APPENDIX B -- THIRD PARTY POINTS LIST (CON’T)
(IN ALPHABETICAL ORDER)
BACnet
Modbus
N2
LON Works
Point Name
Read/
Write
BACnet Point
Name
OBJECT
ID
Register
Type
Register
#
Network
Point
Type
Network
Point
Address
SNVT Type
SNVT Name
Override Time Re-
maining
R
ovrde_time
AV:2016
float
value
40093
ADF
41
SNVT_time_min
(123)
nvoOvrTimeR
emain
Password Protected
Output Variable
R/W
ppo
AV:90000
Power Exhaust Relay
State
R
pexh
BV:2010
Power Exhaust Set-
point
R/W
pexh_stpt
AV:3010
float
value
40097
ADF
43
SNVT_lev_per-
cent (81)
nviPwrExhSp
Power Exhaust Test
R/W
pexh_test
BV:81008
Pushbutton Override
R
pb_status
BV:31
Reset Comp 1
Runtime Alarm
R/W
comp1_rntm_
clr
BV:7514
Reset Comp 2
Runtime Alarm
R/W
comp2_rntm_
clr
BV:7515
Reset Filter Runtime
Alarm
R/W
filter_rntm_clr
BV:7517
discrete
out
22
BO
22
SNVT_switch
(95)
nvoSafety-
Chain
Reset Supply Fan
Runtime Alarm
R/W
sfan_rntm_clr
BV:7510
Safety Chain
R
safety_alarm
BV:7024
Safety Chain Feed-
back
R
safety_status
BV:1009
Schedule
R/W
schedule
BV:8000
Service Test
R/W
test_enable
BV:81000
Setpoint / Cooling
Occupied Setpoint
R/W
occ_cl_stpt
AV:3001
float
value
40009
ADF
4
SNVT_temp_p
(105)
nviOccCoolSP
Setpoint / Cooling
Setpoint Adjust
R/W
cl_stpt_adj
AV:2
Setpoint / Cooling
Unoccupied Setpoint
R/W
unocc_cl_stpt
AV:3003
float
value
40015
ADF
7
SNVT_temp_p
(105)
nviUnoc-
cCoolSP
Setpoint / Effective
Cooling Setpoint
R/W
eff_cl_stpt
AV:4
Setpoint / Effective
Heating Setpoint
R/W
eff_ht_stpt
AV:5
Setpoint / Heating
Occupied Setpoint
R/W
occ_ht_stpt
AV:3002
float
value
40019
ADF
9
SNVT_temp_p
(105)
nviOccHeatSP
Setpoint / Heating
Setpoint Adjust
R/W
ht_stpt_adj
AV:3
Setpoint / Heating
Unoccupied Setpoint
R/W
unocc_ht_stpt
AV:3004
float
value
40017
ADF
8
SNVT_temp_p
(105)
nviUnoc-
cHeatSP
Setpoint Adjust
R/W
stpt_adj_en-
able
BV:1013
discrete
out
26
BO
26
SNVT_switch
(95)
nviSPAdjEn-
able
Setpoint Adjustment
R
stpt_adj
AV:1006
float
value
40099
ADF
44
SNVT_temp_p
(105)
nvoSPAdjust
Setpoint Adjustment
Range
R/W
stpt_adj_rang
e
AV:9015
float
value
40101
ADF
45
SNVT_temp_p
(105)
nviS-
PAdjRange
Setpoint Slider
R
slidepot_alarm
BV:7002
Shutdown
R/W
shutdown
BV:9001
Space Relative Hu-
midity
R
space_rh
AV:1011
float
value
40103
ADF
46
SNVT_lev_per-
cent (81)
nvoSpaceRH
Space Relative Hu-
midity Sensor
R
sprh_alarm
BV:7022
discrete
in
10045
BI
45
SNVT_switch
(95)
nvoSpaceRH-
Sensor
Space sensor type
R/W
spt_type
MSV:9001
Space Temp / Over-
ride Time Remaining
R/W
over-
ride_time_re-
maining
AV:1
Space Temp / Zone
Temp
R
zone_temp
AI:1
Space Temp Sensor
R
spt_fail
BV:7001
discrete
in
10046
BI
46
SNVT_switch
(95)
nvoSPTemp-
Sensor
Space Temp Sensor
R
spt_status
MSV:2003
Space Temperature
R
spt_alrm_statu
s
BV:37
Space Temperature
--- Prime Variable
R
space_temp
AV:2007
float
value
40107
ADF
48
SNVT_temp_p
(105)
nvoSpaceTem
p
Space Temperature
Offset Pot
R
stpt_adj_offset
AV:91006