10

Use a scale having a precision with at least 10 g per index line when adding 
the refrigerant.
Do not use a bathroom scale or similar instrument.

     Precautions for adding refrigerant

Drain
guide

Space for pipes

Wall

Shield pipe

Inside the room

Drain hose

Extension drain hose

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.

CAUTION

OUTDOOR UNIT

OUTDOOR UNIT

Installation Place

•  A place which provides the spaces around the outdoor unit as shown in the 

diagram

•  A place which can bear the weight of the outdoor unit and does not allow an 

increase in noise level and vibration

•  A place where the operation noise and discharged air do not disturb your 

neighbors

•  A place which is not exposed to a strong wind
•  A place free of a leakage of combustible gases
•  A place which does not block a passage
•  When the outdoor unit is to be installed in an elevated position, be sure to 

secure its feet.

•  The allowable length of the connecting pipe.

Model

38TVBA018

38TVBA024

Chargeless

Up to 15 m

Up to 15 m

Maximum length

20 m

20 m

Additional refrigerant 
charging

16 - 20 m

(20 g / 1 m)

16 - 20 m

(20 g / 1 m)

Maximum refrigerant 
charging

1.050 kg

1.060 kg

•  The allowable height of outdoor unit installation site.

Model

38TVBA018

38TVBA024

Maximum height

12 m

12 m

•  A place where the drain water does not raise any problems

CAUTION

1.  Install the outdoor unit without anything blocking the air discharging.
2.  When the outdoor unit is installed in a place always exposed to strong 

wind like a coast or on a high storey of a building, secure the normal fan 
operation using a duct or a windshield.

3.  In particularly windy areas, install the unit such as to avoid admission of 

wind.

4.  Installation in the following places may result in trouble.
  Do not install the unit in such places.
  •  A place full of machine oil
  •  A saline-place such as the coast
  •  A place full of sul

fi

 de gas

  •  A place where high-frequency 

waves are likely to be generated 
as from audio equipment, welders, 
and medical equipment

Strong 

wind

2.  Put water in the drain pan and make sure that the water is drained out of 

doors.

3.  When connecting extension drain hose, insulate the connecting part of 

extension drain hose with shield pipe.

Do not form the
drain hose into
a wavy shape.

Do not rise the
drain hose.

50 mm
or more

Do not put the
drain hose end
into water.

Do not put the
drain hose end
in the drainage ditch.

Drainage

1.  Run the drain hose sloped downwards.

NOTE

•  The hole should be made at a slight downward slant on the outdoor side.

When the outdoor unit is installed in a place where the drain water 
might cause any problems, Seal the water leakage point tightly using a 
silicone adhesive or caulking compound.

CAUTION

90

Obliquity

Roughness

Warp

Refrigerant Piping Connection

1.  Cut the pipe with a pipe cutter.

2. Insert a 

fl

 are nut into the pipe and 

fl

 are the pipe.

 • 

Projection margin in 

fl

 aring : A (Unit : mm)

RIDGID

 (clutch type)

IMPERIAL

 (wing nut type)

Outer dia. of copper pipe

R32

Ø6.35

1.5 to 2.0

Ø9.52

1.5 to 2.0

Ø12.70

2.0 to 2.5

Pipes thickness

0.8 mm or more

Outer dia.

of copper pipe

R32 tool used

Conventional tool 

used

Ø6.35

0 to 0.5

1.0 to 1.5

Ø9.52

0 to 0.5

1.0 to 1.5

Ø12.70

0 to 0.5

1.0 to 1.5

Pipes thickness

0.8 mm or more

     Flaring

A

Die

Pipe

•  Do not scratch the inner surface of the 

fl

 are part when removing burrs

•  Flare processing under the condition of scratches on the inner surface 

of 

fl

 are processing part will cause refrigerant gas leak.

CAUTION

01_1124950113_EN.indd   10

01_1124950113_EN.indd   10

23/11/2563 BE   18:36

23/11/2563 BE   18:36

Summary of Contents for 42TVBA018

Page 1: ...nit 42TVBA018 024 Outdoor unit 38TVBA018 024 1124950113 R32 ENGLISH AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 00_1124950113_Cover indd 1 00_1124950113_Cover indd 1 23 11 2563 BE 17 39 23 11 2563...

Page 2: ...ct Remote Controller for Wire Operation 7 Piping and Drain Hose Installation 8 Indoor Unit Fixing 9 Drainage 10 OUTDOOR UNIT 10 Installation Place 10 Refrigerant Piping Connection 10 Evacuating 11 ELE...

Page 3: ...uire admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use sh...

Page 4: ...WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION T...

Page 5: ...esult in explosion and injury Thickness of copper pipes used R32 must be more than 0 8 mm Never use copper pipes thinner than 0 8 mm Do not perform flare connection inside a building or dwelling or ro...

Page 6: ...ld result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakag...

Page 7: ...commend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use th...

Page 8: ...e control Saddle Extension drain hose Not available provided by installer The provided Remote Controller is a wireless type which also can be used as a wire Please see How to Connect The Remote Contro...

Page 9: ...no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installe...

Page 10: ...wire Notch for wire out Control wire Terminal Display unit Screw Front panel Wire size 28 22AWG or 0 08 0 32 mm2 Outer diameter not over 4 7 mm control wire length 30 m or less Remark 1 Recommend to...

Page 11: ...cribing slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tight...

Page 12: ...ilding secure the normal fan operation using a duct or a windshield 3 In particularly windy areas install the unit such as to avoid admission of wind 4 Installation in the following places may result...

Page 13: ...y the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 20 meters 15 minutes for 20 met...

Page 14: ...air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Co...

Page 15: ...use some electrical part burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A s...

Page 16: ...rved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are d...

Page 17: ...ge quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated...

Page 18: ...1 1 2 1 2 H07RN F 60245 IEC66 3 R32 02_1124950113_TH indd 1 02_1124950113_TH indd 1 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 19: ...TH 2 2 R32 02_1124950113_TH indd 2 02_1124950113_TH indd 2 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 20: ...3 R32 R32 R22 R32 0 8 0 8 Amin m2 Amin m2 Amin M 2 5 x 0 22759 x h0 2 M kg h0 m 0 6 1 8 1 0 2 2 2 5 02_1124950113_TH indd 3 02_1124950113_TH indd 3 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 21: ...TH 4 R32 GWP 1 675 R32 ref AR4 1 GWP F gas regulation 517 2014 02_1124950113_TH indd 4 02_1124950113_TH indd 4 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 22: ...5 1 1 2 1 3 2 4 1 5 Ultra pure 2 6 6 7 2 8 1 9 1 2 1 1 2 1 2 3 4 3 6 1 2 3 4 3 2 P N RB A623DA 02_1124950113_TH indd 5 02_1124950113_TH indd 5 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 23: ...1 5 3 7 7 4 2 A 6 35 12 70 B 8 1 C 8 10 50 300 170 600 100 100 600 600 SPACER 8 125 108 28 320 340 600 90 86 102 2 5 02_1124950113_TH indd 6 02_1124950113_TH indd 6 24 11 2563 BE 16 46 24 11 2563 BE 1...

Page 24: ...nter of pipe hole 35 120 180 240 65 23 6 1 50 40 170 132 23 6 5 300 85 2 5 1 5 4 45 0 6 RF 1 2 3 5 6 4 6 6 15 5 4 x 25R 1 2 1 3 2 4 3 0 12 0 01 5 3 6 1 2 02_1124950113_TH indd 7 02_1124950113_TH indd...

Page 25: ...3 1 25L 9 9 3 1 25L 0 15 0 02 10 A B A B 28 22AWG 0 08 0 32 2 4 7 30 4 5 6 7 30 10 1 2 1 1 3 70 5 1 3 2 28 22AWG 0 08 0 32 2 4 7 30 8 9 0 15 0 02 3 1 16L 3 1 25L A B 02_1124950113_TH indd 8 02_112495...

Page 26: ...9 1 1 4 2 43 43 30 80 520 420 43 R 30 2 2 1 2 3 4 1 2 02_1124950113_TH indd 9 02_1124950113_TH indd 9 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 27: ...1 060 38TVBA018 38TVBA024 12 12 1 2 A 90 RIDGID R32 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1 0 1 5 12 70 0 0 5 1 0 1 5 0 8 IMPERIAL R32 6 35 1 5 2 0 9 52 1 5 2 0 12 70 2 0 2 5 0 8 A 1 2 3 4 10 02_1124950113_T...

Page 28: ...6 R32 1 2 3 4 15 20 15 20 27 101 76 5 6 7 8 Hight Low 101 76 6 1 2 3 4 5 6 12 70 A 4 15 88 A 5 H H17 H19 14 18 1 4 1 8 H22 H30 33 42 3 3 4 2 H14 8 12 0 8 1 2 H17 14 18 1 4 1 8 A H 02_1124950113_TH in...

Page 29: ...2 0 12 7 8 42TVBA018 42TVBA024 50Hz 220 V 1 9 05A 10 20A 11 5A 15A H07RN F 60245 IEC66 1 5 2 H07RN F 60245 IEC66 0 75 2 1 2 3 4 5 6 02_1124950113_TH indd 12 02_1124950113_TH indd 12 24 11 2563 BE 16...

Page 30: ...13 1 2 3 1 2 3 3 50 10 70 10 1 2 3 4 5 6 7 8 9 3 02_1124950113_TH indd 13 02_1124950113_TH indd 13 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 31: ...CHECK 00 1 4 MODE CHECK B 00 B 2 1 A 2 A A 3 A 1 2 B A A B TEST RUN COOL RESET 10 OPERATION RESET OPERATION 3 3 5 5 OPERATION 3 3 ON 02_1124950113_TH indd 14 02_1124950113_TH indd 14 24 11 2563 BE 16...

Page 32: ...8 R22 3 4 5 6 7 8 9 Freol S MS HAB Barrel Freeze PVE R32 1 1 30 0 5 MPa R32 1 H H 6 4 9 5 12 7 R32 R410A 17 22 26 R22 24 2 A A 6 4 9 5 12 7 R32 R410A 9 1 13 2 16 6 R22 9 0 13 0 16 2 R32 0 5 MPa 02_11...

Page 33: ...MEMO 00_1124950113_Cover indd 3 00_1124950113_Cover indd 3 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Page 34: ...MEMO 00_1124950113_Cover indd 4 00_1124950113_Cover indd 4 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Page 35: ...00_1124950113_Cover indd 5 00_1124950113_Cover indd 5 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Page 36: ...1124950113 00_1124950113_Cover indd 6 00_1124950113_Cover indd 6 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Reviews: