background image

29

The burners will ignite within 5 seconds. If the burners do

not light, there is a 22-second delay before another 5-second
attempt. If the burners still do not light, this sequence is repeat-
ed for 15 minutes. After the 15 minutes have elapsed, if the
burners still have not ignited, heating is locked out. The control
will reset when the request for heat is temporarily removed.

When ignition occurs, the IGC board will continue to moni-

tor the condition of the rollout switch, limit switches, Hall
Effect sensor, and the flame sensor. If the unit is controlled
through a room thermostat set for fan auto, 45 seconds after
ignition occurs the indoor-fan motor will be energized (and the
outdoor-air dampers will open to their minimum position). If
for some reason the overtemperature limit opens prior to the
start of the indoor fan blower, on the next attempt, the
45-second delay will be shortened to 5 seconds less than the
time from initiation of heat to when the limit tripped. Gas will
not be interrupted to the burners and heating will continue.
Once modified, the fan on delay will not change back to
45 seconds unless power is reset to the control.

When additional heat is required and the MBB senses that

W2 is On, the MBB closes the HTR.2 relay and sends power to
the second stage of the main gas valve. If the thermostat
removes the call for W2, the unit will turn off HTR.2 (mini-
mum on-time 2 minutes [MRT.H], minimum off-time 2 min-
utes [MOT.H]). If W1 is satisfied, the main base board will
open HTR.1 (minimum on-time 2 minutes and minimum
off-time 2 minutes), interrupting the flow of gas to the main
burners. The IGC also has a minimum on-time of 1 minute.
Therefore, in modes such as Service Test where the long mini-
mum on-time and off-times are not enforced, the one minute
minimum on-time for the IGC will still be followed. If the unit
is controlled through a room thermostat set for fan auto, the
indoor-fan motor will continue to operate for an additional
45 seconds then stop. If the overtemperature limit opens after
the indoor motor is stopped within 10 minutes of W becoming
inactive, on the next cycle the time will be extended by 15 sec-
onds. The maximum delay is 3 minutes. Once modified, the
fan off delay will not change back to 45 seconds unless power
is reset to the control.

An LED indicator is provided on the IGC to monitor opera-

tion. The IGC is located by removing the heat section side
panel. See Fig. 4. During normal operation, the LED is contin-
uously on. See Table 26 for error codes.

If the user has selected Adaptive (see Cooling section) for

its thermostat mode, the algorithm will follow the configurable
delays for adding and removing stages. When adding addition-
al heat stages, the delay is measured from when the last stage
was added (H.INC). When removing stages, the delay is mea-
sured from when the last stage was removed (H.DEC). There-
fore, if W1 and W2 turn on simultaneously, the second stage
will turn on after a H.INC delay.
NOTE: If the mode is not Adaptive, then there are no delays
for adding and removing stages.
SPACE SENSOR CONTROL — During  Space  Sensor  con-
trol, the electronic control uses information from the space sen-
sor to determine the number of heat stages. Once the number of
stages needed for heating is determined, this information is
passed to the IGC by turning on either HTR.1 or HTR.1 and
HTR.2. See Thermostat Control section for description of IGC
operation.
NOTE: The jumper wire in the installer’s packer must be con-
nected between R and W1 when using a T55, T56, or T58
device. See Fig. 1 and 2.

During Space Sensor control, two methods are used to add

stages of heat and two methods are used to subtract stages of
heat. The first method of adding and subtracting stages causes
the unit to operate around its configured steady state number of
stages. For example, if the correct number of stages is between
0 and 1, this method will cause the first stage to cycle. If the

correct number of stages is between 1 and 2, this method will
cause the second stage to cycle.

The second method of adding and subtracting stages causes

the unit to find the steady state number of stages. The first
method will not add or remove a stage of heating unless the
current Heat Demand (set point – SPT), corrected by the rate of
change in the Heat Demand, is greater than Heat Demand
Positive Level (HT.PD) or less than Heat Demand Negative
Level (HT.ND). The correction term is the Heat Thermal Lag
(H.LAG) multiplied by the change in the Heat Demand. There-
fore, if the corrected current demand is in between –1.0 and
1.0, the number of stages will not change no matter how long
there has been a positive error. Because the corrected heat
demand incorporates the rate of change in heat demand, it will
have a tendency to add or remove stages earlier when the
temperature in the space is moving very rapidly, thereby
reducing overshoot.

Because the first method of adding or removing a stage of

heat is used to operate around the steady number of stages, this
method can not be used to add an additional stage until a stage
has been subtracted. Likewise, if this method has subtracted a
stage, it can not be used again to subtract another stage until a
stage has been added.

The second method will add additional stages of heat when-

ever Heat Demand is greater than HT.PD + 0.5 and the heat de-
mand is increasing at rate greater than 0.3 F per min. Addition-
al stages of heat will be removed whenever the Heat Demand is
less than HT.ND – 0.5 and the heat demand is decreasing at
rate less than 0.3 F per min.

Table 26 — IGC LED Indications

LEGEND

NOTES:
1. There is a 3-second pause between error code displays.
2. If more than one error code exists, all applicable error codes will

be displayed in numerical sequence.

3. Error codes on the IGC will be lost if power to the unit is

interrupted.

Heating (50HG Units)

NOTE: THE 50HG units have 2 stages of heat.

For 50HG units, the heat type will automatically be set to 2

for electric heat units if the electric heat was installed in the fac-
tory (HT.TY). If electric heat is being installed in the field, the
user must change HT.TY from 0 to 2. If a 15 kW heater is in-
stalled, N.HTR must be changed from 2 to 1.

Heat will not operate if the outdoor temperature is greater

than the heat lockout temperature (HT.LO).
THERMOSTAT CONTROL — The  first  stage  of  electric
heat (HTR.1) will follow the W1 input and the second stage
(HTR.2) of heat will follow the W2 input. During auto fan, the
indoor fan will follow the HTR.1 output. During continuous
fan, the indoor fan will follow the G input.

ERROR CODE

LED INDICATION

Normal Operation

On

Hardware Failure

Off

Fan On/Off Delay Modified

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Five Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Inducer Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Software Lockout

9 Flashes

IGC

Integrated Gas Unit Controller

LED

Light-Emitting Diode

Summary of Contents for 48HG016

Page 1: ...ONS Installation and servicing of air conditioning equipment can be hazardous due to system pressure and electrical compo nents Only trained and qualified service personnel should install repair or se...

Page 2: ...with drain wire and is field supplied and installed See Table 6 for wiring infor mation The system elements are connected to the communica tion bus in a daisy chain arrangement The positive pin of eac...

Page 3: ...3 Fig 1 Low Voltage Control Schematic 48HG Units...

Page 4: ...4 Fig 2 Low Voltage Control Schematic 50HG Units...

Page 5: ...5 Fig 3 Typical Power Schematic...

Page 6: ...m Temp Device with Set Point Adjustment Terminal Block Terminal Unmarked Terminal Marked Splice Factory Wiring Field Wiring To indicate common potential only not to represent wiring To indicate FIOP o...

Page 7: ...11 12 MBB Saturated Condensing Temperature for Cir B SCT_B Circuit B condenser hairpin SCT_C T5 J8 13 14 MBB Saturated Condensing Temperature for Cir C SCT_C Circuit C condenser hairpin Transducers SS...

Page 8: ...J8 15 16 MBB TB3 11 12 Part No HK06WC028 Y1 J7 10 MBB TB4 2 Thermostat Y1 1st Stage Cooling Y2 J7 8 MBB TB4 3 Thermostat Y2 2nd Stage Cooling W1 J7 6 MBB TB4 4 Thermostat W1 1st Stage Heating W2 J7 4...

Page 9: ...Fan Motor 48HG only Fan Power J10 3 MBB Allows indoor fan to operate OFC1 J10 19 MBB Controls outdoor fan motor 1 OFC2 J10 16 MBB Controls outdoor fan motor 3 and 6 also 2 and 5 on size 028 units OFC3...

Page 10: ...Mounting 2 3 4 5 6 1 SW1 SEN BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING 2 3 4 5 6 1 SW1 SEN SET Cool Warm WHT T56 BLK GND RED SPT RED WHT GND BLK CCN COM SENSOR WIRING JUMPER TERMINALS AS...

Page 11: ...eferred configuration CONTROLS AND FUNCTIONS Marquee Display Usage See Fig 7 and Tables 7 21 The display module provides the user interface to the ComfortLink control system The display has up and dow...

Page 12: ...ode can used to test the system outputs that are independent and can operate in all modes fan only cooling and heating These outputs are ECON E PWR PE 1 PE 2 and ALM When an economizer output ECON oth...

Page 13: ...un Hours HTR 2 XXXX Heat Stage 2 Run Hours PE 1 XXXX Power Exhaust1 Run Hours PE 2 XXXX Power Exhaust2 Run Hours E PWR XXXX Economizer Pwr Run Hours ALM XXXX Alarm Output Run Hours CYCS Component Cycl...

Page 14: ...ON OFF Compressor B1 Test C1 ON OFF Compressor C1 Test HEAT Test Heating HTR 1 ON OFF Heat Stage 1 Test HTR 2 ON OFF Heat Stage 2 Test SUBMODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION COMMENT UNIT Uni...

Page 15: ...ng Set points OCSP XX Occupied Cool Set point Default 78 UCSP XX Unoccupied Cool Set point Default 85 HEAT Heating Set points OHSP XX Occupied Heat Set point Default 68 UHSP XX Unoccupied Heat Set poi...

Page 16: ...lity CS IN Current Sensor Inputs CS A1 ON OFF A1 Current Sensor CS B1 ON OFF B1 Current Sensor CS C1 ON OFF C1 Current Sensor SUBMODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION FANS Fan Outputs IDF ON O...

Page 17: ...h 1 Normal Open 2 Normal Close ECB YES NO ECB Installed Default YES SAT T XXX SAT Settling Time Secs Default 240 sec COOL Cooling Configuration N CMP X Number of Compressors Default 3 016 024 2 014 02...

Page 18: ...Default Yes EN SW X Enthalpy Switch Input Default 0 0 No Switch 1 Normal Open 2 Normal Close PE EN YES NO Power Exhaust Control Default NO PE1 P XXX PE Stage1 Econo Position Default 25 PE2 P XXX PE St...

Page 19: ...t YES A SSP YES NO SSP Transducer Failure Default YES A SCT YES NO SCT Thermistor Failure Default YES A FAN YES NO Indoor Fan Failure Default YES A FIL YES NO Plugged Filter Default YES A TST YES NO T...

Page 20: ...cal Schedule 65 99 Global Schedule OVR E OVR E YES NO SPT Override Enabled Default YES OTL OTL X Override Time Limit Default 4 SCH L Local Occupancy Schedule PER 1 Occupancy Period 1 OCC 1 XX XX Perio...

Page 21: ...Saturday In Period Default No SUN 3 YES NO Sunday In Period Default No HOL 3 YES NO Holiday In Period Default No PER 4 Occupancy Period 4 OCC 4 XX XX Period Occupied Time Range 00 00 to 23 59 Default...

Page 22: ...Range 00 00 to 23 59 Default 00 00 UNC 7 XX XX Period Unoccupied Time Range 00 00 to 23 59 Default 00 00 MON 7 YES NO Monday In Period Default No TUE 7 YES NO Tuesday In Period Default No WED 7 YES NO...

Page 23: ...4 X Holiday Start Day Default 0 LEN 4 XX Holiday Duration Days Default 0 HOL 5 Holiday 5 MTH 5 XX Holiday Start Month Default 0 DAY 5 X Holiday Start Day Default 0 LEN 5 XX Holiday Duration Days Defa...

Page 24: ...O Scrolling stops YES Select YES YES Changed accepted MON 1 YES Monday In Period Item Value Units scrolls again TUE 1 NO Tuesday In Period NO Scrolling stops YES Select YES YES Changed accepted TUE 1...

Page 25: ...If a compressor shuts down because of a safety the software will set the compressor request A1 B1 or C1 to OFF forcing the user to reselect the compressor to restart the compressor in Service mode Al...

Page 26: ...Centurion unit can only store one local schedule and therefore changing this number only changes the title of the schedule table c SCH N 65 99 Follow the global programmed schedule If the Centurion u...

Page 27: ...ues are 50 25 and 0 for circuits A B and C respectively The maximum value will remain in effect until the compressor in trouble turns off The effective maximum economizer position must always be highe...

Page 28: ...opposite order In all cases the minimum on time of 3 minutes MRT C and the minimum off time of 5 minutes MOT C must be honored Therefore if the staging order is BtoT and Circuit A was shut down two m...

Page 29: ...r description of IGC operation NOTE The jumper wire in the installer s packer must be con nected between R and W1 when using a T55 T56 or T58 device See Fig 1 and 2 During Space Sensor control two met...

Page 30: ...the last stage of compressor might cycle rapidly slowed only by its minimum on and off time requirements For size 016 to 024 units the algorithm must decide how to map a two stage thermostat to three...

Page 31: ...it to shut down for 15 min utes This feature reduces the likelihood of false alarms causing a properly working system to be shutdown incorrectly If three strikes occur before the circuit has an opport...

Page 32: ...causes are 1 Welded contactor 2 Frozen compressor relay on MBB To check out alerts 51 55 and 59 1 Place the unit in Service Test Mode All compressors should be Off 2 Verify that there is not 24V at t...

Page 33: ...e with Economizer Actuator This alert occurs when the MBB cannot communicate with the Belimo Actuator This is usually caused by a wiring problem Investigate using the Low Voltage Schematic Alarm Code...

Page 34: ...W1 is turned On Alert Code 413 Y and W Simultaneously This alert occurs in Thermostat Mode when Y1 or Y2 is energized simul taneously with W1 or W2 Verify thermostat and thermostat wiring The software...

Page 35: ...ards loose or broken fan belt plugged filter drier faulty transducer exces sively cold return air or stuck open economizer when the ambient temperature is low T140 Circuit C Loss of Charge Shutdown Ci...

Page 36: ...er coil dirty or restricted Clean coil or remove restriction Excessive head pressures Loose condenser thermistors Tighten thermistors Dirty condenser coil Clean coil Refrigerant overcharge Recover exc...

Page 37: ...r Check economizer position and configuration Adjust mini mum position using ComfortLink Scrolling Marquee Limit switch cycles main burners Check rotation of blower thermostat heat anticipator set tin...

Page 38: ...38 Fig 13 IGC Control Heating and Cooling LEGEND NOTE Thermostat Fan Switch in the AUTO position IDM Induced Draft Motor IGC Integrated Gas Unit Controller...

Page 39: ...ng the resistance with unit shut down and thermistor dis connected from J8 Compare the values determined with the value read by the control in the Temperatures mode using the Scrolling Marquee display...

Page 40: ...96 86 1 340 4 000 87 1 319 3 906 88 1 298 3 814 89 1 278 3 726 90 1 257 3 640 91 1 237 3 556 92 1 217 3 474 93 1 198 3 395 94 1 179 3 318 95 1 160 3 243 96 1 141 3 170 97 1 122 3 099 98 1 104 3 031 99...

Page 41: ...710 23 1 623 5 461 24 1 580 5 225 25 1 538 5 000 26 1 497 4 786 27 1 457 4 583 28 1 417 4 389 29 1 378 4 204 30 1 340 4 028 31 1 302 3 861 32 1 265 3 701 33 1 229 3 549 34 1 194 3 404 35 1 160 3 266...

Page 42: ...2 231 8 056 87 2 202 7 869 88 2 173 7 685 89 2 144 7 507 90 2 115 7 333 91 2 087 7 165 92 2 059 6 999 93 2 030 6 838 94 2 003 6 683 95 1 975 6 530 96 1 948 6 383 97 1 921 6 238 98 1 894 6 098 99 1 86...

Page 43: ...580 109 075 21 4 557 102 868 20 4 533 97 060 19 4 508 91 588 18 4 482 86 463 17 4 455 81 662 16 4 426 77 162 15 4 397 72 940 14 4 367 68 957 13 4 335 65 219 12 4 303 61 711 11 4 269 58 415 10 4 235 55...

Page 44: ...Delay Gas Heat 45 600 45 sec GAS_FOD SAT Cool Demand Level 0 5 10 0 1 0 F SAT_POS SAT Cool Demand Level 10 0 0 5 1 0 F SAT_NEG SAT Settling Time 10 900 240 sec SAT_SET Minimum SAT Upper Level 35 0 65...

Page 45: ...tch 0 Not Installed 1 Normally Open 2 Normally Closed 0 No FIOP 1 FIOP FILSTCFG Fire Shutdown Switch 0 Not Installed 1 Normally Open 2 Normally Closed 0 No FIOP 2 FIOP SHTDNCFG Remote Occupancy Switch...

Page 46: ...XB Middle Stage Max Econmzr 0 100 25 ECONMAXM Top Stage Max Econmzr 0 100 0 ECONMAXT Economizer PID Deadband 0 25 3 ECONBAND Economizer PID kP 0 0 99 9 2 5 ECONO_P Economizer PID kI 0 0 99 9 12 ECONO_...

Page 47: ...nnn TIMGD_H2 N CIRCUIT A Saturated Suct Temp A snnn n dF SST_A N Saturated Suct Press A nnn n PSIG SSP_A N Saturated Cond Temp A snnn n dF SCT_A N Saturated Cond Press A 0 0 PSIG SCP_A N Compressor A1...

Page 48: ...Input On Off G Y DESCRIPTION STATUS UNITS POINT FORCIBLE Economizer Power On Off ECON_PWR N Economizer Commanded Pos nn ECONOCMD N Economizer Position nn ECONOPOS N Minimum Position in Effect Nnn MIN_...

Page 49: ...Lag Factor n n COOL_LAG Y SPT Cool Demand Level n n F DEM_POS Y SPT Cool Demand Level sn n F DEM_NEG Y SAT Cool Demand Level n n F SAT_POS Y SAT Cool Demand Level sn n F SAT_NEG Y MET2Add SAT Trend Le...

Page 50: ...1 Compressor B1 Cycles nnnnnn CY_B1 Compressor C1 Cycles nnnnnn CY_C1 Indoor Fan Run Hours nnnnn nn hours HR_IDF Indoor Fan Cycles nnnnnn CY_IDF OD Fan Cont 1 Run Hours nnnnn nn hours HR_OFC_1 OD Fan...

Page 51: ...rent Mode 1 Occup 0 1 MODE Current Occup Period 0 8 PER NO Timed Override in Effect Yes No OVERLAST Time Override Duration 0 4 hours OVR_HRS Current Occupied Time hh mm STRTTIME Current Unoccupied Tim...

Page 52: ...Txxx ALARM03C Active Alarm 4 Axxx or Txxx ALARM04C Active Alarm 5 Axxx or Txxx ALARM05C Active Alarm 6 Axxx or Txxx ALARM06C Active Alarm 7 Axxx or Txxx ALARM07C Active Alarm 8 Axxx or Txxx ALARM08C A...

Page 53: ......

Page 54: ...ange at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80090 Printed in U S A Form 48 50HG 2T Pg 54 202 10 01 Replaces 48 50HG 1T Book 1 1 4...

Page 55: ...Stage Y1 OC FN ________ Y N S DLY ________ 30 IDF F ________ N Y FN SW ________ No Switch Normal Open Normal Close FL SW ________ No Switch Normal Open Normal Close FS SW ________ No Switch Normal Op...

Page 56: ...100 PPM AQD H ________ 700 PPM I 4M ________ 0 PPM I 20M ________ 2000 PPM O 4M ________ 0 PPM O 20M ________ 2000 PPM OAQ L ________ 600 PPM CCN CCN A ________ 1 CCN B ________ 0 BAUD ________ 3 9600...

Reviews: