Table 17 — Fan Performance, 48TJD/TJE/TJF006 Horizontal Discharge Units;

Alternate Motor (Belt)

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.1

0.2

0.4

0.6

0.8

1.0

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

1500

730

357

789

420

896

557

990

704

1072

872

1153

1051

1600

770

420

826

483

931

641

1020

788

1101

956

1178

1145

1700

811

494

865

567

966

725

1051

883

1133

1061

1205

1240

1800

852

578

905

651

1002

820

1084

977

1163

1156

1235

1355

1900

894

567

945

757

1037

925

1119

1093

1194

1271

1266

1471

2000

936

778

984

862

1072

1030

1154

1219

1226

1397

1297

1608

2100

978

893

1024

977

1108

1156

1192

1355

1259

1545

1327

1744

2200

1021

1019

1064

1103

1145

1282

1225

1503

1294

1702

1359

1902

2300

1064

1156

1104

1240

1183

1429

1260

1650

1330

1870

1392

2070

2400

1107

1303

1145

1387

1222

1524

1296

1818

1365

2038

1426

2259

2500

1150

1460

1186

1555

1262

1765

1331

1986

1400

2227

1461

2459

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

1500

1221

1229

1256

1366

1283

1387

1303

1282

1600

1252

1334

1311

1524

1340

1660

1330

1692

1700

1278

1439

1345

1650

1397

1849

1424

1986

1800

1303

1555

1371

1776

1433

1996

1480

2196

1900

1330

1671

1396

1902

1460

2133

1517

2364

2000

1362

1818

1422

2038

1485

2270

1544

2522

2100

1393

1965

1452

2185

1510

2427

1570

2674

2200

1423

2122

1483

2354

1538

2585

1594

2821

2300

1454

2291

1515

2532

1571

2758

1623

2976

2400

1485

2480

1544

2721

1604

2947

1657

3152

2500

1518

2679

1574

2905

1633

3134

1692

3345

NOTES:
1. Boldface indicates a field-supplied drive is required. (See

Note 6.)

2.

indicates field-supplied motor and drive are required.

3. Maximum usable watts input is 1921. Extensive motor and elec-

trical testing on these units ensures that the full range of the motor
can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. For ad-
ditional information on motor performance, refer to Table 4.

4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact

Carrier representative to verify.

6. Alternate motor drive range: 900 to 1300. All other rpms require

field-supplied drive.

7. To convert watts to bhp:

watts input x motor efficiency

bhp =

746

Motor efficiency = .74

Table 18 — Fan Performance, 48TJD/TJE/TJF007 Horizontal Discharge Units;

Standard Motor (Belt)

AIRFLOW

(Cfm)

EXTERNAL STATIC PRESSURE (in. wg)

0.1

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts

1800

885

623

942

700

1047

835

1139

956

1193

1031

1276

1165

1341

1250

1413

1378

1474

1404

1900

928

700

982

779

1084

932

1160

1006

1223

1114

1301

1233

1374

1361

1437

1439

1490

1482

2000

971

787

1022

867

1121

1014

1188

1097

1254

1216

1329

1284

1396

1473

1460

1491

1509

1569

2100

1015

891

1063

998

1140

1064

1196

1140

1272

1292

1354

1404

1413

1552

1475

1534

1529

1700

2200

1060

998

1104

1081

1159

1106

1229

1258

1306

1361

1363

1508

1434

1604

1487

1639

1554

1831

2300

1104

1123

1130

1140

1196

1224

1264

1387

1340

1473

1397

1648

1459

1665

1520

1831

1576

1980

2400

1138

1165

1174

1224

1245

1396

1305

1447

1373

1630

1440

1726

1502

1823

1552

1980

1604

2136

2500

1183

1275

1201

1335

1284

1465

1338

1552

1402

1761

1469

1805

1524

1980

1585

2136

1638

2292

2600

1210

1404

1246

1482

1312

1560

1366

1735

1435

1858

1494

1936

1552

2119

1616

2317

1671

2462

2700

1254

1560

1285

1595

1354

1726

1403

1892

1474

1954

1536

2171

1584

2300

1646

2487

1706

2653

2800

1274

1613

1304

1639

1374

1875

1459

1989

1514

2136

1570

2343

1624

2504

1677

2661

2900

1318

1726

1345

1814

1412

2050

1496

2240

1529

2300

1603

2521

1671

2725

3000

1362

1945

1378

2032

1451

2119

1534

2343

1560

2470

1611

2648

1690

2886

NOTES:
1. Boldface indicates a field-supplied drive is required. (See

Note 6.)

2.

indicates field-supplied motor and drive are required.

3. Maximum usable watts input is 2120. Extensive motor and elec-

trical testing on these units ensures that the full range of the motor
can be utilized with confidence. Using your fan motors up to the
wattage ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected. For ad-
ditional information on motor performance, refer to Table 4.

4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact

Carrier representative to verify.

6. Standard motor drive range: 1070 to 1460. All other rpms require

field-supplied drive.

7. To convert watts to bhp:

watts input x motor efficiency

bhp =

746

Motor efficiency = .84

26

Summary of Contents for 48TJD Series

Page 1: ...o pres sure greater than 1 2 psig it must be re placed before use When pressure testing field supplied gas piping at pressures of 1 2 psig or less a unit connected to such piping must be isolated by m...

Page 2: ...e of 50 F dry bulb or an intermittent opera tion down to 45 F dry bulb such as when used with a night set back thermostat Step 3 Install External Trap for Condensate Drain The unit s 3 4 in condensate...

Page 3: ...u the Bottom ROOF CURB ACCESSORY A UNIT SIZE 48TJ CRRFCURB001A00 18 29 356 004 007 CRRFCURB002A00 28 09 610 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in...

Page 4: ...e in accordance with the CAN1 B149 1 and CAN1 B149 2 installation codes for gas burning appliances For natural gas applications gas pressure at unit gas con nection must not be less than 4 in wg or gr...

Page 5: ...in the legend for Table 2 Note 2 to determine the percent of voltage imbalance Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical com...

Page 6: ...ging to prevent rigging straps from damaging unit UNIT MAX WEIGHT A B C Lb Kg in mm in mm in mm 48TJE TJF004 510 231 73 69 1872 37 50 953 33 35 847 48TJD TJE TJF005 520 236 48TJD TJE TJF006 540 245 48...

Page 7: ...600 2000 2400 Alt 1200 1600 2000 Maximum Continuous Bhp Std 34 75 1 20 2 40 Alt 1 00 1 00 1 80 Motor Frame Size Std 48 48 48 56 Alt 48 48 56 Nominal Rpm High Low Std 860 800 1075 970 1075 970 Alt Fan...

Page 8: ...80 25 55 35 65 50 80 25 55 35 65 50 80 Manifold Pressure in wg Natural Gas 3 5 3 5 3 5 3 5 Liquid Propane 3 5 3 5 3 5 3 5 Gas Valve Quantity 1 1 1 1 Field Gas Connection Size in 1 2 1 2 1 2 1 2 HIGH...

Page 9: ...jurisdiction may prevail a Between unit flue side and combustible surfaces 36 inches b Bottom of unit to combustible surfaces when not using curb 1 inch Bot tom of base rail to combustible surfaces wh...

Page 10: ...E Follow all local codes SPACING OF SUPPORTS STEEL PIPE X DIMENSIONS feet NOMINAL DIAMETER in 1 2 6 3 4 or 1 8 11 4 or larger 10 Fig 8 Gas Piping Guide With Accessory Thru the Curb Service Connections...

Page 11: ...A Adjustable Heat Anticipator TH Thermostat Heating CC Cooling Compensator Field Wiring TC Thermostat Cooling Factory Wiring NOTES 1 Connect Y2 when unit is equipped with an economizer 2 Connect W2 wh...

Page 12: ...6 20 15 94 575 3 60 Std 518 632 7 9 58 0 0 6 2 6 30 14 4 15 12 76 IMPORTANT Optional alternate evaporator fan motor and drive are not available for 48TJ007 units Contact your local Carrier representat...

Page 13: ...he 4 screws removed in Step 3 See Fig 15 6 Remove and save 6 screws 3 on each side from sides of the manual outdoor air damper 7 Align screw holes on hood with screw holes on side of manual outdoor ai...

Page 14: ...g hood assembly See Fig 20 5 Insert economizer plug into economizer harness Re move tape from barometric relief damper See Fig 21 6 If ventilation air is not required proceed to Step 8 If ventilation...

Page 15: ...fm Determine Setting 5 in Fig 22 Varislide Economizer Minimum Position Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 6...

Page 16: ...ired perform the following a Make sure the factory installed jumper is in place across terminals P and P1 on the economizer logic module T and T1 should be disconnected during adjustment b The 2 poten...

Page 17: ...y en gaged See Fig 28 8 Fasten hood top and side plate assembly Fig 29 to outdoor air opening panel with screws provided 9 Slide outdoor air inlet screen into screen track on hood side plate While hol...

Page 18: ...n speed make sure the new fan speed will provide an air temperature rise range as shown in Table 1 To change fan speed 1 Shut off unit power supply 2 Loosen belt by loosening fan motor mounting nuts S...

Page 19: ...10 1070 Approximate fan rpm shown Indicates alternate motor and drive package Indicates standard motor and drive package Table 4 Motor Data UNIT 48TJ EVAPORATOR FAN MOTOR MAXIMUM CONTINUOUS BHP MAXIMU...

Page 20: ...487 1100 687 219 746 259 806 298 867 348 929 398 964 398 1013 487 1068 547 1200 733 259 785 318 843 348 903 408 960 467 994 497 1045 557 1090 637 1300 754 288 826 378 891 428 942 477 991 527 1047 597...

Page 21: ...1072 950 1107 998 1700 791 515 873 599 907 678 941 757 1024 889 1064 976 1103 1063 1137 1128 1800 831 609 881 693 929 772 976 851 1057 991 1095 1078 1132 1165 1167 1239 1900 872 704 919 788 965 877 1...

Page 22: ...70 869 1144 1032 1226 1216 1301 1492 1380 1757 1600 770 429 826 501 930 654 1015 797 1098 961 1173 1134 1242 1308 1318 1523 1392 1800 1700 811 511 864 582 964 736 1051 899 1124 1053 1203 1237 1270 142...

Page 23: ...or and drive are required 3 Maximum usable watts input is 2120 Extensive motor and elec trical testing on these units ensures that the full range of the motor can be utilized with confidence Using you...

Page 24: ...your fan motors up to the wattage ratings shown will not result in nuisance tripping or pre mature motor failure Unit warranty will not be affected For ad ditional information on motor performance re...

Page 25: ...d elec trical testing on these units ensures that the full range of the motor can be utilized with confidence Using your fan motors up to the wattage ratings shown will not result in nuisance tripping...

Page 26: ...ll other rpms require field supplied drive 7 To convert watts to bhp watts input x motor efficiency bhp 746 Motor efficiency 74 Table 18 Fan Performance 48TJD TJE TJF007 Horizontal Discharge Units Sta...

Page 27: ...Natural Gas Orifice Size Liquid Propane Orifice Size Natural Gas Orifice Size Liquid Propane Orifice Size 0 2 000 33 45 30 38 2 000 34 46 30 39 3 000 35 47 31 40 4 000 36 47 32 41 5 000 36 47 33 42 6...

Page 28: ...thermostat calls for cooling the economizer damper moves to the minimum position If the supply air tempera ture is above 57 F the damper continue to open until it reaches the fully open position or u...

Page 29: ...top cover as shown in Fig 36 and 37 It is not necessary to remove the top cover 2 Remove 3 screws on right side of compressor access panel Remove one screw securing condenser coil top cover to compres...

Page 30: ...harging charts are different from type normally used Charts are based on charg ing the units to the correct superheat for the various oper ating conditions Accurate pressure gage and temperature sensi...

Page 31: ...Fig 40 Cooling Charging Chart 48TJ004 Fig 41 Cooling Charging Chart 48TJ005 Fig 42 Cooling Charging Chart 48TJ006 Fig 43 Cooling Charging Chart 48TJ007 31...

Page 32: ...aporator Fan On Off Delay Modified 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced Draft Motor F...

Page 33: ...Fig 45 Burner Tray Details Fig 46 Spark Adjustment LOW HEAT 48TJE004 48TJD005 007 74 000 BTUH INPUT MEDIUM AND HIGH HEAT 48TJE005 007 48TJF004 115 000 BTUH INPUT 48TJF005 007 150 000 BTUH INPUT 33...

Page 34: ...trode spacing gaps etc Ensure that flame sense and ignition wires are prop erly terminated Verify that unit is obtaining proper amount of gas Induced draft motor fault LED 6 flashes IGC does not sense...

Page 35: ...pressure at manifold Clock gas meter for input If too low increase manifold pressure or replace with correct orifices Unit undersized for application Replace with proper unit or add additional unit Re...

Page 36: ...ace Restriction in refrigerant system Locate restriction and remove Compressor operates con tinuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Therm...

Page 37: ...l board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are function ing and wired properly and no 24 vac exists check wiring s...

Page 38: ...ed If these actions do not occur replace module 4 Disconnect 1 2 Kohm checkout resistor before resuming operation Damper does not close No power to economizer 1 Disconnect power at TR and TR1 Disconne...

Page 39: ...inal wire furnished must be replaced it must be replaced with type 90 C wire or its equivalent 2 Three phase motors are protected under primary single phasing conditions 3 Thermostat HH07AT170 172 174...

Page 40: ...Fig 47 Typical Wiring Diagram and Component Arrangement 40...

Page 41: ......

Page 42: ...turer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 1a 6a PC 111 Catalog No 534 852 Printed in U S A F...

Page 43: ......

Page 44: ...M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3 TEMPER...

Reviews: