42VQV

GB - 11

E N G L I S H

Two seconds elapse between the yellow LED and the green LED
lighting.
The sequence ends with both LEDs off for 4 seconds.
Example:
Fault code 12

• The yellow LED blinks (it indicates the tens digits).

• Both LEDS are off for 2 seconds.

• The green LED blinks twice with a 0,5 seconds frequency.

• Both LEDS are off for 4 seconds.

The fault sequence described above is repeated until the fault has
been repaired.
If the fault code is lower than 10, the yellow LED (R) is not
blinking.

Table VI

Code Description

2

Condensate Pump Failure or water drain Failure

3

Indoor unit air sensor failure

4

Indoor unit coil sensor failure (TC)

10

Indoor unit software fault (EEProm Corrupt)

12

Indoor unit software fault 

(Address / Zone)

14

Loss of Signal From CDU

15

Indoor unit coil sensor failure (TCJ)

18

Outdoor unit control box fault (G-Tr short circuit protection)

20

Position Detection Circuit Error

21

Outdoor unit current sensor failure

22

Outdoor unit coil sensor failure (TE)

23

Outdoor unit flow temperature sensor (TD)

24

Outdoor unit Fan fault

26

Other Outdoor unit fault

27

Outdoor unit Compressor Lock

28

Outdoor unit discharge temperature too high

29

Outdoor unit Compressor Breakdown

31

Outdoor unit High Temperature/Pressure Release

For the fault codes of the outdoor unit please refer to Installation
manual of 38VYX.
In case of malfunction, record the fault code, turn the system off,
disconnect the mains power supply and contact a qualified service
engineer.

Operating  test

• Perform the operating test after the units have been installed in

position and the gas leak test has been completed.

• Check all electrical connections  (instructions and wiring diagram).

• Insert the batteries into the remote control and leave it OFF.

• Energise the system, turning the power supply ON.

Fault code, operating  test and guide for the owner

• Press the 

 and 

 buttons of the infrared remote control and

hold them pressed for more than 5 seconds.

The display will be cleared, the time segments will display the icon
(Src = service test).

When test mode is selected, the unit  operates as described below:

• The green  LED and the yellow LED blink every 2 seconds.

• The indoor fan operates at low speed.

• The louver operates according to “Auto heat” or “Auto cool”

based on operating mode.

• The system works in Cool Mode at fixed compressor frequency

for 3 minutes.

• The system stops for 3 minutes.

• The system  works in Heat Mode with fixed compressor

frequency for 3 minutes or until the indoor coil temperature is
greater than 40

°

C.

During the cool mode and heat mode check the following
conditions:

1. Difference between indoor ambient temperature and indoor unit

air discharge temperature must be greater than 3

°

C.

2. Indoor fan must operate at low speed.

3. Louver must be in auto heat or cool louver based on operating

mode.

4. No fault code must be signalled by the system.

If one of the above conditions is not positive, please check the
correct installation of the system.

• After test has been completed, press button 

 on the remote

control to leave the test menu.

Note:
When 30 minutes have elapsed and no buttons have been
pressed, the remote control will automatically exit the test menu
and resume its normal operation.

Guide for the owner

When installation and tests are completed explain the Operation
and Maintenance Manual to the owner, with particular attention to
the main operating modes of the air conditioner, such as:

• Turning the unit on and off.

• Functions of the remote control.

• Removal and cleaning of the air filters.

Leave the two installation manuals for the indoor and outdoor units
with the owner for future use during maintenance operations or for
any other needs.

Summary of Contents for 42VQV050

Page 1: ...42VQV Console Underceiling T h e S t andards Institutiono f I s r a e l Q u ality Assured Fi r m SI ISO 9001 INSTALLATION MANUAL...

Page 2: ...anuals supplied with the remote controls The operation and maintenance instructions for the indoor unit and the installation instructions for the indoor and the outdoor unit are given in the manuals f...

Page 3: ...to the outdoor unit installation instructions Dimensions mm and weights Minimum clearances Wall installation Ceiling installation B A 80 D C 50 min 500 min 50 min 42VQV050 080 050 080 050 080 42VQV 05...

Page 4: ...llation manual Outoor unit Indoor unit Height difference 1 The accessories have not been awarded IMQ certification Description Part number Condensate discharge 42VKG9002 pump 220 240V 50Hz Cable cover...

Page 5: ...r s outdoor unit Coupling units which have different control systems may cause irreversible damage and void the warranty protection The manufacturer declines any liability for system malfunction resul...

Page 6: ...ause condensate dripping flattening or kinking the refrigerant pipes or condensate pipes excessive height difference between outdoor and indoor units see installation manual of outdoor unit unnecessar...

Page 7: ...connections to the outdoor unit can be concealed For better operation of the thermostat located on the unit it is advisable to avoid unit installation in enclosed spaces There are three alternatives f...

Page 8: ...n For exit to the rear the wall hole must be made in the position shown in the illustration Drill a 70 or 80 mm diameter hole The hole must have a 5 10 mm downward slope towards the outside Insert the...

Page 9: ...g diameter Model Gas Liquid 42VQV Suction Discharge mm inches mm inches 050 12 70 1 2 6 35 1 4 080 15 87 5 8 9 52 3 8 For refrigerant tubes use seamless insulated refrigeration grade tube Cu DHP type...

Page 10: ...hat mains supply connection is made through a switch that disconnects all poles with contact gap of a least 3 mm The indoor outdoor unit connecting wires must be A07 RN F type 245 IEC 57 or higher wit...

Page 11: ...ller Press the and buttons of the infrared remote control and hold them pressed for more than 5 seconds The display will be cleared the temperature segments will display the first configuration item C...

Page 12: ...e it OFF Energise the system turning the power supply ON Fault code operating test and guide for the owner Press the and buttons of the infrared remote control and hold them pressed for more than 5 se...

Page 13: ...m the room is drawn into the unit through the grilles and filter at the bottom of the unit No draught guide vane fully open position recommended for ceiling installation in cooling mode to avoid draug...

Page 14: ...ensate dripping the manufacturer will not be held responsible for any damage caused The supplementary fan motor for outside air intake has to be supplied separately and controlled by a bipolar ON OFF...

Page 15: ...26H17 0604 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice June 2004 Supersedes April 2004 Printed in Is...

Reviews: