background image

48/50PG C03-14
48/50PM C16-28
Single Package Rooftop Units
With 

COMFORT

Link

t

 Controls Version 5.x

and PURON

R

 (R-410A) Refrigerant

Controls, Start-Up, Operation, Service

and Troubleshooting Instructions

IMPORTANT: This literature covers 48/50PG03−14 and
48/50PM16−28 models with Comfortlink Software version 5.x.
The 48/50PG C16−28 (15 – 25 ton) model reference has been
removed from this manual; however version 5.x software is
backward compatible with all Comfortlink PG models.  Refer to
past manuals for  obsolete model information.

TABLE OF CONTENTS

Page

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . . . . . . .

GENERAL

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

BASIC CONTROL USAGE

3

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Comfort

Link

 Control

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Scrolling Marquee

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessory Navigator Display

4

. . . . . . . . . . . . . . . . . . . . . . . . . .

Operation

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Pilot

 and Touch Pilot Devices

4

. . . . . . . . . . . . . . . . .

CCN Tables and Display

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Conventions Used in This Manual

6

. . . . . . . . . . . . . . . . . . . . . .

START−UP

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit Preparation

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Mounting

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant Service Ports

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Crankcase Heater(s)

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Rotation

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Power Supply

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Internal Wiring

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Evaporator Fan

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Condenser Fans and Motors

8

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Return−Air Filters

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor−Air Inlet Screens

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Baffles

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessory Installation

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Orifice Change (48PG and 48PM)

8

. . . . . . . . . . . . . . . . . . . . . .

Gas Heat (48PG and 48PM)

8

. . . . . . . . . . . . . . . . . . . . . . . . . .

EnergyX

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CONTROLS QUICK SET−UP

8

. . . . . . . . . . . . . . . . . . . . . . . . .

Control Set Point and Configuration Log

8

. . . . . . . . . . . . . . . .

Thermostat Control

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Space Temperature Sensor Control − Direct Wired
(T−55 or T−56 or T−59)

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T−58 Communicating Room Sensor

9

. . . . . . . . . . . . . . . . . . . .

CCN Linkage Control

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

System Pilot − Communication Space Sensor

9

. . . . . . . . . . . . .

Thermidistat Control

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Space Humidistat Control

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Relative Humidity Sensor Control

9

. . . . . . . . . . . . . . . . . . . . . .

CCN Communication

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accessories

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Programming Operating Schedules

10

. . . . . . . . . . . . . . . . . . . .

SERVICE TEST

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Independent Outputs

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fan Test

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cooling Test

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Humidi−MiZer

 Test

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Heating Test

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

THIRD PARTY CONTROL

13

. . . . . . . . . . . . . . . . . . . . . . . . . .

Cooling/Heating Control

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Dehumidification Control

13

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Remote Occupancy

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fire Shutdown

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Alarm Output

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Economizer Monitoring

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Economizer Damper Control

14

. . . . . . . . . . . . . . . . . . . . . . . . .

CONTROLS OPERATION

14

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Display Configuration

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit Configuration

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Modes

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

General Operation

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature Setpoint Determination

16

. . . . . . . . . . . . . . . . . . .

Occupancy Determination

17

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Fan Operation

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cooling Operation

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Heating Operation

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Economizer

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Optional Humidi−MiZer

 Dehumidification System

24

. . . . . .

Indoor Air Quality (IAQ)

30

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

EnergyX

34

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Adaptive Fan

34

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature Compensated Start

35

. . . . . . . . . . . . . . . . . . . . . . .

Carrier Comfort Network (CCN)

 Configuration

35

. . . . . . . . .

Demand Limit

36

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Linkage

36

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Alarm Handling

37

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Summary of Contents for 48/50PG C03-14

Page 1: ...sory Installation 8 Orifice Change 48PG and 48PM 8 Gas Heat 48PG and 48PM 8 EnergyX 8 CONTROLS QUICK SET UP 8 Control Set Point and Configuration Log 8 Thermostat Control 8 Space Temperature Sensor Co...

Page 2: ...lacing filters Trained service personnel should perform all other operations When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and o...

Page 3: ...nk control system is easy to access through the use of a unit mounted display module There is no need to bring a separatecomputer to this unit for start up Access to control menus is simplified by the...

Page 4: ...turn the display to its default menu of rotating AUTO VIEW display items In addition the password will need to be entered again before changes can be made Changing item values or testing outputs is ac...

Page 5: ...l force The Scrolling Marquee uses a Control Force at level 7 The Navigator writes a Service Force which is level 3 System Pilots and Touch Pilots write Supervisor Forces at level 4 Network programs c...

Page 6: ...he crankcase heaters are energized if there is power to the unit the compressor is not operating and the ambient temperature is below 75 F IMPORTANT Unit power must be on for 24 hours prior to start u...

Page 7: ...S PANEL CONDENSER COIL ACCESS PANEL C07002 Fig 4 48 50PG03 14 Size Units Panel and Filter Locations 48PG03 07 Unit Shown CONTROL BOX FILTER ACCESS DOOR GAS SECTION OUTDOOR AIR SCREEN HIDDEN PEM 1 2 CO...

Page 8: ...Scrolling Marquee display Temporarily install the jumper wire between R and W1 on TB1 Use the Service Test feature to set Service Test HEAT HT 1 to ON first stage of heat using the Scrolling Marquee M...

Page 9: ...itch configuration Configuration UNIT RH SW identifies the normally open or normally closed status of this input at LOW humidity and the input is the Humidistat 1 terminal only on Humidi MiZer units S...

Page 10: ...Sunday to ON with the desired Occupied On and Off times NOTE By default the time schedule periods are programmed for 24 hours of occupied operation To create a schedule perform the following procedur...

Page 11: ...d Unoccupied Time Item Value Units scrolls again MON 1 NO Monday In Period ENTER NO Scrolling stops YES Select YES ENTER YES Change accepted ESCAPE MON 1 YES Monday In Period Item Value Units scrolls...

Page 12: ...compressor is turned on The Reduced Cool Fan Speed F SPD can only be changed while one stage is running If more then one stage is on the actual fan speed will be 100 F SPD shows the reduced speed not...

Page 13: ...y open or normally closed status of this input at LOW humidity The Humidistat 1 terminal is the input signal and R can be used as the source NOTE Dehumidification is considered a cooling function in t...

Page 14: ...ation section for more information CONTROLS OPERATION Display Configuration The Configuration DISP submenu is used to configure the local display settings Metric Display METR This variable is used to...

Page 15: ...then the unit determines dehumidification demand based on this input and the appropriate set point A NO value disables SP RH display and use Space Humidity Switch RH SW This configuration identifies i...

Page 16: ...ntrol Type Configuration UNIT T CTL affects how cooling operates based on Y1 and Y2 commands and if cooling heating stage time guards are applied When space temperature sensor control is enabled Confi...

Page 17: ...Broadcaster Configuration CCN BROD B GS YES the unit will follow the unit s programmed schedule and broadcast the schedule so that other devices programmed to follow this schedule number can receive...

Page 18: ...ut Based on the unit control configuration requested cooling stages Run Status COOL REQ C will be determined then passed to compressor control to actually add the cooling stages Thermostat Control The...

Page 19: ...to protect the compressors Compressor Min On Time Configuration COOL MRT C and Compressor Min Off Time Configuration COOL MOT C apply before a compressor can be turned back on or turned off Outdoor F...

Page 20: ...0 size 20 PM16 40 sizes 24 28 57 Level 3 On 65 68 PG03 16 size 24 28 88 size 20 PM16 Level 3 Off 55 62 PG03 16 size 24 28 78 size 20 PM16 NOTE Where not specified the models are both PG and PM Levels...

Page 21: ...er The default Supply Air Temperature location is at the fan inlet upstream of the heat section When SAT H ENBL the Supply Air Temperature Temperatures AIR T SAT sensor reading is displayed at the Scr...

Page 22: ...ration HEAT MOT H apply before a heat relay can be turned back on or turned off Integrated Gas Controller IGC The heat staging is determined as described above and the Integrated Gas Controller IGC in...

Page 23: ...allows the ComfortLink system to communicate with the actuator through a feedback signal The configuration Economizer Control Type determines the communication method either digital or analog used to...

Page 24: ...his configuration sets the offset above the heating set point at which a unit in Reheat2 mode will turn off This is a protection against over cooling the space and causing a heat demand NOTE When ther...

Page 25: ...2 x Valve 2 way No power OFF Off Off Off Off open Off open Off closed Off Off closed Low No Off Per Ventilation Control Off Off Off Off open On closed Off closed Off Off closed Low Yes Cool On On Off...

Page 26: ...ALVE RH1 x RH2 x CV x C07004 Fig 10 Subcooling Mode Reheat1 Humidi MiZert System 48 50PG03 16 COMP COND COIL HUMIDI MIZER COIL EVAP COIL INDOOR ENTERING AIR OUTDOOR AIR METERING DEVICE CLOSED VALVE OP...

Page 27: ...x RH2 x a48 8222 C07122 Fig 12 Normal Cooling Mode Humidi MiZert System 48 50PG20 28 and 48 50PM16 28 COMP COND COIL HUMIDI MIZER COIL EVAP COIL INDOOR ENTERING AIR OUTDOOR AIR METERING DEVICE CLOSED...

Page 28: ...uit can be restricted from Reheat2 operation by the outside temperature and saturated suction temperature Reheat2 OAT Limit A Configuration HMZR RA LO and Reheat2 OAT Limit B C Configuration HMZR RB L...

Page 29: ...A value of On will turn on circuit A in Reheat2 mode Service Test HMZR RH2 B Reheat2 B C Test A value of On will turn on circuits A B and C in Reheat2 mode Service Test HMZR CRC Cool Reheat1 Valve Tes...

Page 30: ...on IA CF 1 DCV When IA CF 1 the IAQ algorithm is set for Demand Control Ventilation DCV During DCV the damper modulates between two user configurations depending upon the relationship between the IAQ...

Page 31: ...31 C07009 Fig 18 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...

Page 32: ...32 C08077 Fig 19 Air Baffle Dimensions 48 50PM16 28 48 50PG and PM...

Page 33: ...2 DCV NC The Demand Control Ventilation DCV allows the economizer minimum position to be decreased when there is no IAQ problem If IAQ is low the economizer minimum position is Minimum IAQ Damper Pos...

Page 34: ...d with a linearly variable VFD concept the different speeds are pre programmed per condition there is no linear modulation of fan speed Adaptive Fan is enabled by setting Adaptive Fan Operation to yes...

Page 35: ...erature compensated start is disabled when these factors are set to 0 Temperature Compensated Start Logic The following conditions must be met for the algorithm to run Unit is in unoccupied state Next...

Page 36: ...vidually with configuration decisions If the active stages is greater then the loadshed or redline configurations when a loadshed or redline command is given the unit will remove stages Configuration...

Page 37: ...ke configuration is ignored during Service Test and all alerts are broadcast Alarm Relay Output The alarm relay output is a normally open 24 vac output between field connection terminal board terminal...

Page 38: ...he Current Sensor CS detects current when the compressor should be off When this occurs the control turns off all of the compressors Use the Scrolling Marquee to reset the alert The possible causes ar...

Page 39: ...s situation when the compressor is operating Alert Codes T126 T127 and T142 Circuit High Discharge Pressure Alert codes T126 T127 and T142 are for circuits A B and C respectively These alerts have Ser...

Page 40: ...and verify the resistance between pins on the LEN connections Alert Code T180 Loss of Communication with the Economizer Actuator This alert occurs when the ECB cannot communicate with the Belimo Actua...

Page 41: ...ulty 5 V power supply or loose connection T101 Circuit C Suction Pressure Transducer Failure Lockout Circuit C Manual Faulty transducer faulty 5 V power supply or loose connection T102 Compressor A1 C...

Page 42: ...incorrect Fan Status Switch OFF fan commanded on If IDF F Yes then Unit Shutdown If IDF F YES then Manual otherwise automatic Tripped Circuit Breaker Broken belt Bad indoor fan motor Configuration inc...

Page 43: ...with W1 or W2 Verify thermostat and thermostat wiring The software will enter either the cooling or heating mode depending upon which input turned on first This alert resets automaticallywhen Y1 and...

Page 44: ...e board If the red LEDs are not blinking in unison verify that correct power is being supplied to all modules A blinking red LED at the rate of once per second means that software is not loaded on the...

Page 45: ...sized for load Decrease load or increase size of unit Thermostat or occupancy schedule set point too low Reset thermostat or schedule set point Dirty air filters Replace filters Low refrigerant charge...

Page 46: ...put Configuration UNIT RH S using ComfortLink Scrolling Marquee No humidity signal Check wiring Check humidistat or humidity sensor CRC Relay Operation No 24V signal to input terminals Check using Coo...

Page 47: ...hermostat is not calling for heating or cooling Unit is in Unoccupied mode and there is no call for heating or cooling Tripped circuit breaker No power to the unit Unit is off via CCN command Actuator...

Page 48: ...set point not calling for Cooling Check using ComfortLink Scrolling Marquee No gas at main burners Check gas line for air and purge as necessary After purging gas line of air allow gas to dissipate fo...

Page 49: ...49 LEGEND IDM Induced Draft Motor IGC Integrated Gas Unit Controller NOTE Thermostat Fan Switch in the AUTO position C07014 Fig 21 IGC Service Analysis Logic 48 50PG and PM...

Page 50: ...ware error If fault is not cleared by resetting 24 v power replace the IGC 9 Flashes Temporary Software Lockout No gas heating 1 hour auto reset or power reset Electrical interference is disrupting th...

Page 51: ...ure SAT outdoor air temperature OAT space temperature sensors T55 T56 T58 and return air temperature RAT The supply air temperature SAT and outdoor air temperature OAT thermistors use a snap mount to...

Page 52: ...essure of the refrigerant circuits The pressure voltage characteristics of these transducers are in shown in Table 22 the 5vdc power is applied to legs A and B of the transducer and legs B to C repres...

Page 53: ...9 1 108 12 4 273 58 781 98 1 894 6 098 184 0 491 1 089 13 4 254 57 039 99 1 867 5 961 185 0 483 1 070 14 4 235 55 319 100 1 841 5 827 186 0 476 1 052 15 4 215 53 693 101 1 815 5 698 187 0 468 1 033 16...

Page 54: ...272 561 13 3 124 28 473 97 1 122 3 099 181 0 268 551 14 3 103 27 624 98 1 104 3 031 182 0 264 542 15 3 082 26 804 99 1 086 2 964 183 0 259 533 16 3 060 26 011 100 1 068 2 898 184 0 255 524 17 3 038 25...

Page 55: ...2 848 40 0 859 108 1 529 176 2 198 244 2 868 42 0 879 110 1 548 178 2 218 246 2 887 44 0 898 112 1 568 180 2 237 248 2 907 46 0 918 114 1 588 182 2 257 250 2 927 48 0 938 116 1 607 184 2 277 252 2 94...

Page 56: ...56 C08549 Fig 25 48PG03 16 Control Wiring Schematic 48 50PG and PM...

Page 57: ...57 C08550 Fig 26 50PG03 16 Control Wiring Schematic 48 50PG and PM...

Page 58: ...58 C101249 Fig 27 Typical 48 50PG03 14 Power Wiring Schematic and Legend 48 50PG08 14 Shown 48 50PG and PM...

Page 59: ...59 C08552 Fig 28 Typical 48PG03 16 with Humidi MiZert System Control Wiring Schematic 48PG08 16 Shown 48 50PG and PM...

Page 60: ...60 C08554 Fig 29 Typical 50PG03 16 with Humidi MiZert System Control Wiring Schematic 50PG08 16 Shown 48 50PG and PM...

Page 61: ...61 C101250 Fig 30 Typical 48 50PG03 14 with Humidi MiZert System Power Wiring Schematic and Legend 48 50PG08 14 Shown 48 50PG and PM...

Page 62: ...62 C08471 Fig 31 Typical 48PM16 28 Control Schematic 48 50PG and PM...

Page 63: ...63 C08062 Fig 32 Typical 48PM16 28 with Humidi MiZert System Control Schematic 48 50PG and PM...

Page 64: ...64 C101251 Fig 33 Typical 50PM16 28 Control Schematic 48 50PG and PM...

Page 65: ...65 C08064 Fig 34 Typical 50PM16 28 with Humidi MiZert Control Schematic 48 50PG and PM...

Page 66: ...66 C10902 Fig 35 Typical 48 50PM16 28 Power Schematic 48 50PG and PM...

Page 67: ...67 C09213 Fig 36 Typical 48 50PM16 28 with Humidi MiZert System Power Schematic 48 50PG and PM...

Page 68: ...P COMPRESSOR S OAT SCT COMPRESSOR CONTACTOR CAPACITOR CURRENT SENSOR TB1 LOW VOLTAGE TERMINAL STRIP OFC CCHR MBB ECB CB IGC TRAN 1 TRAN 2 UNIT CONTROL BOX IFC C07025 Fig 37 Typical 48 50PG03 16 Unit C...

Page 69: ...69 C08067 Fig 38 48 50PM16 28 Component Arrangement 48 50PG and PM...

Page 70: ...70 C101252 Fig 39 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...

Page 71: ...e Current Sensor inputs for compressors and other discrete or digital inputs The MBB reads space temperature SPT from either a T 55 T 56 or T 58 device and space temperature offset SPTO from a T 56 de...

Page 72: ...l circuit A 5k thermistor J8 9 10 SCT B Saturated condenser temperature circuit B outdoor coil circuit B 5k thermistor J8 11 12 SCT C Saturated condenser temperature circuit C outdoor coil circuit C 5...

Page 73: ...controls two power exhaust outputs By digitally communicating with the ECB the economizer actuator is able to provide the damper position and diagnostic information to the ComfortLink controller The d...

Page 74: ...sensor or Relative humidity sensor field installed 0 20 mA J5 5 Sensor Common Ground J5 3 Actuator Common Ground J7 3 OUTPUTS Output power to enthalpy switch 24 VAC J4 3 Output power for loop power s...

Page 75: ...MINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I O CONNECTION PIN NUMBER INPUTS RT C Input power from TRAN 1 control box 24 VAC SS Speed sensor gas section analog input J1 1 3 FS T1 Flame senso...

Page 76: ...0 11 12 7 ENTH or IAQ S Outdoor enthalpy switch or Indoor air quality switch economizer or return space 24 VAC input J10 9 10 8 EC CP Economizer commanded position actu ator when in digital control ec...

Page 77: ...PVC PVC nylon vinyl Teflon or polyethylene An aluminum polyester 100 foil shield and an outer jacket of PVC PVC nylon chrome vinyl or Teflon with a minimum operating temperature range of 20 C to 60 C...

Page 78: ...Volume HVAC Heating Ventilation and Air Conditoning TCU Terminal Control Unit C07030 Fig 46 CCN System Architecture EnergyX Units equipped with Optional EnergyX have a factory installed energy recove...

Page 79: ...cupants to override the unoccupied schedule if programmed The jumper wire in the installer s packet must be connected between R and W1 when using a T 56 device TB T55 1 Sensor Input TB T55 2 Sensor Co...

Page 80: ...2 SPACE TEMPERATURE AVERAGING 4 T 55 SENSOR APPLICATION SPACE TEMPERATURE AVERAGING 9 T 55 SENSOR APPLICATION LEGEND TB Terminal Block ______ Factory Wiring _ _ _ _ Field Wiring C07032 Fig 47 Space T...

Page 81: ...ssory detects when the indoor fan is blowing air When installing this accessory the unit must be configured for fan status by setting Configuration UNIT FN SW to normally open 1 or normally closed 2 N...

Page 82: ...ct unit interior at beginning of each heating and cooling season and as operating conditions require Remove unit top panel and or side panels for access to unit interior Coil Maintenance and Cleaning...

Page 83: ...LIABILITY HAZARD Failure to follow this caution may result in reduced unit performance High velocity water from a pressure washer garden hose or compressed air should never be used to clean a coil The...

Page 84: ...ove motor and wheel assembly by removing the screws holding the flue box cover to the flue box See Fig 50 or 51 Remove the screws holding the inducer housing to the inlet plate The wheel can then be r...

Page 85: ...isconnect the electrical wires connected to the slide out fan deck supply air thermistor and fan status switch if installed Wires may be damaged if not disconnected For 48 50PM16 28 units disconnect t...

Page 86: ...Loosen nuts on the 4 carriage bolts in the mounting base Using adjusting bolts and plate slide motor and remove belt 3 Loosen movable pulley flange setscrew See Fig 54 4 Screw movable flange toward f...

Page 87: ...nger Coil The service replacement coil is preformed and is equipped with transition joints with copper stub tubes When brazing the connection joints to the unit tubing use a wet cloth around the alumi...

Page 88: ...to the liquid line between the condenser and the TXV thermostatic expansion valve and insulate it so that ambient temperature does not affect reading To Use the Cooling Charging Chart Standard Unit NO...

Page 89: ...Leavin eaving Temp Temp eratu erature re Deg Degrees rees F F C07041 Fig 61 Charging Chart 48 50PG06 R4 R410A RE REFRI RIGERANT RANT OUTDOOR F R FAN M N M UST BE OPERATING ON H N HIGH S H SPEED 20 20...

Page 90: ...Charging Chart 48 50PG12 R4 R410 10A A REF REFRI RIG GE ERANT RANT A AL LL L O OUT UTDO DOO OR R F FANS ANS M MUS UST T B BE E R RUNNI UNNING NG 20 20 40 40 60 60 80 80 10 100 0 12 120 0 14 140 0 16...

Page 91: ...L GAS ORIFICE PROPANE ORIFICE QQ0 1 999 43 50 NN2 000 44 51 NN3 000 44 51 NN4 000 44 51 NN5 000 45 51 NN6 000 45 52 NN7 000 47 52 NN8 000 47 52 NN9 000 47 53 N10 000 48 53 N11 000 49 53 N12 000 50 54...

Page 92: ...ess oxygen is in the air See Table 28 for orifice sizing A high altitude kit is available to convert unit for altitudes up to 7 000 ft Main Burners 48PG and 48PM For all applications main burners are...

Page 93: ...equipped with a manual reset calibrated trip magnetic circuit breaker and overcurrent protection Do not bypass connections or increase the size of the breaker to correct trouble Determine the cause a...

Page 94: ...ECONCOOL COOL Cooling Status COOLDISP DMD C Cooling Demand xxx x F COOL_DMD AVL C Available Cooling Stages x AVLCSTGS REQ C Requested Cooling Stages x REQCSTGS MAX C Max Allowed Cool Stages x MAXCSTGS...

Page 95: ...Temp xxx x F OAU_EXAT OA MN Minimum Outside Air CFM xxxxx CFM MINOACFM DCV M Min DCV Outside Air CFM xxxxx CFM MINDCVSP OA FS OAU OA Fan Speed xxx OAFANSPD A OA Actual Outside Air CFM xxxxx CFM ACTOA...

Page 96: ...s ALRESET forcible Reset Alarm History No Yes ALHISCLR forcible GENERIC CCN only GENERIC up to 20 points LON_DATA CCN only LON_DATA nviSpaceTemp xxx x F NVI_SPT Forcible nviSetPoint xxx x F NVI_SP for...

Page 97: ...1 A Test Off On Off S_RH1_A forcible forcible RH1 B Reheat1 B Test Off On Off S_RH1_B forcible forcible RH1 C Reheat1 C Test Off On Off S_RH1_C forcible forcible RH2 A Reheat2 A Test Off On Off S2_RH2...

Page 98: ...EFC LCSP Low Cool SAT Setpoint 55 to 75 F 55 03 07 65 08 28 LCSASP HCSP High Cool SAT Setpoint 50 to 70 F 55 HCSASP MODE INPUTS ITEM EXPANSION RANGE UNITS CCN TABLE SUB TABLE CCN POINT CCN WRITE STATU...

Page 99: ...uit A Compressor s On Off COMP_A CMP B Compressors B On Off COMP_B CMP C Compressors C On Off COMP_C CCH Crankcase Heat Relay On Off CCH CRC Cool Reheat1 Control On Off CRC RH2 A Reheat2 Valve A On Of...

Page 100: ...Stage Y1 3 Digital 0 STATTYPE 15 OC FN Fan On When Occupied No Yes Yes OCC_FAN 15 IDF F Shut Down on IDF Failure No Yes Yes FATALFAN 15 FN SW Fan Status Switch 0 No Switch 1 Normal Open 2 Normal Clos...

Page 101: ...5 0 to 65 0 F 35 03 07 45 08 14 50 PG16 48 20 28 PM16 SATMIN_L SPT Space Temperature 16 CL PD SPT Cool Demand Level 0 5 to 5 F 1 DEM_POS CL ND SPT Cool Demand Level 5 to 0 5 F 1 DEM_NEG C LAG Cool The...

Page 102: ...to 7 no Humidi MiZer FIOP 0 03 14 3 PG16 0 20 28 PM16 Humidi MiZer FIOP 0 03 14 1 PG16 3 20 28 PM16 CIR_C_3 SST Low Suction Control 39 SST O Suction OK Temperature 10 to 50 F 18 SSTOK SST 1 Low Suctio...

Page 103: ...eat2 SSP Hi Limit A 50 to 100 psig 90 RHSSPH_A 28 RB LO Reheat2 OAT Limit B C 20 to 70 F 50 OATLRH_B 28 RB LP Reheat2 SSP Lo Limit B C 50 to 100 psig 80 RHSSPL_B 28 RB HP Reheat2 SSP Hi Limit B C 50 t...

Page 104: ...E MXB Bottom Stage Max Econo 0 to 100 50 ECONMAXB 104 E MXM Middle Stage Max Econo 0 to 100 35 ECONMAXM 104 E MXT Top Stage Max Econo 0 to 100 25 PG03 16 0 20 28 PM16 ECONMAXT 104 AIR Q Air Quality C...

Page 105: ...NCRV 105 U RUN OAU Unoccupied Operation No Yes NO UNOCCRUN 105 OAU F Shut Down on Fan Failure No Yes Yes FATALOAU 105 M WHL Modulating Wheel Install No Yes NO MODWHEEL 105 OA MN Minimum Outside Air CF...

Page 106: ...NO_I 106 EC D Economizer PID kD 0 00 to 99 90 1 ECONO_D 106 EC DT Economizer PID rate 10 00 to 180 00 secs 15 ECONO_DT 106 EC DB Economizer PID Dead band 0 to 25 3 ECONBAND 106 LK P Linkage Staging PI...

Page 107: ...36 SCH N Schedule Number 0 Always Oc cupied 1 64 Local Schedule 65 99 Global Schedule 0 SCHEDNUM 17 HOL G Accept Global Holidays No Yes No HOLIDAYT 36 OV TL Override Time Limit 0 to 4 hours 4 OTL 17...

Page 108: ...day in Period Yes No No PERxTHU FRI x Friday in Period Yes No No PERxFRI SAT x Saturday in Period Yes No No PERxSAT SUN x Sunday in Period Yes No No PERxSUN HOL x Holiday in Period Yes No No PERxHOL r...

Page 109: ...ges x AVLCSTGS REQ C Requested Cooling Stages x REQCSTGS LMT C Max Cool Stage In Effect x CSTGLIMT ACT C Actual Cooling Stages x ACTCSTGS CMP A Circuit A Compressor s Off On COMP_A CMP B Circuit B Com...

Page 110: ...es IN_COOL OAT Outdoor Air Temperature xxx x F OA_TEMP forcible forcible RAT Return Air Temperature xxx x F RETURN_T forcible forcible E LOC Econo Cool OAT Lockout No Yes ECONLOCK D LOC Econo Diff Dbu...

Page 111: ...Supervisory Element xxx SUPE ADR Supervisory Bus xxx SUPE BUS Supervisory Block Number xxx BLOCKNUM Average Occup Heat Stp xxxx x F AOHS Average Occup Cool Stp xxxx x F AOCS Average Unocc Heat Stp xx...

Page 112: ...figuration 1 and 2 Stage Y1 Thermostat Control Type configuration 2 ECONO AVAILABLE Y1 Y2 HUMIDISTAT CIRCUIT A CIRCUIT B ECONOMIZER NO OFF OFF LOW OFF OFF Min Position Econo closed if fan off NO OFF O...

Page 113: ...eral Fan Performance Notes Fan Performance 48PGD04 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N900 448 0 09 581 0 1...

Page 114: ...ous bhp is 0 85 for low range motor drive and 0 85 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF04 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE...

Page 115: ...and 1 60 single phase for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGE05 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rp...

Page 116: ...l Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 593 0 27 688 0 37 773 0 46 851 0 56 925 0 67 1600 620 0 32 711 0 42 793 0...

Page 117: ...single phase and 2 40 3 phase for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF06 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0...

Page 118: ...ow range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGE07 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8...

Page 119: ...e motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGD08 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rp...

Page 120: ...low range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF08 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0...

Page 121: ...low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGE09 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0...

Page 122: ...for high range motor drive All other rpms require a field supplied drive 2 Maximum continuous bhp is 2 40 for low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance No...

Page 123: ...3 10 for low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF12 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2...

Page 124: ...RFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 911 2 17 954 2 36 996 2 55 1037 2 75 1076 2 95 3950 930 2 39 972 2 59 1012 2 79 1052...

Page 125: ...W Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 920 2 21 963 2 40 1004 2 59 1045 2 79 1084 3 00 3950 940 2 44 982 2 64 1022 2 84 1061 3...

Page 126: ...AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 925 2 23 968 2 42 1009 2 62 1050 2 82 1089 3 02 3950 946 2 47 987 2 67 1027 2 87 1067 3 08 11...

Page 127: ...Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N900 422 0 08 552 0 14 659 0 21 751 0 28 834 0 35 N950 430 0 09 557 0...

Page 128: ...s 0 85 for low range motor drive and 0 85 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF04 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0...

Page 129: ...0 single phase and 2 40 3 phase for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGE05 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6...

Page 130: ...48PGD06 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 521 0 22 628 0 31 718 0 40 800 0 49 877 0 60 1600 546 0...

Page 131: ...single phase and 2 40 3 phase for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF06 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6...

Page 132: ...w range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGE07 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0...

Page 133: ...continuous bhp is 2 40 for low range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGD08 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC...

Page 134: ...low range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF08 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6...

Page 135: ...ow range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGE09 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0...

Page 136: ...ther rpms require a field supplied drive 2 Maximum continuous bhp is 2 40 for low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGD12 Hori...

Page 137: ...for low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 48PGF12 Horizontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4...

Page 138: ...IRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 853 1 93 898 2 11 941 2 30 983 2 49 1025 2 69 3950 869 2 12 912 2 31 955 2 51 996 2...

Page 139: ...IRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 862 1 96 907 2 15 950 2 34 992 2 53 1033 2 73 3950 879 2 17 923 2 36 965 2 56 1006...

Page 140: ...18 AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 868 1 99 912 2 17 955 2 36 997 2 56 1038 2 76 3950 885 2 19 928 2 39 970 2 58 1...

Page 141: ...Notes Fan Performance 50PG04 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N900 438 0 09 574 0 15 685 0 23 780 0 30 86...

Page 142: ...50PG06 Vertical Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 568 0 25 667 0 34 753 0 44 833 0 54 908 0 64 1600 592 0 29...

Page 143: ...supplied drive 2 Maximum continuous bhp is 2 40 for low range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 50PG08 Vertical Units AIRFLOW Cfm AVAI...

Page 144: ...ve All other rpms require a field supplied drive 2 Maximum continuous bhp is 2 40 for low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 50PG...

Page 145: ...FLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3750 878 2 03 922 2 22 965 2 41 1006 2 60 1047 2 80 3950 895 2 24 938 2 43 979 2 63 1020 2...

Page 146: ...zontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N900 413 0 08 544 0 14 653 0 20 748 0 27 832 0 35 N950 420 0 09 549 0 15 6...

Page 147: ...zontal Units AIRFLOW Cfm AVAILABLE EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 1500 491 0 19 604 0 28 697 0 37 781 0 47 859 0 57 1600 513 0 23 623 0 32 7...

Page 148: ...r rpms require a field supplied drive 2 Maximum continuous bhp is 2 40 for low range motor drive and 3 10 for high range motor drive 3 See General Fan Performance Notes Fan Performance 50PG08 Horizont...

Page 149: ...ire a field supplied drive 2 Maximum continuous bhp is 2 40 for low range motor drive and 3 70 for high range motor drive 3 See General Fan Performance Notes Fan Performance 50PG12 Horizontal Units AI...

Page 150: ...4 06 1075 4 30 5350 941 3 65 980 3 89 1017 4 13 1054 4 38 1089 4 62 5550 958 3 96 996 4 21 1033 4 46 1069 4 71 1103 4 96 5750 975 4 28 1013 4 54 1049 4 80 1084 5 06 5950 993 4 63 1030 4 89 1065 5 16 6...

Page 151: ...4500 527 0 82 A 599 1 03 A 670 1 28 A 745 1 60 A 822 1 99 A 4800 551 0 97 A 619 1 18 A 685 1 43 A 753 1 73 A 825 2 10 A 5100 575 1 12 A 639 1 35 A 701 1 60 A 764 1 89 A 830 2 25 A 5400 599 1 30 A 661...

Page 152: ...based on 460V motor max BHP Grey cells indicate field supplied pulley change required Fan Performance 48PME20 and 48PMF20 Vertical Supply Return Units Available External Static Pressure in wg 0 2 0 4...

Page 153: ...code based on 460V motor max BHP Grey cells indicate field supplied pulley change required Fan Performance 48PME24 and 48PMF24 Vertical Supply Return Units CFM Available External Static Pressure in wg...

Page 154: ...Drive option code based on 460V motor max BHP Grey cells indicate field supplied pulley change required Fan Performance 48PME28 and 48PMF28 Vertical Supply Return Units CFM Available External Static...

Page 155: ...Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive RPM BHP Drive 4500 4800 5100 834 2 26 A 5400 836 2 40 A 900 2 80 A 5700 842 2 57 A 901 2 94 A 6000 851 2 76 A 905 3 12 A 961 3 53 A 6300 862 2 99 A 913...

Page 156: ...D Bhp Brake Horsepower Input to Fan Rpm Fan speed Drive Drive option code based on 460V motor max BHP Grey cells indicate field supplied pulley change required Fan Performance 50PM24 Vertical Supply R...

Page 157: ...7 93 C 1005 8 42 C 1041 8 93 D 1076 9 46 D 1111 10 00 D 1145 10 54 D Available External Static Pressure in wg 1 4 1 6 1 8 2 0 2 2 2 4 CFM RP M BHP Driv e RPM BHP Driv e RPM BHP Driv e RPM BHP Driv e R...

Page 158: ...ve RPM BHP Drive RPM BHP Drive 4500 800 2 18 F 861 2 47 F 918 2 75 F 972 3 04 F 1024 3 01 F 4800 845 2 51 F 903 2 80 F 958 3 10 F 1009 3 05 F 1059 3 41 F 5100 891 2 86 F 946 3 17 F 998 3 47 F 1048 3 4...

Page 159: ...irflow Cfm Available External Static Pressure in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N5000 F 1112 3 88 F 1156 4 25 G 1199 4 63 G 1240 5 02 G 1280 5 42 N5500 G 1171 4 67 G 12...

Page 160: ...9 rpm 8 63 Bhp All other rpms require field supplied drive 2 See General Fan Performance Notes Fan Performance 48PMF20 Horizontal Supply Return Units Airflow Cfm Available External Static Pressure in...

Page 161: ...H High Range 1096 to 1339 rpm 8 63 Bhp All other rpms require field supplied drive 2 See General Fan Performance Notes Fan Performance 48PME24 Horizontal Supply Return Units Airflow Cfm Available Ext...

Page 162: ...irflow Cfm Available External Static Pressure in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N5500 G 1189 4 90 G 1232 5 31 G 1273 5 72 H 1313 6 15 1352 6 58 N6000 H 1251 5 85 H 1292...

Page 163: ...Cfm Available External Static Pressure in wg 1 2 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N6500 F 988 3 97 G 1035 4 39 G 1082 4 87 G 1129 5 39 H 1177 5 95 N7000 G 1024 4 57 1066 4 98 11...

Page 164: ...flow Cfm Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N6500 F 1005 4 12 G 1052 4 57 G 1100 5 06 G 1148 5 60 H 1195 6 17 N7000 G 1041 4 72 1084 5...

Page 165: ...flow Cfm Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp N6500 F 1005 4 12 G 1052 4 57 G 1100 5 06 G 1148 5 60 H 1195 6 17 N7000 G 1041 4 72 1084 5...

Page 166: ...quired Do not exceed listed motor maximum BHP value Motor Drive Ranges E Low Range 208 230 and 460V RPM Range 685 to 939 Maximum BHP 4 26 575V RPM Range 751 to 954 Maximum BHP 5 75 F Mid Low Range All...

Page 167: ...Bhp Rpm Bhp Rpm Bhp N5500 886 2 97 E 935 3 25 985 3 55 1035 3 87 1086 4 21 N6000 E 916 3 41 960 3 69 1005 3 98 1050 4 29 1096 4 61 N6500 949 3 90 990 4 19 F 1032 4 48 F 1073 4 78 F 1114 5 10 N7000 98...

Page 168: ...8 22 H 1249 8 59 N9000 1175 8 18 1204 8 50 H 1232 8 83 1260 9 18 1288 9 53 N9500 1222 9 22 H 1249 9 55 1276 9 88 1302 10 22 1329 10 58 10000 H 1270 10 34 1296 10 68 1321 11 02 1346 11 37 1371 11 72 10...

Page 169: ...at 3750 6250 3150 6300 Air Quantity Limits 48PM16 28 Units 48PM COOLING GAS HEAT HEATING NAT GAS VERTICAL HEATING NAT GAS HORIZONTAL HEATING PROPANE VERTICAL HEATING PROPANE HORIZONTAL Minimum Cfm Max...

Page 170: ...3 2 575 3ph 0 80 2 4 2 4 High 208 3ph 0 84 3 1 8 8 230 3ph 0 84 3 1 8 8 460 3ph 0 84 3 1 4 4 575 3ph 0 82 3 7 4 2 09 Low 208 3ph 0 80 2 4 6 4 230 3ph 0 80 2 4 6 4 460 3ph 0 80 2 4 3 2 575 3ph 0 80 2 4...

Page 171: ...mature motor failure Unit warranty will not be af fected 2 Convert bhp to watts using the following formula watts bhp 746 motor efficiency 3 The EPACT Energy Policy Act of 1992 regulates energy requir...

Page 172: ...5 4 460 87 5 5 75 7 7 575 87 5 5 75 6 0 High Horizontal 208 88 5 7 66 22 0 230 88 5 8 51 22 0 460 88 5 8 63 11 6 575 88 5 8 63 9 4 20 Low Vertical 208 85 8 4 26 10 6 230 85 8 4 26 9 6 460 85 8 4 26 4...

Page 173: ...6 0 Mid Low Vertical 208 87 5 5 37 15 8 230 87 5 5 75 15 4 460 87 5 5 75 7 7 575 87 5 5 75 6 0 Mid High Vertical 208 88 5 7 66 22 0 230 88 5 8 51 22 0 460 88 5 8 63 11 6 575 88 5 8 63 9 4 High Vertica...

Page 174: ...51 22 0 460 88 5 8 63 11 6 575 88 5 8 63 9 4 High Horizontal N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A 20 Low Vertical 208 85 8 4 26 10 6 230 85 8 4 26 9 6 460 85 8 4 26 4 8 575...

Page 175: ...87 5 5 75 15 4 460 87 5 5 75 7 7 575 87 5 5 75 6 0 Mid Low Vertical 208 87 5 5 37 15 8 230 87 5 5 75 15 4 460 87 5 5 75 7 7 575 87 5 5 75 6 0 Mid High Vertical 208 88 5 7 66 22 0 230 88 5 8 51 22 0 46...

Page 176: ...High 941 961 980 1000 1019 1039 1059 1078 1098 1117 1137 1156 1176 High 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Horizontal Low n a n a n a n a n a n a n a n a n a n a n a n a...

Page 177: ...019 1039 1059 1078 1098 1117 1137 1156 1176 High Range Vertical 1014 1038 1061 1085 1108 1132 1156 1179 1203 1226 1250 1273 1297 Low Range Horizontal 751 768 785 802 819 836 853 869 886 903 920 937 95...

Page 178: ...13 0 18 0 49 0 07 3000 0 15 0 21 0 56 0 08 Accessory FIOP Pressure Drop in wg 48 50PG08 14 AIRFLOW CFM ELECTRIC HEAT ECONOMIZER Vertical ECONOMIZER Horizontal Humidi MiZer SYSTEM 2250 0 03 0 05 0 10 0...

Page 179: ...in wg 50PM16 28 CFM Nominal Heater Size kw Pressure Drop in wg Nominal Heater Size kw Pressure Drop in wg Nominal Heater Size kw Pressure Drop in wg 4800 25 0 01 50 0 02 75 0 03 5000 0 01 0 02 0 04 6...

Page 180: ...Ds Off On Off display only not in table DISPTEST 14 UNIT Unit Configuration UNIT 14 S DLY Startup Delay 10 to 600 sec 30 STARTDLY 14 U CTL Unit Control Type 2 Thermostat 3 Space Sensor 2 CTL_TYPE 14 T...

Page 181: ...45 08 14 50 PG16 48 20 28 PM16 SATMIN_L SPT Space Temperature 16 CL PD SPT Cool Demand Level 0 5 to 5 F 1 DEM_POS CL ND SPT Cool Demand Level 5 to 0 5 F 1 DEM_NEG C LAG Cool Thermal Lag Factor 0 to 5...

Page 182: ...OP 0 03 14 3 PG16 0 20 28 PM16 Humidi MiZer FIOP 0 03 14 1 PG16 3 20 28 PM16 CIR_C_3 SST Low Suction Control 39 SST O Suction OK Temperature 10 to 50 F 18 SSTOK SST 1 Low Suction Level 1 10 to 50 F 20...

Page 183: ...to 100 psig 90 RHSSPH_A 28 RB LO Reheat2 OAT Limit B C 20 to 70 F 50 OATLRH_B 28 RB LP Reheat2 SSP Lo Limit B C 50 to 100 psig 80 RHSSPL_B 28 RB HP Reheat2 SSP Hi Limit B C 50 to 100 psig 90 RHSSPH_B...

Page 184: ...Econo 0 to 100 50 ECONMAXB 104 E MXM Middle Stage Max Econo 0 to 100 35 ECONMAXM 104 E MXT Top Stage Max Econo 0 to 100 25 PG03 16 0 20 28 PM16 ECONMAXT 104 AIR Q Air Quality Config IAQ_CFG 14 IA CF...

Page 185: ...ccupied Operation No Yes NO UNOCCRUN 105 OAU F Shut Down on Fan Failure No Yes Yes FATALOAU 105 M WHL Modulating Wheel Install No Yes NO MODWHEEL 105 OA MN Minimum Outside Air CFM 0 to 32000 CFM 375 P...

Page 186: ...PID kD 0 00 to 99 90 1 ECONO_D 106 EC DT Economizer PID rate 10 00 to 180 00 secs 15 ECONO_DT 106 EC DB Economizer PID Dead band 0 to 25 3 ECONBAND 106 LK P Linkage Staging PID kP 0 00 to 99 90 10 LI...

Page 187: ...ber 0 Always Oc cupied 1 64 Local Schedule 65 99 Global Schedule 0 SCHEDNUM 17 HOL G Accept Global Holidays No Yes No HOLIDAYT 36 OV TL Override Time Limit 0 to 4 hours 4 OTL 17 OV EX Timed Override H...

Page 188: ...TION VALUES FOR ELECTRONIC CONTROLS REFER TO CONTROL SET UP CHECKLIST VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR AT LEAST 24 HOURS II START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 CO...

Reviews: