background image

Electrical Controls and Wiring —

Electrical con-

trols are difficult to check without proper instrumentation;
therefore, if there are any discrepancies in the operating cycle,
contact your dealer and request service.

Refrigerant Circuit —

The refrigerant circuit is diffi-

cult to check for leaks without the proper equipment; there-
fore, if inadequate cooling is suspected, contact your local
dealer for service.

Combustion Area and Vent System —

The com-

bustion area and vent system should be inspected visually
before each heating season. The normal accumulation of dirt,
soot, rust, and scale can result in loss of efficiency and im-
proper performance if allowed to build up.

If your unit makes an especially loud noise when the
main burners are ignited, shut down the heating section
and call your dealer.

Proceed as follows to inspect the combustion area and power-

venting system of your unit.
1. Turn off electrical power and gas supply to your unit.
2. Remove burner access panel. (See Fig. 1.)
3. Using a flashlight, carefully inspect the burner areas for

dirt, soot, rust, or scale. See Fig. 2.

If dirt, soot, rust, or scale accumulations are found,
call your dealer and do not operate your heating sec-
tion.

4. When you have completed your inspection, follow the

start-up procedures in this manual to restore your unit to
operation.

5. Observe unit heating operation.

Components in heat section may be hot after unit
has been started up. When observing flame, be care-
ful not to get close to or touch heating components
or serious personal injury may result.

Watch the burner flame to see if it is bright blue. If you
observe a suspected malfunction or if the burner flames
are not bright blue, call your dealer.

6. Replace burner access panel.

Unit Panels —

After performing any maintenance or serv-

ice on the unit, be sure all panels are fastened securely in
place to prevent rain from entering unit cabinet and to pre-
vent disruption of the correct unit airflow pattern.

REGULAR DEALER MAINTENANCE

In addition to the type of routine maintenance you might

be willing to perform, your unit should be inspected regu-
larly by a properly trained service technician. An inspection
(preferably each year, but at least every other year) should
include the following:

1. Inspection of all flue product passages — including the

burners, heat exchanger, and flue collector box.

2. Inspection of all combustion- and ventilation-air pas-

sages and openings.

3. Close inspection of all gas pipes leading to and inside of

your unit.

4. Inspection and, if required, cleaning of the condenser

and evaporator coils.

5. Inspection and, if required, cleaning of the evaporator

drain pan.

6. Inspection and cleaning of blower wheel housing and

motor.

7. Inspection of all supply-air and return-air ducts for leaks,

obstructions and insulation integrity. Any problems found
should be resolved at this time.

8. Inspection of the unit base to ensure that no cracks, gaps,

etc., exist which may cause a hazardous condition.

9. Inspection of the unit casing for signs of deterioration.

10. Inspection of all electrical wiring and components to as-

sure proper connection.

11. Inspection for leaks in the refrigerant circuit. Pressure-

check to determine appropriate refrigerant charge.

12. Inspection of compressor oil level.
13. Operational check of the unit to determine working con-

ditions. Repair or adjustment should be made at this time.

Your servicing dealer may offer an economical service con-

tract that covers seasonal inspections. Ask for further
details.

Complete service instructions can be found in the unit

Installation, Start-Up and Service Instructions.

WARRANTIES

Units 48SS and 48SX each have a separate warranty lo-

cated at the back of this book. Be sure to read the warranty
carefully to determine the coverage for your unit.

Fig. 5 — Filter Access Panel — Vertical Supply Shown

FILTER ACCESS PANEL

7

Summary of Contents for 48SS

Page 1: ...y appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire department Before performing recommended maintenance be sure gas supply and main power switch to unit are turned off Electrical shock could cause personal injury Mo...

Page 2: ...Set the temperature selector on room ther mostat to desired setting 1 If the main burners fail to light or the blower fails to start shut down gas heating section and call your dealer for service 2 Never attempt to manually light the main burners on unit with a match lighter or any other flame If the electric sparking device fails to light the main burn ers refer to the following shutdown procedur...

Page 3: ...cked at least ev ery 3 or 4 weeks and changed or cleaned whenever it be comes dirty Dirty filters produce excessive stress on the blower motor and can cause the motor to overheat and shut down Table 1 indicates the correct filter size for your unit Refer to Fig 5 to access the filter s To replace or inspect filter s or accessory filter rack when supplied 1 Remove the filter access panel using a 5 ...

Page 4: ...of condenser or evaporator fan bearings or motors is required or recommended Evaporator and Condenser Coils Cleaning of the coils should only be done by qualified service per sonnel Contact your dealer for the required annual maintenance Condensate Drain The drain pan and condensate drain line should be checked and cleaned at the same time the cooling coils are checked by your dealer Compressor Al...

Page 5: ...STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 STEP 7 STEP 8 STEP 9 STEP 10 Fig 3 To Light Unit 5 ...

Page 6: ...STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 STEP 7 Fig 4 To Shut Unit Off 6 ...

Page 7: ...astened securely in place to prevent rain from entering unit cabinet and to pre vent disruption of the correct unit airflow pattern REGULAR DEALER MAINTENANCE In addition to the type of routine maintenance you might be willing to perform your unit should be inspected regu larly by a properly trained service technician An inspection preferably each year but at least every other year should include ...

Page 8: ...right angle indicating that the valve is closed If closed has the gas been shut off for safety reasons Otherwise you may open the valve and follow the start up procedures listed in this manual NOTE Before proceeding with the next check turn OFF the gas supply then the electrical power supply to the unit Remove the control access door During the heating season check the control switch on the intern...

Page 9: ...9 ...

Page 10: ......

Page 11: ...MODEL 48SS WARRANTY 11 ...

Page 12: ... Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 1a 6a PC 111 Catalog No 564 993 Printed in U S A Form 48SS SX 3SO Pg 12 5 98 Replaces 48SS SX 2SO ...

Reviews: