Table 8 — Electrical Data, 48ZG,ZN035 Units
LEGEND
NOTE: Units use 1 (low heat) or 2 (high heat) combustion fan motors rated at
0.3 FLA each.
NOMINAL
VOLTAGE
(3 Ph 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
EXHAUST
FAN
POWER SUPPLY
No. 1
No. 2
RLA
LRA
RLA
LRA
Qty
Total
FLA
Hp
FLA
Total
Hp
Total
FLA
MCA
MOCP
208/230
187-254
53.2
266
69.2
345
2
6.6
(ea)
7
1
/
2
24.2/22.0
—
—/—
177.1/174.9
225/225
6
21.2/19.2
198.3/194.1
250/250
10
33.4/30.4
210.5/205.3
250/250
15
48.4/44.0
225.5/218.9
250/250
20
61.6/56.0
238.7/230.9
300/300
10
30.8/28.0
—
—/—
183.7/180.9
250/250
6
21.2/19.2
204.9/200.1
250/250
10
33.4/30.4
217.1/211.3
250/250
15
48.4/44.0
232.1/224.9
300/250
20
62.0/56.0
245.3/236.9
300/300
15
46.2/42.0
—
—/—
199.1/194.9
250/250
6
21.2/19.2
220.3/214.1
250/250
10
33.4/30.4
232.5/225.3
300/250
15
48.4/44.0
247.5/238.9
300/300
20
62.0/56.0
260.7/250.9
300/300
20
59.4/54.0
—
—/—
212.3/206.9
250/250
6
21.2/19.2
233.5/226.1
300/250
10
33.4/30.4
245.7/237.3
300/300
15
48.4/44.0
260.7/250.9
300/300
20
62.0/56.0
273.9/262.9
300/300
25
74.8/68.0
—
—/—
229.1/220.9
300/250
6
21.2/19.2
250.3/240.1
300/300
10
33.4/30.4
262.5/251.3
300/300
15
48.4/44.0
277.5/264.9
350/300
20
62.0/56.0
290.7/276.9
350/300
460
414-508
28.8
120
34.6
173
2
3.3
(ea)
7
1
/
2
11.0
—
—
89.7
110
6
9.6
99.3
125
10
15.2
104.9
125
15
22.0
111.7
125
20
28.0
117.7
150
10
14.0
—
—
92.7
125
6
9.6
102.3
125
10
15.2
107.9
125
15
22.0
114.7
125
20
28.0
120.7
150
15
21.0
—
—
99.7
125
6
9.6
109.3
125
10
15.2
114.9
125
15
22.0
121.7
150
20
28.0
127.7
150
20
27.0
—
—
105.7
125
6
9.6
115.3
125
10
15.2
120.9
150
15
22.0
127.7
150
20
28.0
133.7
150
25
34.0
—
—
112.7
125
6
9.6
122.3
150
10
15.2
127.9
150
15
22.0
134.7
150
20
28.0
140.7
175
575
518-632
23.1
96
26.7
120
2
2.4
(ea)
7
1
/
2
9.0
—
—
70.3
90
6
7.8
78.1
100
10
12.2
82.5
100
15
18.0
88.3
110
20
22.0
92.3
110
10
11.0
—
—
72.3
90
6
7.8
80.1
100
10
12.2
84.5
110
15
18.0
90.3
110
20
22.0
94.3
110
15
17.0
—
—
78.3
100
6
7.8
86.1
110
10
12.2
90.5
110
15
18.0
96.3
110
20
22.0
100.3
125
20
22.0
—
—
83.3
100
6
7.8
91.1
110
10
12.2
95.5
110
15
18.0
101.3
125
20
22.0
105.3
125
25
27.0
—
—
88.4
110
6
7.8
96.2
110
10
12.2
100.6
125
15
18.0
106.4
125
20
22.0
110.4
125
FLA
—
Full Load Amps
Hp
—
Nominal Horsepower
IFM
—
Indoor (Supply) Fan Motor
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps (for wire sizing)
MOCP —
Maximum Overcurrent Protection
OFM
—
Outdoor (Condenser) Fan Motor
RLA
—
Rated Load Amps
Summary of Contents for 48ZG
Page 15: ...15 Fig 3 Roof Curb Sizes 075 105 with High Capacity Power Exhaust...
Page 16: ...16 Fig 4 Condenser Section Roof Curb Size 055 and 060 Only...
Page 17: ...17 Fig 5 Condenser Section Roof Curb Size 070 105 Only...
Page 24: ...24 Fig 15 Base Unit Dimensional Drawing 48ZG ZN030 035 Standard Chassis...
Page 25: ...25 Fig 16 Base Unit Dimensional Drawing 48ZG ZN040 050 Standard Chassis...
Page 26: ...26 Fig 17 Base Unit Dimensional Drawing 48ZG ZN055 070 Standard Chassis...
Page 27: ...27 Fig 18 Base Unit Dimensional Drawing 48ZG ZN075 105 Standard Chassis a48 8451...
Page 28: ...28 Fig 19 Base Unit Dimensional Drawing 48ZG ZN030 035 Extended Chassis...
Page 29: ...29 Fig 20 Base Unit Dimensional Drawing 48ZG ZN040 050 Extended Chassis...
Page 30: ...30 Fig 21 Base Unit Dimensional Drawing 48ZG ZN055 060 Extended Chassis a48 8452...
Page 32: ...32 Fig 23 Base Unit Dimensional Drawing 48Z6 Z8075 105 Units with Return Exhaust Fan a48 8454...
Page 66: ...66 Fig 80 CCN Connections COMM BOARD MBB J5...
Page 67: ......