56
8. Setting the Ramp Time:
a. Press the Back key until the following display
appears:
b. Press
▼
(Down Arrow) twice, the following display
appears:
c. Press OK, the following display appears:
d. Press OK again to highlight the bottom row and use
the
▲
and
▼
(Up and Down Arrow) keys to select
10.00s. Press OK again to set the selected Ramp up
Time.
e. Press
▼
(Down Arrow) once, the following display
appears:
f. Press OK again to highlight the bottom row and use
the
▲
and
▼
(Up and Down Arrow) keys to select
10.00s. Press OK again to set the selected Ramp
Down Time.
9. Setting Limits:
a. Press the Back key until the following display
appears:
b. Press
▼
(Down Arrow) once, the following display
appears:
c. Press OK, the following display appears:
d. Press OK again, the following display appears:
e. Press
▼
(Down Arrow) once, the following display
appears:
f. Press
▼
(Down Arrow) again, the following display
appears:
NOTE: Press OK to highlight the Hz value and then use the
▲
and
▼
(Up and Down Arrow) keys to enter the required values.
g. Press
▼
(Down Arrow) once, the following display
appears:
NOTE: Press OK to highlight the % value and then use the
▲
and
▼
(Up and Down Arrow) keys to enter the required value. See
Table 23-27 for proper selection of the value for this parameter,
then press OK to set the selected value.
h. Press
▼
(Down Arrow) once, the following display
appears:
NOTE: Press OK to highlight the Hz value and then use the
▲
and
▼
(Up and Down Arrow) keys to enter the required values.
10. Setting Digital Inputs:
a. Press the Back key until the following display
appears:
b. Press
▼
(Down Arrow) once, the following display
appears:
c. Press OK, the following display appears:
d. Press
▼
(Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis-
play appears:
e. Press
▼
(Down Arrow) again. The following display
appears:
f. Press
▼
(Down Arrow) again. The following display
appears:
g. Press
▼
(Down Arrow) again. The following display
appears:
NOTE: By pressing OK, the number in the bracket can be
changed until the desired number appears. Press OK again to set
the selected value.
11. Setting Analog Inputs:
a. Press the Back key until the following display
appears:
b. Press
▼
(Down Arrow) until the following display
appears:
c. Press OK, the following display appears:
3—0* Reference Limits
3—1* References
3—1* References
3—4* Ramp 1
3-41 Ramp 1 Ramp up Time
3.00s
3-42 Ramp 1 Ramp Down Time
3.00s
2—** Brakes
3—** Reference / Ramps
3—** Reference / Ramps
4—** Limits / Warnings
4—1* Motor Limits
4—4* Adj. Warning 2
4-10 Motor Speed Direction
[2] Both Directions
4-12 Motor Speed Low Limi…
0.0Hz
4-14 Motor Speed High Limi…
65.0Hz
4-18 Current Limit
110%
4-19 Max Output Frequency
65.0Hz
3—** Reference / Ramps
4—** Limits / Warnings
4—** Limits / Warnings
5—** Digital In/Out
5—0* Digital I/O mode
5—1* Digital Inputs
5-10 Terminal 18 Digital In…
[8] Start
5-11 Terminal 19 Digital In…
[16] Preset ref bit 0
5-12 Terminal 27 Digital In…
[17] Preset ref bit 1
5-13 Terminal 29 Digital In…
[18] Preset ref bit 2
4—** Limits / Warnings
5—** Digital In/Out
5—** Digital In/Out
6—** Analog In/Out
6—** Analog In/Out
6—1* Analog Input 53
Summary of Contents for 50LC 14
Page 26: ...26 Fig 34 50LC 14 26 Control Wiring Diagram...
Page 27: ...27 Fig 35 50LC 14 26 RTU Open Control Wiring Diagram...
Page 28: ...28 Fig 36 50LC 14 20 208 230V 3 Phase Power Wiring Diagram...
Page 29: ...29 Fig 37 50LC 24 26 208 230V 3 Phase Power Wiring Diagram...
Page 30: ...30 Fig 38 50LC 14 26 460V 575V 3 Phase Power Wiring Diagram...