
31
Resetting Alarm and Trouble Condition Trips
Manual reset is required to restore smoke detector systems to Nor
-
mal operation. For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an alarm or
trouble condition. Check each sensor for Alarm or Trouble status.
Clear the condition that has generated the trip at this sensor. Then
reset the sensor by pressing and holding the reset button (on the
side) for 2 seconds. Verify that the sensor’s Alarm and Trouble
LEDs are now off. At the controller, clear its Alarm or Trouble
state by pressing and holding the manual reset button (on the front
cover) for 2 seconds. Verify that the controller’s Alarm and Trou
-
ble LEDs are now off. Replace all panels.
Troubleshooting
CONTROLLER’S TROUBLE LED IS ON
1. Check the Trouble LED on each sensor connected to the con
-
troller. If a sensor’s Trouble LED is on, determine the cause
and make the necessary repairs.
2. Check the wiring between the sensor and the controller. If
wiring is loose or missing, repair or replace as required.
CONTROLLER’S TROUBLE LED IS FLASHING
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean that sensor
assembly as described in the detector cleaning section.
SENSOR’S TROUBLE LED IS ON
1. Check the sensor’s Dirty LED. If it is flashing, the sensor is
dirty and must be cleaned.
2. Check the sensor’s cover. If it is loose or missing, secure the
cover to the sensor housing.
3. Replace sensor assembly.
SENSOR’S POWER LED IS OFF
1. Check the controller’s Power LED. If it is off, determine why
the controller does not have power and make the necessary
repairs.
2. Check the wiring between the sensor and the controller. If
wiring is loose or missing, repair or replace as required.
CONTROLLER’S POWER LED IS OFF
1. Make sure the circuit supplying power to the controller is
operational. If not, make sure JP2 and JP3 are set correctly on
the controller before applying power.
2. Verify that power is applied to the controller’s supply input
terminals. If power is not present, replace or repair wiring as
required.
REMOTE TEST/RESET STATION’S TROUBLE LED DOES
NOT FLASH WHEN PERFORMING A DIRTY TEST, BUT
THE CONTROLLER’S TROUBLE LED DOES
1. Verify that the remote test/station is wired as shown in
Fig. 41. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the controller’s
supervision relay. See “Changing Sensor Dirty Test
Operation.”
SENSOR’S TROUBLE LED IS ON, BUT THE CONTROL
-
LER’S TROUBLE LED IS OFF
Remove JP1 on the controller.
PROTECTIVE DEVICES
Compressor Protection
OVERCURRENT
The compressor has internal linebreak motor protection. Reset is
automatic after compressor motor has cooled.
OVERTEMPERATURE
Each compressor has an internal protector to protect it against ex
-
cessively high discharge gas temperatures. Reset is automatic.
HIGH PRESSURE SWITCH
The system is provided with a high pressure switch mounted on
the discharge line. The switch is stem-mounted and brazed into the
discharge tube. Trip setting is 630 psig ± 10 psig (4344 ± 69 kPa)
when hot. Reset is automatic at 505 psig (3482 kPa).
LOW PRESSURE SWITCH
The system is protected against a loss of charge and low evapora
-
tor coil loading condition by a low pressure switch located on the
suction line near the compressor. The switch is stem-mounted.
Trip setting is 54 psig ± 5 psig (372 ± 34 kPa). Reset is automatic
at 117 ± 5 psig (807 ± 34 kPa).
SUPPLY (INDOOR) FAN MOTOR PROTECTION
Motors with 2.9 and 3.7 bhp are equipped with an internal over
-
temperature or protection device. The type of device depends on
the motor size. See Table 8.
The high static option supply fan motor is equipped with a pilot-
circuit Thermix combination overtemperature/overcurrent protec
-
tion device. This device resets automatically. Do not bypass this
switch to correct trouble. Determine the cause and correct it.
The Thermik device is a snap-action overtemperature protection
device that is embedded in the motor windings. The Thermik can
be identified by two blue wires extending out of the motor control
box. It is a pilot-circuit device that is wired into the unit’s 24-v
control circuit. When this switch reaches its trip setpoint, it opens
the 24-v control circuit and causes all unit operation to cease. This
device resets automatically when the motor windings cool. Do not
bypass this switch to correct trouble. Determine the cause and cor
-
rect it.
The external overload breaker is an overcurrent device used on
motors with a horsepower rating of 4.7 hp or greater. This is a spe
-
cially-calibrated circuit breaker that is UL recognized as a motor
overload controller. When the current to the motor exceeds the cir
-
cuit breaker setpoint, the device opens all motor power leads to the
motor, shutting the motor down. Reset requires a manual reset at
the overload switch. This device (designated IFCB) is located on
the side of the supply fan housing, behind the fan access panel.
The must hold and must trip values are listed on the side of the ex
-
ternal overload breaker.
CAUTION
PERSONAL INJURY HAZARD
Failure to follow this caution can result in personal injury.
Disconnect all electrical power when servicing the fan motor.
Apply appropriate lockout/tag-out procedures.
Table 8 —
Overcurrent Device Type
MOTOR SIZE (bhp)
OVERLOAD DEVICE
RESET
1.7
Internal Linebreak
Automatic
2.4
Internal Linebreak
Automatic
2.9
Thermik
Automatic
3.7
Thermik
Automatic
4.7
External (circuit breaker)
Manual
Summary of Contents for 48TC series
Page 40: ...40 Fig 56 Typical IGC Wiring Diagram...
Page 41: ...41 Fig 57 Integrated Gas Control IGC Board RED LED STATUS...
Page 47: ...47 Fig 62 RTU Open Overlay for Economizer Wiring...
Page 48: ...48 Fig 63 VFD Overlay for W2770 Controller Wiring...
Page 97: ...97 Fig D 48TC D17 D30 Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS...
Page 98: ...98 Fig E 48TC D17 D30 Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS...
Page 99: ...99 Fig F 48TC D17 D30 Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS...
Page 100: ...100 Fig G 48TC D17 D30 Control Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Page 104: ...104 Fig K PremierLink System Control Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Page 106: ...106 Fig M RTU OPEN Wiring Diagram APPENDIX D WIRING DIAGRAMS...
Page 107: ...107 Fig N RTU OPEN Wiring Diagram with Humidi MiZer System APPENDIX D WIRING DIAGRAMS...
Page 109: ......