12
Table 10 — 45K Series Fan Powered Terminal Unit Performance
NOTES:
1. 45K maximum primary airflow (cfm) is set by the maximum induced air-
flow, which may vary as a function of downstream pressure. Maximum air-
flow shown is based on the maximum induced airflow (fan airflow) or 1.00
in. wg differential pressure signal from inlet airflow sensor, whichever is
less.
2. Minimum recommended primary airflow (cfm) is based on 0.03 in. wg dif-
ferential pressure of the inlet airflow sensor, or 0 airflow. 0.03 in. wg is
equal to 15% to 20% of the nominal flow rating of the terminal. Less than
15% to 20% may result in greater than +5% control of box flow.
3. 45K maximum/minimum fan airflow is based on 0.10 in. wg / 0.60 in. wg
downstream static pressure, respectively.
45K WITH PSC FAN MOTOR
UNIT SIZE
INLET SIZE (in.)
FAN AIRFLOW (cfm)
PRIMARY AIRFLOW (cfm)
MOTOR
HP
MOTOR AMPS
MIN
MAX
MIN
MAX
120V
208/240V
277V
2
6
50
530
52 or 0
515
1/10
1.4
0.8
0.6
8
92 or 0
530
3
6
200
1100
52 or 0
515
1/4
4.3
2.4
1.8
8
92 or 0
916
10
143 or 0
1100
12
360 or 0
1100
4
8
500
1300
92 or 0
916
1/4
4.3
2.4
1.8
10
143 or 0
1300
12
206 or 0
1300
5
10
800
1900
143 or 0
1432
1/2
8.3
4.4
3.5
12
206 or 0
1900
14
281 or 0
1900
6
10
1200
2600
143 or 0
1432
3/4
9.5
5.0
4.4
12
206 or 0
2062
14
281 or 0
2600
16
367 or 0
2600
7
10
1250
3000
143 or 0
1432
1
N/A
7.1
5.3
12
206 or 0
2062
14
281 or 0
2806
16
367 or 0
3000
45K WITH ECM FAN MOTOR
UNIT SIZE
INLET SIZE (in.)
FAN AIRFLOW (cfm)
PRIMARY AIRFLOW (cfm)
MOTOR
HP
MOTOR AMPS
MIN
MAX
MIN
MAX
120V
208/240V
277V
3
6
250
1030
52 or 0
515
1/2
7.7
5.0
4.1
8
92 or 0
916
10
143 or 0
1030
12
206 or 0
1030
6
10
500
2600
143 or 0
1432
1
12.8
10.5
6.9
12
206 or 0
2000
14
281 or 0
2000
16
367 or 0
2000
7
10
600
2500
143 or 0
1432
1
12.8
10.5
6.9
12
206 or 0
2062
14
281 or 0
2500
16
367 or 0
2500