
7-2. Operation Data
FILE NO. SVM-13035
<Cooling>
Standard
Heat exchanger
Indoor
Outdoor
Compressor
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19
35/24
42UQV050M
0.9 to 1.1
11 to 13
40 to 42
67
42UQV060M
0.9 to 1.1
11 to 13
41 to 43
77
<Heating>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/15
7/6
42UQV050M
2.5 to 2.6
40 to 42
1 to 3
79
42UQV060M
2.6 to 2.8
42 to 44
0 to 2
84
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m
Tempeature
condition(°C)
Model name
RAS-
Model name
RAS-
High
High
High
High
– 21 –
Summary of Contents for 42UQV050M Series
Page 106: ...TOSHIBA CARRIER THAILAND CO LTD...