![Carrier 48LC 14 Service And Maintenance Instructions Download Page 56](http://html1.mh-extra.com/html/carrier/48lc-14/48lc-14_service-and-maintenance-instructions_2561045056.webp)
56
d. Press ▼ (Down Arrow) until the following display
appears:
e. Press OK, the following display appears:
f. Press OK to highlight the number and then use the ▲
and ▼ (Up and Down Arrow) keys to select the num
-
ber provided in Tables 33-37. Press OK again to set
the selected value.
g. Press ▼ (Down Arrow) twice, the following display
appears:
h. Press OK to highlight the number in the bracket and
then use the ▲ and ▼ (Up and Down Arrow) keys to
select the number provided in Tables 33-37. Press OK
again to set the selected value.
i. Press the Back key once, the following display
appears:
j. Press ▼ (Down Arrow) once, the following display
appears:
k. Press OK, the following display appears:
l. Press ▼ (Down Arrow) once, the following display
appears:
m. Press OK to highlight the number and then use the ▲
and ▼ (Up and Down Arrow) keys to select the num
-
ber provided in Tables 33-37. Press OK again to set
the selected value.
n. Press the Back key once, the following display
appears:
o. Press ▼ (Down Arrow) once, the following display
appears:
p. Press OK, the following display appears:
q. Press OK to highlight the number in the bracket then
use the ▲ and ▼ (Up and Down Arrow) keys to
select the number provided in Tables 33-37. Press OK
again to set the selected value.
7. Setting References:
a. Press the Menu key to move the ▼ (triangle icon) so
it is positioned over Main Menu. The display shows
the following:
b. Press ▼ (Down Arrow) three times, the following
display appears:
c. Press OK, the following display appears:
d. Press OK again, the following display appears:
NOTE: If the bottom row displays a number other than 0.000,
press OK and use the ▲ and ▼ (Up and Down Arrow) key to
select 0.000.
e. Press ▼ (Down Arrow) once, the following display
appears:
NOTE: If the bottom row displays a number other than 60.000,
press OK and use the ▲ and ▼ (Up and Down Arrow) key to
select 60.000.
f. Press the Back key until the following display
appears:
g. Press ▼ (Down Arrow) once to move the highlight to
the bottom row and then press OK. The following dis
-
play appears:
h. Press OK once to highlight the number in the bracket.
Press OK again; the highlight moves to the current
percent value.
Use the ▲ and ▼ (Up and Down Arrow) keys and the
table below to enter the required Preset Reference
values.
1—6* Load Depen. Setting
1—7* Start Adjustments
1-71 Start Delay
2.0s
1-73 Flying Start
[1] Enabled
1—6* Load Depen. Setting
1—7* Start Adjustments
1—7* Start Adjustments
1—8* Stop Adjustments
1-80 Function at Stop
[0] Coast
1-82 Min Speed for Functio…
1.0 Hz
1—7* Start Adjustments
1—8* Stop Adjustments
1—8* Stop Adjustments
1—9* Motor Temperature
1-90 Motor Thermal Prote…
[4] ETR trip 1
0—** Operation / Display
1—** Load and Motor
2—** Brakes
3—** Reference / Ramps
3—0* Reference Limits
3—1* References
3-02 Minimum Reference
0.000
3-03 Maximum Reference
60.000
3—0* Reference Limits
3—1* References
3-10 Preset Reference
[0]0.00%
[0]0.00%
Stop
[1]LL.LL%
Low Speed (see Tables 33-37, column labeled “Preset
References 3—10[1]” for the proper % for each unit)
[2]MM.MM%
Medium Speed (see Tables 33-37, column labeled
“Preset References 3—10[2]” for the proper % for each
unit)
[3]100%
Override (High Speed)
[4]100%
High Speed (100% or close to 100% to achieve the
required CFM at high speed)
[5]0.00%
Stop
[6]0.00%
Stop
[7]0.00%
Stop