure the unit to the flat surface except where required by local

codes.
The unit should be level to within 1/4 in. (6 mm). This is necessary

for the unit drain to function properly.

Step 3 — Provide Clearances

The required minimum service clearances and clearances to
combustibles are shown in Fig. 2--4. Adequate ventilation and

condenser air must be provided.
The condenser fan pulls air through the condenser coil and

discharges it through the fan on the top cover. Be sure that the fan

discharge does not recirculate to the condenser coil. Do not locate
the unit in either a corner or under an overhead obstruction. The

minimum clearance under a partial overhang (such as a normal
house overhang) is 48 in. (1219 mm) above the unit top. The

maximum horizontal extension of a partial overhang must not

exceed 48 in. (1219 mm).
Do not place the unit where water, ice, or snow from an overhang

or roof will damage or flood the unit. The unit may be installed on
wood flooring or on Class A, B, or C roof covering materials.

Step 4 — Place Unit

Unit can be moved with the handholds provided in the unit
basepan. Refer to Table 1 for operating weights. Use extreme

caution to prevent damage when moving the unit. Unit must

remain in an upright position during all moving operations. The
unit must be level for proper condensate drainage; the

ground--level pad must be level before setting the unit in place.
When a field--fabricated support is used, be sure that the support is

level and that it properly supports the unit.

Step 5 — Select and Install Ductwork

The design and installation of the duct system must be in
accordance with:

S

the standards of the NFPA (National Fire Protection Association)

for installation of nonresidence--type air conditioning and

ventilating systems;

S

NFPA90A or residence--type, NFPA90B; and/or local codes and

residence--type, NFPA 90B;

S

and/or local codes and ordinances.

Select and size ductwork, supply--air registers and return--air grilles

according to ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) recommendations.
Use the duct flanges provided on the supply-- and return--air

openings on the side of the unit. See Fig. 2--4 for connection sizes
and locations. The 14--in. (356 mm) round duct collars (size

024--048 units) are shipped inside the unit attached to the indoor
blower. They are field--installed and must be removed from the

indoor cavity prior to start--up, even if they are not used for
installation.
INSTALL FLANGES FOR DUCTWORK CONNECTIONS

(50ZP060 ONLY) — The 50ZP060 units are shipped with flanges
which must be field--installed on the unit.
To install unit flanges:

1. Five pieces of flange are shipped on the return--air opening

of the unit. Remove the flanges from the shipping position.
See Fig. 5. Screws are field--supplied.

2. One piece of flange is used as it is shipped (straight). Bend

the other 4 pieces at right angles.

3. Install the straight flange on the right side of the return--air

opening in holes provided. See Fig. 6. Flanges should stick
out from unit to allow for connection of ductwork.

4. Install 2 hand--formed flanges onto return air opening in

holes provided to form a rectangle around the return air

opening.

5. Install remaining 2 hand--formed flanges around discharge

air opening in holes provided.

6. Ductwork can now be attached to flanges.

When designing and installing ductwork, consider the following:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage to unit

components.
When connecting ductwork to units, do not drill deeper

than 3/4 in. (19.1 mm) in shaded area shown in Fig. 7 or

coil may be damaged.

CAUTION

!

S

All units should have field--supplied filters installed in the

return--air side of the unit. Recommended sizes for filters are

shown in Table 1.

S

Avoid abrupt duct size increases and reductions. Abrupt change

in duct size adversely affects air performance. Use flexible
connectors between ductwork and unit to prevent transmission of

vibration. Use suitable gaskets to ensure weathertight and airtight

seal.

50Z

P

Summary of Contents for 50ZP024

Page 1: ...gency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with the kits or accessories when installing C00001 Fig 1 50ZP Size 036...

Page 2: ...E OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT AND BLOCK OR CONCRETE W...

Page 3: ...DUCT SIDE OF UNIT 0 SIDE OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 UNIT...

Page 4: ...T 0 DUCT SIDE OF UNIT 0 SIDE OPPOSITE DUCTS 0 BOTTOM OF UNIT 0 NEC REQUIRED CLEARANCES INCHES mm BETWEEN UNITS POWER ENTRY SIDE 42 00 1066 8 UNIT AND UNGROUNDED SURFACES POWER ENTRY SIDE 36 00 914 0 U...

Page 5: ...the unit where water ice or snow from an overhang or roof will damage or flood the unit The unit may be installed on wood flooring or on Class A B or C roof covering materials Step 4 Place Unit Unit...

Page 6: ...arge ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance operations on the system turn off main power to unit and i...

Page 7: ...ive 10x8 254 x 203 800 550 1000 3 Low 1 4 10x8 254 x 203 1000 550 1000 3 Med 1 4 10x8 254 x 203 1200 800 1050 3 Low 1 2 10x9 254 x 229 1400 800 1050 3 Med 1 2 10x9 254 x 229 1600 1000 1100 2 Low 3 4 1...

Page 8: ...local electrical codes governing such wiring In Canada all electrical connections must be in accordance with CSA standard C22 1 Canadian Electrical Code Part 1 and applicable local codes Refer to uni...

Page 9: ...rigerant from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals 3 Never attempt to repair soldered connection while refrige...

Page 10: ...rging charts are different from the type normally used Charts are based on charging the units to the correct superheat for the various operating conditions Accurate pressure gage and temperature sensi...

Page 11: ...46 45 7 55 13 65 18 75 24 95 35 105 41 85 29 C00016 Fig 15 Cooling Charging Chart 50ZP030 Units OUTDOOR TEMP F C 115 46 45 7 55 13 65 18 75 24 95 35 105 41 85 29 C00017 Fig 16 Cooling Charging Chart 5...

Page 12: ...als of the thermostat On units with a compressor time delay relay there is a 5 minute 45 sec delay between compressor starts Energizing the compressor contactor supplies power to the compressor and th...

Page 13: ...d result in personal injury or death Disconnect electrical power and install lockout tag to the unit before cleaning and lubricating the blower motor and wheel WARNING To clean the blower wheel 1 Acce...

Page 14: ...proper operation If discrepancies are observed in operating cycle or if a suspected malfunction has occurred check each electrical component with the proper electrical instrumentation Refer to the un...

Page 15: ...25 1960 1901 1855 1752 1468 1121 High Watts 1073 1038 1001 958 896 840 800 691 575 Cfm 2230 2202 2160 2122 2052 1926 1791 1588 1202 060 3 Speed Low Watts 1058 1008 942 891 860 828 750 700 630 Cfm 2384...

Page 16: ...16 A10093 Fig 21 50ZP 208 230 1 Wiring Diagram 50ZP...

Page 17: ...17 A10094 Fig 22 50ZP 208 230 3 Wiring Diagram 50ZP...

Page 18: ...Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate re...

Page 19: ...at unit installation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 __________ L2 L3 __________ L3 L1 __________ Compressor Am...

Page 20: ...W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 02 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Reviews: