background image

35

SYSTEM SETUP

INSTALL

01/01/10

N/A

Display order = MM/DD/YY
Setting order = DD, MM, then YY.

UNITS DEG

F

F or C

Sets economizer controller in degrees Fahrenheit or Celsius

EQUIPMENT

CONV

Conventional or HP

CONV = conventional; 
HP O/B = Ena

b

le Heat Pump mode. Use AUX2 I for Heat Pump input from 

thermostat or controller.
See Menu Note 4.

AUX2 IN

W

SD/W or HP(O)/HP(B) In CONV mode:

SD + Ena

b

les configuration of shutdown (default);

W = Informs controller that system is in heating mode. 
NOTE: If using 2-speed fan mode, you must program CONV mode for W. 
Shutdown is not availa

b

le in 2-speed fan mode. See Menu Note 4.

In HP O/B mode: 
HP(O) = energize heat pump on Cool (default); 
HP(B) = energize heat pump on heat.

FAN SPEED

2 speed

1 speed/2 speed

Sets the economizer controller for operation of 1 speed or 2 speed supply 
fan.
NOTE: 2-speed fan option also needs Heat (W1) programmed in AUX 2 In. 
See Menu Note 4.

FAN CFM

5000cfm

100 to 15000 cfm; 
increment 

b

y 100

UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate la

b

el for the specific unit.

AUX1 OUT

NONE

NONE
ERV
EXH2
SYS

Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator

††

• EXH2 = second damper position relay closure for second exhaust fan
• SYS = use output as an alarm signal

OCC

INPUT

INPUT or ALWAYS

OCCUPIED MODE BY EXTERNAL SIGNAL
When using a set

b

ack thermostat with occupancy out (24 vac), the 24 vac 

is input “INPUT” to the OCC terminal. If no occupancy output from the ther-
mostat then change program to “ALWAYS” OR add a jumper from terminal 
R to OCC terminal.

FACTORY DEFAULT

NO

NO or YES

Resets all set points to factory defaults when set to YES. LCD will 

b

riefly 

flash YES and change to NO 

b

ut all parameters will change to the factory 

default values.
NOTE: RECHECK AUX2 IN and FANTYPE for re

q

uired 2-speed values.

ADVANCED 

SETUP

MA LO SET

45°F

35 to 55 F; 
Incremented 

b

y 10

SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to achieve Freeze Protection (close damper and alarm if tem-
perature falls 

b

elow setup value).

FREEZE POS

CLO

CLO or MIN

FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN POS).

CO2 ZERO

0ppm

0 to 500 ppm;        
Increment 

b

y 10

CO

2

 ppm level to match CO

2

 sensor start level.

CO2 SPAN

2000ppm

1000 to 3000 ppm; 
Increment 

b

y 10

CO

2

 ppm span to match CO

2

 sensor.

STG3 DLY

2.0h

0 min, 5 min, 15 min, 
then 15 min intervals. 
Up to 4 hrs or OFF

COOLING STAGE 3 DELAY
Delay after stage 2 cool has 

b

een active. Turns on second  stage of cooling 

when economizer is first  stage and mechanical cooling is second  stage. 
Allows three stages of cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling

SD DMPR POS

CLO

CLO or OPN

Indicates shutdown signal from space thermostat or unitary controller. 
When controller receives 24 Vac input on the SD terminal in conventional 
mode, the OA damper will open if programmed for OPN and OA damper 
will close if programmed for CLO. All other controls, e.g., fans, etc. will shut 
off.

DA LO ALM

45 F (7 C)

35 to 65 F; (2 to 18 C) 
Incremented 

b

y 5 deg.

Used for alarm for when the DA air temperature is too low. Set lower range 
of alarm, 

b

elow this temperature the alarm will show on the display.

DA HI ALM

80 F (27 C)

70 to 180 F; (21 to  82 
C) Incremented 

b

y 5 

deg.

Used for alarm for when the DA air temperature is too high. Set upper 
range of alarm, a

b

ove this temperature the alarm will show on the display.

DCVCAL ENA

MAN

MAN (manual) AUTO

Turns on the DCV automatic control of the dampers. Resets ventilation 

b

ased on the RA, OA, and MA sensor conditions. Re

q

uires all 3 RA, OA, 

and MA sensors.

ADVANCED 

SETUP (CONT)

MAT T CAL

0.0°F

±2.5 F

SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali

b

ration temperature sen-

sor.

OAS T CAL

0.0°F

±2.5 F

OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali

b

ration temperature sen-

sor.

OA H CAL

0% RH

±10% RH

OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of cali

b

ration humidity sensor.

RA T CAL

0.0°F

±2.5 F

RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali

b

ration temperature sen-

sor.

RA H CAL

0% RH

±10% RH

RETURN AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of cali

b

ration humidity sensor.

DA T CAL

0.0°F

±2.5 F

DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of cali

b

ration temperature sen-

sor.

2SP FAN DELAY

5 Minutes

0 to 20 minutes in 1 
minute increments

TIME DELAY ON 2nd STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try to 
satisfy the call for second stage cooling 

b

efore the first stage mechanical 

cooling is ena

b

led.

Table 8 — Menu Structure* (cont)

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

NOTES

Summary of Contents for 50KC*A/B0 Series

Page 1: ...Smoke Detectors 38 PremierLink Controller Factory Option 38 RTU Open Controller Factory Installed Option 38 Controller Options 38 LOW AMBIENT Step 12 Adjust Factory Installed Options 39 Step 13 Instal...

Page 2: ...ETY HAZARD Failure to follow this warning could cause personal injury death and or equipment damage Puron R 410A refrigerant systems operate at higher pres sures than standard R 22 systems Do not use...

Page 3: ...tric Relief F Enthalpy Economizer w Barometric Relief K 2 Position Damper U Temp Ultra Low Leak Economizer w Baro Relief W Enthalpy Ultra Low Leak Econo w Baro Relief Base unit controls 0 Electro mech...

Page 4: ...4 Fig 2 Dimensional Drawing...

Page 5: ...5 Fig 2 Unit Dimensional Drawing cont...

Page 6: ...nit Select a unit mounting system that provides adequate height to allow installation of condensate trap per requirements Re fer to Step 10 Install External Condensate Trap and Line for required trap...

Page 7: ...e shown in Fig 4 Refer to Accessory Roof Curb Installation Instructions for additional information as required Fig 4 Unit Leveling Tolerances Install insulation cant strips roofing felt and counter fl...

Page 8: ...F CARRIER CORPORATION 1 DEC 2 DEC 3 DEC ANG MATERIAL AUTHORIZATION NUMBER TITLE 1041738 CURB ASY ROOF ENGINEERING MANUFACTURING 004 007 ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRA...

Page 9: ...onnection ensure the red plug in the alternate bottom connection is tight Do this be fore setting the unit in place The red drain pan plug can be tightened with a 1 2 in square socket drive extension...

Page 10: ...es are covered by the tape used to secure the insulation to the basepan and are not easily seen See Fig 8 for position of the notches in the basepan Seals around duct openings must be tight Secure wit...

Page 11: ...and remove Locate and cut the 2 plastic tie wraps secur ing the assembly to the damper See Fig 11 Be careful to not damage any wiring or cut tie wraps securing any wiring Fig 11 Economizer Hood Parts...

Page 12: ...its with Hinged Panels Only Relocate latch shipped inside the compressor compartment behind the hinged compressor door to location shown in Fig 15 after unit installation If the unit does not have hin...

Page 13: ...ed option non fused discon nect switch Max wire size is 2 AWG copper only See Fig 18 and unit label diagram for field power wiring connec tions NOTE TEST LEADS Unit may be equipped with short leads pi...

Page 14: ...nit front panel Fig 21 Handle and Shaft Assembly for NFD UNITS WITHOUT FACTORY INSTALLED NON FUSED DISCONNECT When installing units provide a disconnect switch per NEC National Electrical Code of adeq...

Page 15: ...owered Type This type requires the field installation of a general purpose 125 v 15 A circuit powered from a source elsewhere in the building Observe national and local codes when selecting wire size...

Page 16: ...tightness of connector lock nuts before connecting electrical conduits Field supplied and field installed liquid tight conduit connec tors and conduit may be attached to the connectors on the basepan...

Page 17: ...ructions for addi tional features which might require additional conductors in the cable For wire runs up to 50 ft 15 m use no 18 AWG American Wire Gage insulated wire 35 C 95 F minimum For 50 to 75 f...

Page 18: ...pped in cartons marked with a corresponding Heater Sales Package part number See Table 3 for correlation between Heater Model Number and Sales Package part number NOTE The value in position 9 of the p...

Page 19: ...nstalled option Hu midi MiZer is not available for size 04 06 single phase 3 voltage code models The Humidi MiZer dehumidification system requires a field supplied and field installed space relative h...

Page 20: ...20 Fig 34 Accessory Field Installed Humidistat Fig 35 Edge Pro Thermidistat Fig 36 Typical Humidi MiZer Adaptive Dehumidification System Humidistat Wiring RELATIVE HUMIDITY...

Page 21: ...umidification System with EDGE Pro Thermidistat Device Control and Power Wiring Diagrams See Fig 38 44 Rc Rh W1 G Y2 C O W2 B Y1 OAT RRS SRTN HUM D1 D2 V Vg X C G W2 W1 Y2 Y1 R EDGE Pro THERMIDISTAT U...

Page 22: ...22 Fig 38 Electro Mechanical Control Wiring Diagram...

Page 23: ...23 Fig 39 Electro Mechanical Control Wiring Diagram with Humidi MiZer System...

Page 24: ...24 Fig 40 Electro Mechanical Power Wiring...

Page 25: ...25 Fig 41 PremierLink Wiring Schematic...

Page 26: ...26 Fig 42 PremierLink Wiring Schematic with Humidi MiZer System...

Page 27: ...27 Fig 43 RTU Open System Control Wiring Diagram...

Page 28: ...28 Fig 44 RTU Open System Control Wiring Diagram with Humidi MiZer System...

Page 29: ...and other options are available with bus sensors User Interface Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD displ...

Page 30: ...m Left Terminal Block IAQ 2 10 2 10 vdc Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source ACT 2 10 2 10 vdc Damper Actuator...

Page 31: ...Buttons Press the Menu Up Exit button to exit a menu s item and return to the list of menus To use the keypad when work ing with Setpoints System and Advanced Settings Checkout tests and Alarms 1 Nav...

Page 32: ...the and arrow buttons to move for ward and backward through the menus and press the button to select and confirm setup item changes Time Out and Screensaver When no buttons have been pressed for 10 m...

Page 33: ...temperature Displays _ _ _F if sensor sends invalid value short or out of range OA HUM _ _ 0 to 100 OUTSIDE AIR RELATIVE HUMIDITY Displays measured value of outdoor humidity from OA sensor Displays _...

Page 34: ...th 2 speed fan units VENT L low speed fan and MIN POS H high speed fan settings are required Default for VENTMAX L is 3 2V and VENTMAX H is 2 8V VENTMIN With 2 speed fan units VENTMIN L low speed fan...

Page 35: ...ement by 10 CO2 ppm span to match CO2 sensor STG3 DLY 2 0h 0 min 5 min 15 min then 15 min intervals Up to 4 hrs or OFF COOLING STAGE 3 DELAY Delay after stage 2 cool has been active Turns on second st...

Page 36: ...CO2 sensor has failed gone out of range or become disconnected check wiring then replace sensor if the alarm continues OA SYLK T ERR N A N A OUTSIDE AIR S BUS SENSOR ERROR Outdoor air enthalpy sensor...

Page 37: ...UX2 I W FAN SPEED 2SPEED For damper minimum position settings and checkout menu readings see Table 9 MENU PARAMETER PARAMETER DEFAULT VALUE PARAMETER RANGE AND INCREMENT NOTES ALARMS CONT SHUTDOWN ACT...

Page 38: ...See Fig 51 Step 3 4 Connect the flexible tube on the sampling inlet to the sampling tube on the basepan ADDITIONAL APPLICATION DATA Refer to the application data document Factory Installed Smoke Detec...

Page 39: ...2 sensor DDC interface PremierLink Louvered hail guard Motormaster head pressure controls Phase monitor control Refer to separate installation instructions for information on installing these accessor...

Page 40: ...ntire liquid header assembly For more information see the 50KC04 06 Service and Maintenance Instructions Pre Start and Start Up This completes the mechanical installation of the unit Refer to the unit...

Page 41: ...41 Fig 55 50KC A B Sizes 04 05 Metering Devices ACCUTROL NOTE Each feeder tube in the liquid header has a metering device...

Page 42: ...42 Fig 56 50KC A B Sizes 06 Dual Metering Devices ACCUTROL ACCURATER NOTE Each feeder tube in the liquid header has a metering device...

Page 43: ...43 Fig 57 TXV Metering Device Position in Reheat Coil Typical Diagram for Sizes 04 06 TXV...

Page 44: ......

Page 45: ......

Page 46: ...o discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500199 01 Printed in U S A Form 50KC 4 6 02SI Pg 46 11 18 Replaces 50KC 4...

Page 47: ...location in housing orifice and verify setscrew is tight Y N _____ Verify that fan sheaves are aligned and belts are properly tensioned Y N _____ Verify that scroll compressors are rotating in the co...

Page 48: ...outdoor fan motor as condenser coil warms Y N _____ 4 Check unit charge per charging chart Y N _____ Jumper 32L Motormaster temperature sensor during this check Remove jumper when complete 5 Switch u...

Reviews: