d. Press ▼ (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis
-
play appears:
e. Press ▼ (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis
-
play appears:
f. Press ▼(Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis
-
play appears:
g. Press ▼ (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis
-
play appears:
12. Setting Reset Mode and RFI Filter:
a. Press the Back key until the following display
appears:
b. Press ▼ (Down Arrow) until the following display
appears:
c. Press OK, the following display appears:
d. Press ▼ (Down Arrow) twice. The following display
appears:
e. Press OK, the following display appears:
f. Press OK to highlight the number in the bracket.
g. Use the ▲ and ▼ (Up and Down Arrow) keys to
change the number to 3 for 3 automatic resets and
then press OK. The display changes to:
h. Press ▼ (Down Arrow) once, the following display
appears:
i. Press OK to highlight the number of seconds and use
the ▲ and ▼ (Up and Down Arrow) keys to select
600 seconds. Press OK again to set the selected value.
j. Press the Back key once, the following display
appears:
k. Press ▼ (Down Arrow) twice, the following display
appears:
l. Press OK, the following display appears:
m. Press OK to highlight the number in the bracket and
use the ▲ and ▼ (Up and Down Arrow) keys to
select [0]. Press OK again to set the selected value.
13. To Complete Reprogramming:
a. Press the Auto On key before disconnecting the VFD
Remote Keypad from the variable frequency drive.
6-10 Terminal 53 Low Voltage
2V
6-11 Terminal 53 High Voltage
[10V]
6-14 Set Min Reference
[0 Hz]
6-15 Set Max Reference
[60 Hz]
0—** Operation / Display
1—** Load and Motor
13—** Smart Logic
14—** Special Functions
14—0* Inverter Switching
14—1* Mains On/Off
14—1* Mains On/Off
14—2* Reset Functions
14-20 Reset Mode
[0] Manual reset
14-20 Reset Mode
[3] Automatic reset x 3
14-21 Automatic Restart T…
10s
14—1* Mains On/Off
14—2* Reset Functions
14—4* Energy Optimising
14—5* Environment
14-50 RFI Filter
[1] On