Curb should be level. Unit leveling tolerances are shown

in Fig. 3. This is necessary for unit drain to function prop-
erly. Refer to Accessory Roof Curb Installation Instructions
for additional information as required.

SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 6 in. beyond unit
cabinet. Install a gravel apron in front of condenser coil air
inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if
required.

Step 2 — Field Fabricate Ductwork —

Secure all

ducts to roof curb and building structure on vertical units.
Do not connect ductwork to unit. For horizontal applica-
tions, field-supplied flanges should be attached to horizontal
discharge openings and all ductwork should be secured to
the flanges. Insulate and weatherproof all external duct-
work, joints, and roof openings with counter flashing and
mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be

insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return

should be ducted through the roof deck to comply with
applicable fire codes.

A minimum clearance is not required around ductwork.

Cabinet return air static shall not exceed

2

.20 in. wg with

PARABLADE, economizer

2

.35 in. wg with Varislide™

economizer or

2

.45 in. wg without economizer.

These units are designed for a minimum continuous return-

air temperature of 50 F (dry bulb), or an intermittent opera-
tion down to 45 F (dry bulb), such as when used with a night
set-back thermostat.

Step 3 — Install External Trap for Condensate
Drain —

The unit’s 3/4-in. condensate drain connections

are located at the bottom and side of the unit. Unit discharge
connections do not determine the use of drain connections;
either drain connection can be used with vertical or hori-
zontal applications.

When using the standard side drain connection, make sure

the plug in the alternate bottom connection is tight before
installing the unit.

To use the bottom drain connection for a roof curb in-

stallation, relocate the factory-installed plug from the bot-
tom connection to the side connection. See Fig. 4A. The piping
for the condensate drain and external trap can be completed
after the unit is in place.

All units must have an external trap for condensate drain-

age. Install a trap at least 4-in. deep and protect against freeze-
up. See Fig. 4B. If drain line is installed downstream from
the external trap, pitch the line away from the unit at 1 in.
per 10 ft of run. Do not use a pipe size smaller than the unit
connection.

Step 4 — Rig and Place Unit —

Inspect unit for trans-

portation damage. File any claim with transportation agency.
Keep unit upright and do not drop. Spreader bars
are not required if top crating is left on unit. Rollers may be
used to move unit across a roof. Level by using unit frame
as a reference. See Table 1 and Fig. 5 for additional
information.

Lifting holes are provided in base rails as shown in

Fig. 6. Refer to rigging instructions on unit.

All panels must be in place when rigging.

Fig. 1 — Horizontal Conversion Panels

2

Summary of Contents for 48TJD Series

Page 1: ...o pres sure greater than 1 2 psig it must be re placed before use When pressure testing field supplied gas piping at pressures of 1 2 psig or less a unit connected to such piping must be isolated by m...

Page 2: ...e of 50 F dry bulb or an intermittent opera tion down to 45 F dry bulb such as when used with a night set back thermostat Step 3 Install External Trap for Condensate Drain The unit s 3 4 in condensate...

Page 3: ...u the Bottom ROOF CURB ACCESSORY A UNIT SIZE 48TJ CRRFCURB001A00 18 29 356 004 007 CRRFCURB002A00 28 09 610 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in...

Page 4: ...e in accordance with the CAN1 B149 1 and CAN1 B149 2 installation codes for gas burning appliances For natural gas applications gas pressure at unit gas con nection must not be less than 4 in wg or gr...

Page 5: ...in the legend for Table 2 Note 2 to determine the percent of voltage imbalance Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical com...

Page 6: ...ging to prevent rigging straps from damaging unit UNIT MAX WEIGHT A B C Lb Kg in mm in mm in mm 48TJE TJF004 510 231 73 69 1872 37 50 953 33 35 847 48TJD TJE TJF005 520 236 48TJD TJE TJF006 540 245 48...

Page 7: ...600 2000 2400 Alt 1200 1600 2000 Maximum Continuous Bhp Std 34 75 1 20 2 40 Alt 1 00 1 00 1 80 Motor Frame Size Std 48 48 48 56 Alt 48 48 56 Nominal Rpm High Low Std 860 800 1075 970 1075 970 Alt Fan...

Page 8: ...80 25 55 35 65 50 80 25 55 35 65 50 80 Manifold Pressure in wg Natural Gas 3 5 3 5 3 5 3 5 Liquid Propane 3 5 3 5 3 5 3 5 Gas Valve Quantity 1 1 1 1 Field Gas Connection Size in 1 2 1 2 1 2 1 2 HIGH...

Page 9: ...jurisdiction may prevail a Between unit flue side and combustible surfaces 36 inches b Bottom of unit to combustible surfaces when not using curb 1 inch Bot tom of base rail to combustible surfaces wh...

Page 10: ...E Follow all local codes SPACING OF SUPPORTS STEEL PIPE X DIMENSIONS feet NOMINAL DIAMETER in 1 2 6 3 4 or 1 8 11 4 or larger 10 Fig 8 Gas Piping Guide With Accessory Thru the Curb Service Connections...

Page 11: ...A Adjustable Heat Anticipator TH Thermostat Heating CC Cooling Compensator Field Wiring TC Thermostat Cooling Factory Wiring NOTES 1 Connect Y2 when unit is equipped with an economizer 2 Connect W2 wh...

Page 12: ...6 20 15 94 575 3 60 Std 518 632 7 9 58 0 0 6 2 6 30 14 4 15 12 76 IMPORTANT Optional alternate evaporator fan motor and drive are not available for 48TJ007 units Contact your local Carrier representat...

Page 13: ...he 4 screws removed in Step 3 See Fig 15 6 Remove and save 6 screws 3 on each side from sides of the manual outdoor air damper 7 Align screw holes on hood with screw holes on side of manual outdoor ai...

Page 14: ...g hood assembly See Fig 20 5 Insert economizer plug into economizer harness Re move tape from barometric relief damper See Fig 21 6 If ventilation air is not required proceed to Step 8 If ventilation...

Page 15: ...fm Determine Setting 5 in Fig 22 Varislide Economizer Minimum Position Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 6...

Page 16: ...ired perform the following a Make sure the factory installed jumper is in place across terminals P and P1 on the economizer logic module T and T1 should be disconnected during adjustment b The 2 poten...

Page 17: ...y en gaged See Fig 28 8 Fasten hood top and side plate assembly Fig 29 to outdoor air opening panel with screws provided 9 Slide outdoor air inlet screen into screen track on hood side plate While hol...

Page 18: ...n speed make sure the new fan speed will provide an air temperature rise range as shown in Table 1 To change fan speed 1 Shut off unit power supply 2 Loosen belt by loosening fan motor mounting nuts S...

Page 19: ...10 1070 Approximate fan rpm shown Indicates alternate motor and drive package Indicates standard motor and drive package Table 4 Motor Data UNIT 48TJ EVAPORATOR FAN MOTOR MAXIMUM CONTINUOUS BHP MAXIMU...

Page 20: ...487 1100 687 219 746 259 806 298 867 348 929 398 964 398 1013 487 1068 547 1200 733 259 785 318 843 348 903 408 960 467 994 497 1045 557 1090 637 1300 754 288 826 378 891 428 942 477 991 527 1047 597...

Page 21: ...1072 950 1107 998 1700 791 515 873 599 907 678 941 757 1024 889 1064 976 1103 1063 1137 1128 1800 831 609 881 693 929 772 976 851 1057 991 1095 1078 1132 1165 1167 1239 1900 872 704 919 788 965 877 1...

Page 22: ...70 869 1144 1032 1226 1216 1301 1492 1380 1757 1600 770 429 826 501 930 654 1015 797 1098 961 1173 1134 1242 1308 1318 1523 1392 1800 1700 811 511 864 582 964 736 1051 899 1124 1053 1203 1237 1270 142...

Page 23: ...or and drive are required 3 Maximum usable watts input is 2120 Extensive motor and elec trical testing on these units ensures that the full range of the motor can be utilized with confidence Using you...

Page 24: ...your fan motors up to the wattage ratings shown will not result in nuisance tripping or pre mature motor failure Unit warranty will not be affected For ad ditional information on motor performance re...

Page 25: ...d elec trical testing on these units ensures that the full range of the motor can be utilized with confidence Using your fan motors up to the wattage ratings shown will not result in nuisance tripping...

Page 26: ...ll other rpms require field supplied drive 7 To convert watts to bhp watts input x motor efficiency bhp 746 Motor efficiency 74 Table 18 Fan Performance 48TJD TJE TJF007 Horizontal Discharge Units Sta...

Page 27: ...Natural Gas Orifice Size Liquid Propane Orifice Size Natural Gas Orifice Size Liquid Propane Orifice Size 0 2 000 33 45 30 38 2 000 34 46 30 39 3 000 35 47 31 40 4 000 36 47 32 41 5 000 36 47 33 42 6...

Page 28: ...thermostat calls for cooling the economizer damper moves to the minimum position If the supply air tempera ture is above 57 F the damper continue to open until it reaches the fully open position or u...

Page 29: ...top cover as shown in Fig 36 and 37 It is not necessary to remove the top cover 2 Remove 3 screws on right side of compressor access panel Remove one screw securing condenser coil top cover to compres...

Page 30: ...harging charts are different from type normally used Charts are based on charg ing the units to the correct superheat for the various oper ating conditions Accurate pressure gage and temperature sensi...

Page 31: ...Fig 40 Cooling Charging Chart 48TJ004 Fig 41 Cooling Charging Chart 48TJ005 Fig 42 Cooling Charging Chart 48TJ006 Fig 43 Cooling Charging Chart 48TJ007 31...

Page 32: ...aporator Fan On Off Delay Modified 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced Draft Motor F...

Page 33: ...Fig 45 Burner Tray Details Fig 46 Spark Adjustment LOW HEAT 48TJE004 48TJD005 007 74 000 BTUH INPUT MEDIUM AND HIGH HEAT 48TJE005 007 48TJF004 115 000 BTUH INPUT 48TJF005 007 150 000 BTUH INPUT 33...

Page 34: ...trode spacing gaps etc Ensure that flame sense and ignition wires are prop erly terminated Verify that unit is obtaining proper amount of gas Induced draft motor fault LED 6 flashes IGC does not sense...

Page 35: ...pressure at manifold Clock gas meter for input If too low increase manifold pressure or replace with correct orifices Unit undersized for application Replace with proper unit or add additional unit Re...

Page 36: ...ace Restriction in refrigerant system Locate restriction and remove Compressor operates con tinuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Therm...

Page 37: ...l board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are function ing and wired properly and no 24 vac exists check wiring s...

Page 38: ...ed If these actions do not occur replace module 4 Disconnect 1 2 Kohm checkout resistor before resuming operation Damper does not close No power to economizer 1 Disconnect power at TR and TR1 Disconne...

Page 39: ...inal wire furnished must be replaced it must be replaced with type 90 C wire or its equivalent 2 Three phase motors are protected under primary single phasing conditions 3 Thermostat HH07AT170 172 174...

Page 40: ...Fig 47 Typical Wiring Diagram and Component Arrangement 40...

Page 41: ......

Page 42: ...turer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 1a 6a PC 111 Catalog No 534 852 Printed in U S A F...

Page 43: ......

Page 44: ...M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3 TEMPER...

Reviews: