background image

19

If all of the above conditions are met, the controller uses a

PID logic loop to energize or de--energize heat outputs to

satisfy the heat demand. If the SAT begins to exceed the

high supply air setpoint, a ramping function will cause the

Heat Stages Capacity algorithm to decrease the number of

stages until the SAT has dropped below the setpoint.

There is a fixed one minute minimum on time and a one

minute off time for each heat output. Heat staging has a 2

minute stage up and 30 second stage down delay.
Heat pump operation is the same as above except for what

is explained below. There is a fixed 3 minute on and 5

minute off time for the first heat stage output, and a one

minute on and one minute off time for the second heat

stage output. There is a 10 minute minimum stage up

delay if the heat demand is <= 3

_

F, and a 2 minute

minimum stage up delay if heat demand is > 3

_

F. The

stage down delay is still 30 seconds. If the Compressor

Safety Alarm is active, the second heat stage will come on

with the first stage with no delay.

Indoor Air Quality

If the optional indoor air quality sensor is installed, the

RTU--OPEN will maintain indoor air quality within the

space at the user configured differential set point. The set

point is the difference between the indoor air quality and

an optional outdoor air quality sensor. If the outdoor air

quality is not present then a fixed value of 400ppm is

used. The following conditions must be true in order for

this algorithm to run:

S

The mode is occupied.

S

Indoor Fan has been ON for at least 30 seconds.

S

Indoor Air Quality sensor has a valid reading.

As air quality within the space changes, the minimum

position of the economizer damper will be changed thus

allowing more or less outdoor air into the space depending

on the relationship of the indoor air quality to the

differential setpoint. If all the above conditions are true,

the IAQ algorithm will run and calculates an IAQ

minimum position value using a PID loop. The IAQ

minimum damper position is then compared against the

user configured economizer minimum position and the

greatest value becomes the final minimum damper

position of the economizer output.
If the calculated IAQ minimum position is greater than

the DCV Max Vent Damper Pos configuration, then it will

be clamped to the configured value.

Dehumidification

The RTU--OPEN will provide occupied and unoccupied

dehumidification only on units that are equipped with the

Humidi--MiZer

t

option from the factory. This function

requires a space relative humidity sensor or a humidistat

for control. The space relative humidity senor can be

installed and configured as one of the two analog input

channels (inputs 1 or 2 on J4), or a humidistat can be

installed and configured as switch input 9 on J5. When

using

a

relative

humidity

sensor

to

control

dehumidification,

occupied

or

unoccupied

dehumidification setpoints are use accordingly. When

using a humidistat, setpoints are not used and the

dehumidification call comes when the humidistat

indicates high humidity.

When the indoor relative humidity becomes greater then

the dehumidification setpoint (or switches from low to

high), a dehumidification demand will acknowledged.

Compressor state is monitored and time guards are

honored. If a compressor was just turned off prior to the

dehum call the dehumidification output will be delayed

the 5 minute minimum off time of the compressor. When

ok to dehumidify, the dehumidification output (J11--7, 8)

will be energized. This will bring on the supply fan, all

compressors, and the dehumidification relay placing the

unit in Hot Gas Reheat dehumidification mode. If

dehumidification is called for during cooling or cooling is

called for during dehumidification, the unit will run in

Subcooling dehumidification mode. Individual unit

circuits can be in different dehumidification modes based

on the demand. Refer to the base units operation for

additional information.

NOTE

: There is a fixed 5% hysteresis that the indoor

relative humidity must drop below the active setpoint to
end the dehumidification mode and de--energize the
dehumidification output. The output will also de--energize
if the fan relay is de--energized.

Demand Limit

If the RTU--OPEN receives a level 1 (one degree offset), 2

(two degree offset), or a 3 (4 degree offset) to the BACnet

demand limit variable, the controller will outwardly

expand the heating and cooling setpoints by the

configured demand limit setpoint value and remain in

effect until the BACnet demand limit variable receives a 0

value.

Unoccupied Free Cooling

When the unit is equipped with an economizer, the control

can run a night time free cooling (NTFC) mode called

Unocc Free Cooling. In this mode the damper is utilized

to bring in outdoor air for free cooling during unoccupied

periods. The following conditions must be true for

unoccupied free cooling to operate:

S

Unocc Free Cool Enable set to Enable

S

The system is unoccupied

S

The outside air temperature is below the Economizer
High OAT Lockout Temp

S

The outside air temperature is less than the space
temperature

S

Enthalpy (if enabled) is Low

When the RTU--OPEN schedule is unoccupied and the

space temperature rises at least 1 degree above the

Occupied Cooling Setpoint, the supply fan starts. The

economizer damper opens as necessary to cool the space.

The RTU--OPEN continues to operate in this mode until

the space is satisfied or the outside air conditions are no

longer suitable for free cooling.

Summary of Contents for 48/50HC04---14

Page 1: ...mpressor 2 Test 13 Heat 1 and Heat 2 Test 13 Reversing Valve Test 13 Dehumidification Test 14 Power Exhaust Test 14 Economizer Test 14 Analog Output 2 Test 14 Configuration 14 Setpoint 14 Unit 14 Inpu...

Page 2: ...RNING GENERAL The RTU OPEN controller is an integrated component of the Carrier rooftop unit Its internal application programming provides optimum performance and energy efficiency RTU OPEN enables th...

Page 3: ...3 C10818 Fig 1 RTU OPEN Control Module...

Page 4: ...d S Space temperature sensor SPS SPPL SPP SPPF 33ZCT55SPT 33ZCT56SPT or 33ZCT59SPT S Indoor air quality sensor 33ZCSENCO2 33ZCT55CO2 33ZCT56CO2 required for demand control ventilation S Outdoor air qu...

Page 5: ...5 C10819 Fig 2 Typical Factory Option Wiring...

Page 6: ...rs and BACview6 must be addressed Use the jumpers on the SPS sensor s circuit board and refer to the BACview6 s installation instructions for addressing For Rnet wiring up to 500ft 152m use 18 AWG 4 c...

Page 7: ...7 BLK RED SPACE TEMPERATURE AVERAGING 4 SENSOR APPLICATION SPACE TEMPERATURE AVERAGING 9 SENSOR APPLICATION LEGEND Factory Wiring Field Wiring 1 2 C07133 Fig 5 Space Temperature Averaging C10820 Fig...

Page 8: ...actory default control for the Humidi MiZert option To wire in the field S J5 8 24 VAC source for dry contact S J5 7 Signal input Single Enthalpy Outdoor Enthalpy The outdoor enthalpy switch receiver...

Page 9: ...NIT SHUTDOWN Smoke Alarm Signal input to RTU OPEN NOTE Input 5 can also be wired into J5 3 Filter Status The filter status accessory is a field installed accessory This accessory detects plugged filte...

Page 10: ...to the RTU OPEN is through plug J19 See Fig 13 for wiring Refer to the RTU OPEN 3rd Party Integration Guide for more detailed information on protocols 3rd party wiring and networking NOTE Power must...

Page 11: ...ev J The speed of a Modbus network can range from 9600 to 76 8K baud Physical Addresses can be set from 01 to 99 Johnson N2 N2 is not a standard protocol but one that was created by Johnson Controls I...

Page 12: ...ere is a 10 minute auto logout if a screen is left idle See Appendix A for navigation and screen content Virtual BACview Virtual BACview is a freeware computer program that functions as the BACview6 H...

Page 13: ...Service Test function can be used to verify proper operation of compressors heating stages indoor fan power exhaust fans economizer and dehumidification Use of Service Test is recommended at initial...

Page 14: ...upied Cooling Setpoint The cooling setpoint the controller maintains during the unoccupied period Range 55 99_F Effective Heating Setpoint The current setpoint value heating operation will control to...

Page 15: ...nsor Default Enable Setpoint Adjustment Range Sets the slider range of a space sensor with built in function The slider is used to offset the control setpoint Range 0 5n_F Default 5n_F Cooling Lockout...

Page 16: ...able on a specific unit Set this point to One Stage if there is one compressor in the specific unit set to Two Stage if there are two compressors in the unit and set to None if economizer cooling ONLY...

Page 17: ...ing a local or OPEN schedule The push button will override an unoccupied period to occupied for the specified time duration BAS On Off When Occupancy Source is set to BAS On Off RTU OPEN follows occup...

Page 18: ...ons must be true for economizer operation S Indoor Fan has been on for at least 30 seconds S Enthalpy is Low if the Enthalpy input is enabled S SAT reading is available S OAT reading is available S SP...

Page 19: ...figured as one of the two analog input channels inputs 1 or 2 on J4 or a humidistat can be installed and configured as switch input 9 on J5 When using a relative humidity sensor to control dehumidific...

Page 20: ...a differential pressure switch that senses the pressure drop across a filter bank When the pressure across the filter bank exceeds the setpoint of the differential pressure switch the Filter status i...

Page 21: ...nsor To check accuracy use a high quality digital volt ohmmeter Connect the meter to the thermistor leads to obtain a resistance value Use Table 2 to convert that resistance to a temperature Next step...

Page 22: ...per second Off Normal 2 flashes per second 2 flashes alternating with Run LED Five minute auto restart delay after system error 2 flashes per second 3 flashes then off Control module has just been for...

Page 23: ...e value is less then the low allowed value or Space value is greater then the high allowed value Alarming Temperature spt_alrm_temp Shows temperature that caused alarm N A N A Alarm Limit Exceeded spt...

Page 24: ...aced by Aux Heat Stage 2 The compressor output stays on when the safety alarm is present For cooling the alarm indicates the compressors are down Space Temp Sensor This alarm occurs if the space senso...

Page 25: ...ndicates the space humidity falls below the alarm configuration Low Space Humidity Alarm Limit for 5 minutes This alarm is inhibited until the RTU runs for 5 minutes to allow for system stabilization...

Page 26: ...and contain embedded information ORT These first three digits are unique to RTU OPEN and are used as an identifier YM These two digits identify the last digit of the year and month in hex A 10 Oct of...

Page 27: ...vice Configuration Maintenance Alarms Linkage BACview Navigation STATUS MAINT ALARM BACnet LINKAGE SETPOINT Alarm Login Keypad Sched UserPw Weekly schedule Network Exceptions ClockSet ALARMS DST LINKA...

Page 28: ...SETTINGS BACnet BACnet Device Instance xxxxxxx 1610100 Base BACnet Device ID xxxxxxx 1610100 Autogenerate Device ID Y N Y Keypad Keypad Configuration Inactivity Timeout 1 255 minutes 10 BACnet Write...

Page 29: ...re sa_temp xxx F Outdoor Air Temperature oa_temp xxx F Space Relative Humidity space_rh 0 100 Indoor Air CO2 iaq 0 5000 ppm Outdoor Air CO2 oaq 0 5000 ppm Economizer Output econ_output 0 100 open LINK...

Page 30: ...ty Set point unocc_de hum_stpt 30 100 rh 95 DCV Max Ctrl Setpoint iaq_stpt_max 0 9999 ppm 650 Power Exhaust Setpoint pexh_stpt 20 90 Open 50 Sched Weekly schedule MON SUN none BACview Only Exceptions...

Page 31: ...lter Service Alarm Timer filter_service_hrs 0 9999 hr 600 Pushbutton Override pb_enable Disable En able Enable Setpoint Adjustment stpt_adj_enable Disable En able Enable Setpoint Adjustment Range stpt...

Page 32: ...Contact Compressor Safety Input 3 Switch Configuration di3_type N O N C N O Input 5 Function di5_function 1 No Function 2 Fire Shut down 3 Fan Status 4 Filter Status 5 Remote Oc cupancy 6 Door Contac...

Page 33: ...3 phase gas units HC04 09 3 phase gas units and All 12 30 gas units Continuous Occupied Exhaust occ_exh No Yes No Indoor CO2 Sensor Value Min mA iaq_ref_lo_ppm 0 9999ppm 0 Indoor CO2 Sensor Value Max...

Page 34: ...ble Active Compressor Stages comp_run x Active Heat Stages heat_run x Enthalpy Status enthalpy_status High Low Humidistat Input Status humstat_status Low High Filter Status filter_status Clean Dirty D...

Page 35: ...t_alrm_status Normal Alarm Alarming Temperature spt_alrm_temp xxx F Alarm Limit Exceeded spt_alrm_lmt xxx F High Supply Air Temperature sat_hi_alarm Normal Alarm Low Supply Air Temperature sat_lo_alar...

Page 36: ...rete in 10030 BI 30 SNVT_switch 95 nvo CompSafety Compressor Safety Status R comp_status BV 1008 Continuous Occu pied Exhaust R W occ_exh BV 9002 Cooling Lockout Temperature R W oat_cl_lockout AV 9002...

Page 37: ...R filter_status BV 1004 Fire Shutdown R fire_alarm BV 7007 discrete in 10032 BI 32 SNVT_switch 95 nvoFireShut down Fire Shutdown Status R fire down_status BV 1005 Heat Stage 1 Relay State R heat_1 BV...

Page 38: ...Low Space Temp Alarm R spt_lo_alarm BV 7012 discrete in 10039 BI 39 SNVT_switch 95 nvo LoSpaceTemp Low Supply Air Tem perature R sat_lo_alarm BV 7021 discrete in 10040 BI 40 SNVT_switch 95 nvoLoSATAl...

Page 39: ...emp_p 105 nviUnoc cCoolSP Setpoint Effective Cooling Setpoint R W eff_cl_stpt AV 4 Setpoint Effective Heating Setpoint R W eff_ht_stpt AV 5 Setpoint Heating Occupied Setpoint R W occ_ht_stpt AV 3002 f...

Page 40: ...10024 BI 24 SNVT_switch 95 nvoFanStatus Switch Configuration R di_cfg_alarm BV 7025 System Cooling De mand Level R cool_de mand_level AV 9006 System Heating De mand Level R heat_de mand_level AV 9036...

Page 41: ...y Setpoint occ_dehum_stpt 0 unocc setpoint rh 60 Unocc Relative Humidity Setpoint unocc_de hum_stpt 30 100 rh 95 DCV Max Ctrl Setpoint iaq_stpt_max 0 9999 ppm 650 Power Exhaust Setpoint pexh_stpt 20 9...

Page 42: ...s 0 9999 hr 0 Filter Service Alarm Timer filter_service_hrs 0 9999 hr 600 Pushbutton Override pb_enable Disable Enable Enable Setpoint Adjustment stpt_adj_enable Disable Enable Enable Setpoint Adjustm...

Page 43: ...Switch Configuration di3_type N O N C N O Input 5 Function di5_function 1 No Function 2 Fire Shutdown 3 Fan Status 4 Filter Status 5 Remote Occu pancy 6 Door Contact Fire Shutdown Input 5 Switch Confi...

Page 44: ...s heat_stages 1 2 0 no heat 0 50 series cooling only units 1 All TCQs and HCQs Low Nox units single phase gas units TC04 09 low and TC05 07 med heat 3 phase gas units 2 TC04 and 08 09 med TC05 09 high...