Table B — Physical Data (Heating) 12.5 TO 23 Tons
48LC*14
48LC*17
48LC*20
48LC*24
48LC*26
GAS CONNECTION
# of gas valves
1
1
1
1
1
Natural gas supply line pressure (in. wg) / (psig)
4-13 / 0.18 - 0.47 4-13 / 0.18 - 0.47 4-13 / 0.18 - 0.47 4-13 / 0.18 - 0.47 4-13 / 0.18 - 0.47
Liquid propane supply line pressure (in. wg) / (psig)
11-13 / 0.40-0.47 11-13 / 0.40-0.47 11-13 / 0.40-0.47 11-13 / 0.40-0.47 11-13 / 0.40-0.47
HEAT ANTICIPATOR SETTING (AMPS)
First stage
0.14
0.14
0.14
0.14
0.14
Second stage
0.14
0.14
0.14
0.14
0.14
NATURAL GAS HEAT
LOW
# of stages / # of burners (total)
1 or 2 / 4
1 or 2 / 5
1 or 2 / 5
1 or 2 / 5
1 or 2 / 5
Connection size
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
Rollout switch opens / closes (°F)
195 / 115
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise (°F)
20 - 50
20 - 55
20 - 55
20 - 55
20 - 55
MED
# of stages / # of burners (total)
1 or 2 / 5
1 or 2 / 7
1 or 2 / 7
1 or 2 / 7
1 or 2 / 7
Connection size
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
Rollout switch opens / closes (°F)
195 / 115
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise (°F)
20 - 55
30 - 60
30 - 60
30 - 60
30 - 60
HIGH
# of stages / # of burners (total)
1 or 2 / 7
1 or 2 / 9
1 or 2 / 9
1 or 2 / 9
1 or 2 / 9
Connection size
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
Rollout switch opens / closes (°F)
195 / 115
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise (°F)
30 - 60
35 - 65
35 - 65
35 - 65
35 - 65
LIQUID PROPANE HEAT
LOW
# of stages / # of burners (total)
1 or 2 / 4
1 or 2 / 5
1 or 2 / 5
1 or 2 / 5
1 or 2 / 5
Connection size
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
Rollout switch opens / closes (°F)
195 / 115
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise (°F)
20 - 50
20 - 55
20 - 55
20 - 55
20 - 55
MED
# of stages / # of burners (total)
1 or 2 / 5
1 or 2 / 7
1 or 2 / 7
1 or 2 / 7
1 or 2 / 7
Connection size
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
Rollout switch opens / closes (°F)
195 / 115
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise (°F)
20 - 55
30 - 60
30 - 60
30 - 60
30 - 60
HIGH
# of stages / # of burners (total)
1 or 2 / 7
1 or 2 / 9
1 or 2 / 9
1 or 2 / 9
1 or 2 / 9
Connection size
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
3
/
4
-in. NPT
Rollout switch opens / closes (°F)
195 / 115
195 / 115
195 / 115
195 / 115
195 / 115
Temperature rise (°F)
30 - 60
35 - 65
35 - 65
35 - 65
35 - 65
APPENDIX B — PHYSICAL DATA