* As the height above sea level increases, there is less oxygen per
cubic ft. of air. Therefore, heat input rate should be reduced at higher
altitudes.
XX
1
= CRNGELEV001A00
XX
2
= CRNGELEV002A00
XX
3
= CRLPELEV006A00
XX
4
= CRLPELEV006A00
XX
5
= CRLPKIT9001A00
Table 16 — Altitude Compensation* (17 - 30) – Natural Gas
NATURAL GAS
NOMINAL HEAT INPUT
ELEVATION
220k BTUH
310k BTUH
400k BTUH
Feet
Meters
Orifice Size
Input
(btu/hr)
Orifice Size
Input
(btu/hr)
Orifice Size
Input
(btu/hr)
0 - 2000
0-610
30
220,000
30
310,000
30
400,000
2,000
610
30
202,400
30
285,200
30
368,000
3,000
914
31
1
193,600
31
1
272,800
31
1
352,000
4,000
1219
31
1
184,800
31
1
260,400
31
1
336,000
5,000
1524
31
1
176,000
31
1
248,000
31
1
320,000
6,000
1829
31
1
167,200
31
1
235,600
31
1
304,000
7,000
2134
32
1
158,400
32
1
223,200
32
1
288,000
8,000
2438
32
1
149,600
32
1
210,800
32
1
272,000
9,000
2743
34
1
140,800
34
1
198,400
34
1
256,000
10,000
3048
35
2
132,000
35
1
186,000
35
1
240,000
11,000
3353
37
2
123,200
37
2
173,600
37
2
224,000
12,000
3658
37
2
114,400
37
2
161,200
37
2
208,000
13,000
3962
39
2
105,600
39
2
148,800
39
2
192,000
14,000
4267
39
2
96,800
39
2
136,400
39
2
176,000
Table 17 — Altitude Compensation* (17 - 30) – Propane Gas
Propane GAS
NOMINAL HEAT INPUT
ELEVATION
220k BTUH
310k BTUH
400k BTUH
Feet
Meters
Orifice Size
Input
(btu/hr)
Orifice Size
Input
(btu/hr)
Orifice Size
Input
(btu/hr)
0 - 2000
0-610
48
5
220,000
48
5
310,000
48
5
400,000
2,000
610
49
3
202,400
49
3
285,200
49
3
368,000
3,000
914
49
3
193,600
49
3
272,800
49
3
352,000
4,000
1219
49
3
184,800
49
3
260,400
49
3
336,000
5,000
1524
50
3
176,000
50
3
248,000
50
3
320,000
6,000
1829
50
3
167,200
50
3
235,600
50
3
304,000
7,000
2134
50
3
158,400
50
3
223,200
50
3
288,000
8,000
2438
51
3
149,600
51
3
210,800
51
3
272,000
9,000
2743
51
3
140,800
51
3
198,400
51
3
256,000
10,000
3048
52
4
132,000
52
4
186,000
52
4
240,000
11,000
3353
52
4
123,200
52
4
173,600
52
4
224,000
12,000
3658
53
4
114,400
53
4
161,200
53
4
208,000
13,000
3962
53
4
105,600
53
4
148,800
53
4
192,000
14,000
4267
53
4
96,800
53
4
136,400
53
4
176,000
Summary of Contents for 48TC series
Page 40: ...40 Fig 56 Typical IGC Wiring Diagram...
Page 41: ...41 Fig 57 Integrated Gas Control IGC Board RED LED STATUS...
Page 47: ...47 Fig 62 RTU Open Overlay for Economizer Wiring...
Page 48: ...48 Fig 63 VFD Overlay for W2770 Controller Wiring...
Page 97: ...97 Fig D 48TC D17 D30 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS...
Page 98: ...98 Fig E 48TC D17 D30 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS...
Page 99: ...99 Fig F 48TC D17 D30 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS...
Page 100: ...100 Fig G 48TC D17 D30 Control Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Page 104: ...104 Fig K PremierLink System Control Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Page 106: ...106 Fig M RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Page 107: ...107 Fig N RTU OPEN Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Page 109: ......