background image

28

MOISTUREMISER SYSTEM CHARGING — The  system
charge for units with the MoistureMiser option is greater than
that of the standard unit alone. The charge for units with this
option is indicated on the unit nameplate drawing. To charge
systems using the MoistureMiser Dehumidification package,
fully evacuate, recover, and re-charge the system to the name-
plate specified charge level. To check or adjust refrigerant
charge on systems using the MoistureMiser Dehumidification
package, charge per the standard subcooling charts. The sub-
cooler MUST be deenergized to use the charging charts. The
charts reference a liquid pressure (psig) and temperature at a
point between the condenser coil and the subcooler coil. A tap
is provided on the unit to measure liquid pressure entering the
subcooler (leaving the condenser).

Filter Drier — 

Replace whenever refrigerant system is ex-

posed to atmosphere.

Protective Devices

COMPRESSOR PROTECTION
Overcurrent — Each compressor has internal line break motor
protection, except the circuit no. 1 on the 50TJ028 unit. Com-
pressor no. 1 on the 50TJ028 unit uses an electronic module lo-
cated with the compressor junction box, to provide motor pro-
tection. This electronic module monitors winding and dis-
charge temperatures. If these temperatures reach the trip
values, the module interrupts the control line and causes the
compressor to switch off.
Crankcase Heater — Only the 50TJ028 unit and units with
the optional MoistureMiser Dehumidification system are
equipped with a 70-watt crankcase heater to prevent absorption
of liquid refrigerant by oil in the crankcase when the compres-
sor is idle. The crankcase heater is energized whenever there is
a main power to the unit and the compressor is not energized.

Compressor Lockout — If any of the safeties (high-pressure,
low-pressure, freeze protection thermostat, compressor internal
thermostat) trip, or if there is loss of power to the compressors,
the CLO (compressor lockout) will lock the compressors off.
To reset, manually move the thermostat setting.
EVAPORATOR FAN MOTOR PROTECTION — A  manu-
al reset, calibrated trip, magnetic circuit breaker protects
against overcurrent. Do not bypass connections or increase the
size of the breaker to correct trouble. Determine the cause and
correct it before resetting the breaker.
CONDENSER-FAN MOTOR PROTECTION —  Each
condenser-fan motor is internally protected against
overtemperature.
HIGH- AND LOW-PRESSURE SWITCHES — If  either
switch trips, or if the compressor overtemperature switch acti-
vates, that refrigerant circuit will be automatically locked out
by the CLO. To reset, manually move the thermostat setting.
FREEZE PROTECTION THERMOSTAT (FPT) — An FPT
is located on the top and bottom of the evaporator coil. It de-
tects frost build-up and turns off the compressor, allowing the
coil to clear. Once the frost has melted, the compressor can be
reenergized.

Relief Devices — 

All units have relief devices to protect

against damage from excessive pressures (e.g., fire). These de-
vices protect the high and low side.

Control Circuit, 24-V — 

This control circuit is protect-

ed against overcurrent by a 3.2-amp circuit breaker. Breaker
can be reset. If it trips, determine cause of trouble before
resetting.

Replacement Parts — 

A complete list of replacement

parts may be obtained from any Carrier distributor upon
request.

EconoMi$er LEDs — 

The EconoMi$er control module

has an LED for diagnostic purposes. The flash code identifica-
tion is shown in Table 15.

Optional Hinged Access Doors — 

When the optional

service package is ordered or the if the hinged access doors
option is ordered, the unit will be provided with external and
internal hinged access doors to facilitate service.

Four external hinged access doors are provided. All external

doors are provided with 2 large 

1

/

4

 turn latches with folding

bail-type handles. (Compressor access doors have one latch.) A
single door is provided for filter and drive access. One door is
provided for control box access. The control box access door is
interlocked with the non-fused disconnect which must be in the
OFF position to open the door. Two doors are provided for ac-
cess to the compressor compartment.

Two internal access doors are provided inside the filter/

drive access door. The filter access door (on the left) is secured
by 2 small 

1

/

4

 turn latches with folding bail-type handles. This

door must be opened prior to opening the drive access door.
The drive access door is shipped with 2 sheet metal screws
holding the door closed. Upon initial opening of the door, these
screws may be removed and discarded. The door is then held
shut by the filter access door, which closes over it. 

IMPORTANT: After prolonged shutdown or servicing,
energize the crankcase heaters for 24 hours before start-
ing the compressors.

50

40

100

150

200

250

300

350

400

60

80

100

120

140

ALL OUTDOOR FANS MUST BE OPERATING

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

LIQUID 

TEMPERA

TURE 

A

T

 LIQUID V

A

L

VE (DEG F)

BOTH CIRCUITS

REDUCE CHARGE IF BELOW CURVE

ADD CHARGE IF ABOVE CURVE

Fig. 36 — Cooling Charging Chart

Summary of Contents for 50TJ016

Page 1: ...f curb or horizontal adapter roof curb are shown in Fig 1 and 2 Install insulation cant strips roofing and counter flashing as shown Ductwork can be secured to roof curb before unit is set in place Curb or adapter roof curb should be level This is necessary to permit unit drain to function properly Unit leveling toler ance is 1 16 in per linear ft in any direction Refer to Accesso ry Roof Curb or ...

Page 2: ... for units equipped with electric heaters NOTE To prevent the hazard of stagnant water build up in the drain pan of the indoor section unit can only be pitched as shown DIMENSIONS degrees and inches UNIT A B Deg in Deg in ALL 28 45 28 43 PKG NO REF CURB HEIGHT DESCRIPTION CRRFCURB010A00 1 2 305 Standard Curb 14 High CRRFCURB011A00 2 0 610 Standard Curb for Units Requiring High Installation CRRFCUR...

Page 3: ...o rigging 4 Rig by inserting hooks into unit base rails as shown Use corner post from packaging to protect coil from damage Use bumper boards for spreader bars 5 Weights do not include optional EconoMi er See Fig 4 and 5 for EconoMi er weight See Table 1 for MoistureMiser weight 6 Weights given are for aluminum evaporator and condenser coil plate fins Fig 3 Rigging Details UNIT 50TJ MAXIMUM SHIPPI...

Page 4: ...to be attached to accessory roof curb only 6 Minimum clearance Rear 7 0 2134 for coil removal This dimension can be reduced to 4 0 1219 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and power exhaust if so equipped Top 6 0 1829 to assure proper condenser fa...

Page 5: ...o be attached to accessory roof curb only 6 Minimum clearance Rear 7 0 2134 for coil removal This dimension can be reduced to 4 0 1219 if conditions permit coil removal from the top Left side 4 0 1219 for proper condenser coil airflow Front 4 0 1219 for control box access Right side 4 0 1219 for proper operation of damper and power exhaust if so equipped Top 6 0 1829 to assure proper condenser fan...

Page 6: ...lt Nominal Cfm 6000 6000 7200 8000 10 000 Motor Hp 3 7 3 0 5 7 5 10 Motor Nominal Rpm 1725 1725 1745 1745 1740 Maximum Continuous Bhp 4 25 3 45 5 90 8 7 208 230 575 v 9 5 460 v 10 2 208 230 575 v 11 8 380 460 v Motor Frame Size 56H 56H 184T 213T 215T Nominal Rpm High Low Fan r s Range Low Medium Static 891 1179 1159 1429 910 1095 1002 1225 1066 1283 High Static 1227 1550 1069 1287 1193 1458 1332 1...

Page 7: ...e and must be removed when unit is operating One 3 4 in half coupling is provided inside unit evaporator section for conden sate drain connection An 81 2 in x 3 4 in diameter nipple and a 2 in x 3 4 in diameter pipe nipple are coupled to standard 3 4 in diameter elbows to provide a straight path down through holes in unit base rails see Fig 10 A trap at least 4 in deep must be used For vertical su...

Page 8: ...rature Route thermostat cable or equivalent single leads of no 18 AWG American Wire Gage colored wire from subbase termi nals through conduit in unit to low voltage connections as shown on unit label wiring diagram and in Fig 12 NOTE For wire runs up to 50 ft use no 18 AWG insulated wire 35 C minimum For 50 to 75 ft use no 16 AWG insu lated wire 35 C minimum For over 75 ft use no 14 AWG insulated ...

Page 9: ... 0 5 1 7 5 0 15 8 15 8 87 87 110 110 4 6 18 8 92 92 110 110 26 34 71 82 109 122 110 125 4 6 18 8 26 34 71 82 114 128 125 150 42 56 117 135 166 155 175 175 4 8 18 8 42 56 117 135 172 161 175 175 56 75 156 180 176 200 200 225 4 6 18 8 56 75 156 180 182 206 200 225 460 414 508 15 5 114 14 7 95 3 0 5 0 8 5 0 7 9 44 50 2 3 6 0 47 60 32 39 59 60 2 3 6 0 32 39 61 70 55 66 76 90 2 3 6 0 55 66 79 90 80 96 ...

Page 10: ...1 25 x IFM amps 1 00 x heater FLA UNIT 50TJ NOMINAL VOLTAGE 3 Ph 60 Hz VOLTAGE RANGE COMPRESSOR OFM IFM POWER EXHAUST ELECTRIC HEAT POWER SUPPLY No 1 No 2 Min Max RLA LRA RLA LRA Qty Hp FLA ea Hp FLA FLA LRA kW FLA MCA MOCP 028 25 Tons 208 230 187 253 41 0 350 37 8 239 2 1 6 6 10 0 28 0 28 0 130 130 150 150 4 6 18 8 135 135 175 175 26 34 71 82 130 138 150 150 4 6 18 8 26 34 71 82 135 143 175 175 4...

Page 11: ...d close the door The handle should fit over the end of the shaft when the door is closed 8 The handle must be in the OFF position to open the con trol box door OPTIONAL CONVENIENCE OUTLET On units with optional convenience outlet a 115 v GFI ground fault inter rupt convenience outlet receptacle is provided for field wiring Field wiring should be run through the 7 8 in knockout pro vided in the bas...

Page 12: ...N Perform the following procedure to install the out door air enthalpy sensor part no CROUTENT001A00 1 Remove the outdoor air temperature sensor cover See Fig 21 Save cover and screws 2 Disconnect the wiring from the installed outdoor air tem perature sensor See Fig 22 3 Use a 1 4 in nut driver to remove the 2 screws securing the outdoor air temperature sensor to the sheet metal 4 Mount the outdoo...

Page 13: ... in the fan section of the unit The DAT is factory wired to the EconoMi er Control Module CO2 CONTROL SETUP If a CO2 sensor is not being used proceed to the next section If a CO2 sensor is being used perform the following 1 Determine the value at which you want the minimum position of the dampers to begin opening to allow a greater amount of outdoor air to enter The range is 800 to 1 400 ppm 2 Loc...

Page 14: ...noMi er Switchover Control Strategy Must be selected manually Table 5 Changeover Set Points Field installed accessory Table 6 Default Potentiometer Settings ECONOMI ER SWITCHOVER STRATEGY SENSORS REQUIRED Outdoor Air Temperature Outdoor Air Enthalpy Return Air Temperature Return Air Enthalpy Dry Bulb X Single Enthalpy X Differential Temperature X X Differential Enthalpy X X SETTINGS A B C D Dry Bu...

Page 15: ...ind Baffles Wind baffles must be field fabricated for all units to ensure proper cooling cycle operation at low ambient temperatures See Fig 25 for baffle details Use 20 gage galvanized sheet metal or similar corrosion resistant metal for baffles Use field supplied screws to attach baffles to unit Screws should be 1 4 in diameter and 5 8 in long Drill required screw holes for mounting baffles Outd...

Page 16: ...ce outdoor fan motor no 1 with motor included in accessory kit Existing motor is not Motormaster III compatible Install Motormaster III Controls Only one Motormaster III control is required per unit Sensor Install the sensor for thermistor input control in the location shown in Fig 27 Connect sensor leads to the purple and grey control signal leads on the Motormaster III control Signal Selection S...

Page 17: ...ION HAIRPIN END SENSOR LOCATION HAIRPIN END NOTE All sensors are located on the eighth hairpin up from the bottom Fig 27 Motormaster III Sensor Locations Fig 28 Typical MoistureMiser Dehumidification Package Humidistat Wiring Schematic 460V Unit Shown LEGEND LLSV Liquid Line Solenoid Valve LPS Low Pressure Switch TB Terminal Block TRAN Transformer 50TJ016 50TJ020 50TJ024 50TJ028 ...

Page 18: ...and discharge pressure levels should now move to their normal start up levels NOTE When compressors are rotating in the wrong direction the unit will have increased noise levels and will not provide heating and cooling After a few minutes of reverse operation the scroll com pressor internal overload protection will open which will acti vate the unit s lockout and requires a manual reset Reset is a...

Page 19: ...m Bhp Watts Rpm Bhp Watts Rpm Bhp Watts 4500 684 1 28 1102 791 1 49 1283 887 1 70 1466 977 1 92 1652 1061 2 13 1841 1139 2 36 2034 4800 715 1 47 1265 817 1 68 1451 910 1 90 1638 997 2 12 1828 1078 2 34 2021 1155 2 57 2217 5100 747 1 67 1442 844 1 89 1633 934 2 12 1825 1018 2 34 2019 1097 2 57 2216 1171 2 80 2416 5400 779 1 90 1635 872 2 12 1831 959 2 35 2027 1040 2 58 2226 1117 2 81 2426 1189 3 05...

Page 20: ...2441 965 3 22 2712 1027 3 56 2990 6 000 730 2 38 2005 802 2 68 2257 871 2 99 2516 935 3 31 2783 997 3 63 3057 1056 3 97 3337 6 500 778 2 82 2373 846 3 13 2630 911 3 44 2893 972 3 76 3164 1031 4 09 3440 1087 4 43 3722 7 000 828 3 31 2780 892 3 62 3042 953 3 94 3310 1011 4 26 3583 1067 4 59 3863 1121 4 93 4148 7 500 878 3 84 3227 938 4 15 3494 996 4 48 3766 1051 4 81 4043 1105 5 14 4326 1156 5 49 46...

Page 21: ...883 1137 5 08 4 200 7 500 896 3 82 3156 956 4 17 3450 1014 4 54 3752 1069 4 91 4060 1123 5 29 4375 1174 5 68 4 698 8 000 948 4 43 3667 1005 4 80 3969 1060 5 17 4278 1112 5 56 4593 1163 5 94 4915 1213 6 34 5 243 8 500 1001 5 11 4226 1054 5 49 4537 1106 5 87 4853 1156 6 26 5175 1205 6 66 5504 1253 7 06 5 838 9 000 1053 5 85 4836 1104 6 23 5155 1154 6 63 5478 1202 7 02 5808 1248 7 43 6142 1294 7 84 6...

Page 22: ...07 0 09 0 11 0 12 32 0 06 0 07 0 09 0 11 0 12 35 0 07 0 08 0 12 0 15 0 17 42 56 0 07 0 08 0 12 0 16 0 17 50 0 09 0 10 0 15 0 20 0 21 55 0 07 0 08 0 12 0 15 0 17 56 75 0 09 0 10 0 15 0 20 0 21 80 0 09 0 10 0 15 0 20 0 21 FIOP Factory Installed Option COMPONENT CFM 5400 6000 7200 9000 10 000 11 250 EconoMi er 0 06 0 07 0 09 0 11 0 12 0 14 Glycol Coil 0 30 0 35 0 44 0 58 0 66 0 77 Electric Heat kW 20...

Page 23: ...il It detects frost build up and turns off the compressor allowing the coil to clear Once frost has melted the compressor can be reenergized by resetting the compressor lockout HEATING UNITS WITH ECONOMI ER If Accessory or Optional Heater is Installed When the room thermostat calls for heat the heating controls are energized as described in the Heating Units Without EconoMi er section The IFM is e...

Page 24: ...perating conditions require Refer to Table 1 for type and size NOTE The 50TJ028 unit requires industrial grade throwaway filters capable of withstanding face velocities up to 625 fpm Ensure that replacement filters for the 50TJ028 units are rated for 625 fpm OUTDOOR AIR INLET SCREENS Clean screens with steam or hot water and a mild detergent Do not use throwaway filters in place of screens Lubrica...

Page 25: ...on Adjustment section on page 26 To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along fan shaft 3 Make angular alignment by loosening motor from mounting plate Evaporator Fan Service and Replacement 50TJ016 UNITS See Fig 32 NOTE To remove belts only follow Steps 1 6 1 Remove filter and supply air section panels 2 Remove unit top panel 3 Loosen carriage nuts A and B...

Page 26: ... 5 Tighten setscrews and replace panel s 6 Turn on unit power 50TJ024 028 UNITS Fig 35 1 Shut off unit power supply 2 Remove fan top grille assembly and loosen fan hub screws 3 Adjust fan height on unit using a straightedge placed across the fan orifice 4 Tighten setscrews and replace rubber hubcap to prevent hub from rusting to motor shaft 5 Fill hub recess with permagum if rubber hubcap is missi...

Page 27: ...nd procedures Unit panels must be in place when unit is operating during charging procedure NOTE Do not use recycled refrigerant as it may contain con taminants NO CHARGE Use standard evacuating techniques After evacuating system weigh in the specified amount of refriger ant refer to Table 1 LOW CHARGE COOLING Using cooling charging chart see Fig 36 add or remove refrigerant until conditions of th...

Page 28: ... PRESSURE SWITCHES If either switch trips or if the compressor overtemperature switch acti vates that refrigerant circuit will be automatically locked out by the CLO To reset manually move the thermostat setting FREEZE PROTECTION THERMOSTAT FPT An FPT is located on the top and bottom of the evaporator coil It de tects frost build up and turns off the compressor allowing the coil to clear Once the ...

Page 29: ...29 Fig 37 Typical Wiring Schematic 50TJ024 208 230 3 60 Shown ELECTRIC HEAT 208 240 v Amps 200 230 v kW A 71 3 82 3 25 7 34 2 B 117 135 42 2 56 1 C 156 180 56 2 74 8 ...

Page 30: ...30 Fig 37 Typical Wiring Schematic 50TJ024 208 230 3 60 Shown cont Fig 38 Typical Component Arrangement 50TJ024 Shown ...

Page 31: ...r Terminal Marked Terminal Unmarked Terminal Block Splice Factory Wiring Field Control Wiring Option Accessory Wiring To indicate common potential only not to represent wiring NOTES 1 Compressor and fan motor s thermally protected 3 phase motors protected against primary single phasing conditions 2 If any of the original wire furnished must be replaced it must be replaced with type 90 C wire or it...

Page 32: ...eplace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil...

Page 33: ... MIN POS to 100 to verify operation and then set to correct setting EconoMi er Changeover Set Point Set Too High or Too Low Set at correct value See Table 5 Discharge Air Thermistor Faulty If STATUS light is flashing 4 flashes Discharge Air Thermistor is faulty Check wiring or replace sensor Outdoor Air Temperature Sensor Faulty If STATUS light is flashing 5 flashes Outdoor Air Temperature Sensor ...

Page 34: ...d in this manual including Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product theory and skills programs are available using popular video based formats and materials All include video and or slides plus companion book Classroom Service Training which includes hands on experience with the products in our labs can mean increased confidence that re...

Page 35: ......

Page 36: ...N IN HOUSING ORIFICE AND VERIFY SETSCREW IS TIGHT VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED VERIFY THAT SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION VERIFY THAT CRANKCASE HEATER HAS BEEN ENERGIZED FOR 24 HOURS SIZE 028 AND UNITS WITH OPTIONAL MOISTUREMISER DEHUMIDIFICATION SYSTEM ONLY START UP ELECTRICAL SUPPLY FAN AMPS EXHAUST FAN AMPS TEMPERATURES OUTDOOR AIR...

Reviews: