APPENDIX B - VFD INFORMATION (CONT)
Table 40 — VFD CONFIGURATIONS
APPLICATION CRITICAL DRIVE PARAMETERS FOR ABB ACH550 DRIVES
Parameter Group
Parameter
Number
Description
Value
UNITS
NOTE
HK30WA001---208/230V
HK30WA008---460V
START---UP
DATA
9901
Language
(0) English
---
ABB Drive default
9902
Application Macro
(1) HVAC Default
---
PD Product specific
setting
9904
Motor Control Mode
(3) Scalar : Freq
---
ABB Drive default
9905
Motor Nominal Voltage
230
460
Volts
PD Product specific
setting
9906
Motor Nominal Current
7.0
3.5
Amps
PD Product specific
setting
9907
Motor Nominal Frequency
60
Hz
ABB Drive default
9908
Motor Nominal Speed
1725
RPM
PD Product specific
setting
9909
Motor Nominal Power
2.4
HP
PD Product specific
setting
START/STOP/DIR
1001
EXT1 Commands
(1) DI --- 1 Start/Stop
---
ABB Drive default
1002
EXT2 Commands
(1) DI --- 1 Start/Stop
---
ABB Drive default
1003
Direction
(1) Forward
---
PD Product specific
setting
ANALOG INPUTS
1301
Minimum Al --- 1
20
%
ABB Drive default
1302
Maximum Al --- 1
100
%
ABB Drive default
RELAY OUTPUTS
1401
Relay Output 1
(7) Started
---
Carrier default settings
from PPS
1402
Relay Output 2
(2) Run
---
ABB Drive default
1403
Relay Output 3
(3) Fault (---1)
---
ABB Drive default
SYSTEM
CONTROL
1601
Run Enable
(0) Not Set
---
ABB Drive default
1608
Start Enable 1
(4) DI --- 4
---
ABB Drive default
OVER RIDE
1701
Override Set
(3) DI --- 3
---
Carrier default settings
from PPS
1702
Override Freq
60
Hz
Carrier default settings
from PPS
1703
Override Speed
1750
RPM
Carrier default settings
from PPS
1704
Over Pass Code
0
---
Carrier default settings
from PPS
1705
Override
On
---
Carrier default settings
from PPS
LIMITS
2003
Maximum Current
8.0
4.0
Amps
PD Product specific
setting
2007
Minimum Frequency
0
Hz
ABB Drive default
2008
Maximum Frequency
60
Hz
ABB Drive default
START/STOP
2101
Start Function
(8) Ramp
---
PD Product specific
setting
2102
Stop Function
(2) Ramp
---
PD Product specific
setting
ACCEL/DECEL
2202
Accelerate Time
30
Seconds
ABB Drive default
2203
Decelerate Time
30
Seconds
ABB Drive default
MOTOR
2601
Flux Optimization
(1) On
---
PD Product specific
setting
2605
Volt/Freq Ratio
(2) Squared
---
Carrier default settings
from PPS
2606
Switching Frequency
8
kHz
Carrier default settings
from PPS
FAULT
FUNCTIONS
3006
Motor Thermal Time
1050
Seconds
Carrier default settings
from PPS
All Other Parameter Settings are ABB Drive Default Settings
48/
50P