9

How to remove the drain cap

Clip the drain cap by needle-nose 
pliers and pull out.

How to remove the drain hose

•  The drain hose can be removed by removing the 

screw securing the drain hose and then pulling out 
the drain hose.

•  When removing the drain hose, be careful of any 

sharp edges of steel plate. The edges can injuries.

•  To install the drain hose, insert the drain hose 

fi

 rmly until the connection part contacts with heat 

insulator, and then secure it with original screw.

How to 

fi

 x the drain cap

1)  Insert hexagon wrench (4 mm) 
  in a center head.

2)  Firmly insert the drain cap.

Firmly insert the drain hose and drain cap; otherwise, water may leak.

CAUTION

Drain hose

Left-hand connection with piping

•  Bend the connecting pipe so that it is laid within 43 mm above the wall 

surface. If the connecting pipe is laid exceeding 43 mm above the wall 
surface, the indoor unit may unstably be set on the wall.

  When bending the connecting pipe, make sure to use a spring bender so 

as not to crush the pipe.

Bend the connecting pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (

fi

 gure)

80

  

520 mm

420 mm

43 mm

Liquid side

Gas side

(To the forefront of 

fl

 are)

Outward form of indoor unit

R 30 mm (Use polisin (polyethylene)

core or the like for bending pipe.)

Use the handle of screwdriver, etc.

NOTE

If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the 
connecting pipes to the auxiliary pipes and wrap the facing tape around 
them.

In case of right or left piping

•  After scribing slits of the front panel 

with a knife or a making-off pin, cut 
them with a pair of nippers or an 
equivalent tool. 

In case of bottom right or bottom left piping

•  After scribing slits of the front panel 

with a knife or a making-off pin, cut 
them with a pair of nippers or an 
equivalent tool. 

CAUTION

•  Bind the auxiliary pipes (two) and connecting cable with facing tape 

tightly. In case of leftward piping and rear-leftward piping, bind the 
auxiliary pipes (two) only with facing tape.

Indoor unit

Connecting cable

Auxiliary pipes

Installation plate

•  Carefully arrange pipes so that any pipe does not stick out of the rear 

plate of the indoor unit.

•  Carefully connect the auxiliary pipes and connecting pipes to one 

another and cut off the insulating tape wound on the connecting pipe 
to avoid double-taping at the joint; moreover, seal the joint with the 
vinyl tape, etc.

•  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

•  When bending a pipe, carefully do it, not to crush it. 

Do not apply lubricating oil
(refrigerant machine oil)
when inserting the drain
cap. Application causes
deterioration and drain
leakage of the plug.

Insert a hexagon wrench 
(4 mm).

No gap

Slit

Slit

1

2

Hook here.

1

Installation plate

Hook

Press

(unhook)

Indoor Unit Fixing

•  For detaching the indoor unit 

from the installation plate, 
pull the indoor unit toward 
you while pushing its bottom 
up at the speci

fi

 ed parts.

1.  Pass the pipe through the hole in the wall and hook the indoor unit on the 

installation plate at the upper hook.

2.  Swing the indoor unit to right and left to con

fi

 rm that it is 

fi

 rmly hooked up 

on the installation plate.

3.  While pressing the indoor unit onto the wall, hook it at the lower part on the 

installation plate. Pull the indoor unit toward you to con

fi

 rm that it is 

fi

 rmly 

hooked up on the installation plate.

The lower part of indoor unit may 

fl

 oat, 

due to the condition of piping and you 
cannot 

fi

 x it to the installation plate. In 

that case, use the 

!

 screws provided 

to 

fi

 x the unit and the installation plate. 

Information

!

Screw

Push

Push

01_1124950113_EN.indd   9

01_1124950113_EN.indd   9

23/11/2563 BE   18:36

23/11/2563 BE   18:36

Summary of Contents for 42TVBA018

Page 1: ...nit 42TVBA018 024 Outdoor unit 38TVBA018 024 1124950113 R32 ENGLISH AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 00_1124950113_Cover indd 1 00_1124950113_Cover indd 1 23 11 2563 BE 17 39 23 11 2563...

Page 2: ...ct Remote Controller for Wire Operation 7 Piping and Drain Hose Installation 8 Indoor Unit Fixing 9 Drainage 10 OUTDOOR UNIT 10 Installation Place 10 Refrigerant Piping Connection 10 Evacuating 11 ELE...

Page 3: ...uire admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use sh...

Page 4: ...WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION T...

Page 5: ...esult in explosion and injury Thickness of copper pipes used R32 must be more than 0 8 mm Never use copper pipes thinner than 0 8 mm Do not perform flare connection inside a building or dwelling or ro...

Page 6: ...ld result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakag...

Page 7: ...commend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use th...

Page 8: ...e control Saddle Extension drain hose Not available provided by installer The provided Remote Controller is a wireless type which also can be used as a wire Please see How to Connect The Remote Contro...

Page 9: ...no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installe...

Page 10: ...wire Notch for wire out Control wire Terminal Display unit Screw Front panel Wire size 28 22AWG or 0 08 0 32 mm2 Outer diameter not over 4 7 mm control wire length 30 m or less Remark 1 Recommend to...

Page 11: ...cribing slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tight...

Page 12: ...ilding secure the normal fan operation using a duct or a windshield 3 In particularly windy areas install the unit such as to avoid admission of wind 4 Installation in the following places may result...

Page 13: ...y the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 20 meters 15 minutes for 20 met...

Page 14: ...air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Co...

Page 15: ...use some electrical part burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A s...

Page 16: ...rved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are d...

Page 17: ...ge quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated...

Page 18: ...1 1 2 1 2 H07RN F 60245 IEC66 3 R32 02_1124950113_TH indd 1 02_1124950113_TH indd 1 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 19: ...TH 2 2 R32 02_1124950113_TH indd 2 02_1124950113_TH indd 2 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 20: ...3 R32 R32 R22 R32 0 8 0 8 Amin m2 Amin m2 Amin M 2 5 x 0 22759 x h0 2 M kg h0 m 0 6 1 8 1 0 2 2 2 5 02_1124950113_TH indd 3 02_1124950113_TH indd 3 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 21: ...TH 4 R32 GWP 1 675 R32 ref AR4 1 GWP F gas regulation 517 2014 02_1124950113_TH indd 4 02_1124950113_TH indd 4 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 22: ...5 1 1 2 1 3 2 4 1 5 Ultra pure 2 6 6 7 2 8 1 9 1 2 1 1 2 1 2 3 4 3 6 1 2 3 4 3 2 P N RB A623DA 02_1124950113_TH indd 5 02_1124950113_TH indd 5 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 23: ...1 5 3 7 7 4 2 A 6 35 12 70 B 8 1 C 8 10 50 300 170 600 100 100 600 600 SPACER 8 125 108 28 320 340 600 90 86 102 2 5 02_1124950113_TH indd 6 02_1124950113_TH indd 6 24 11 2563 BE 16 46 24 11 2563 BE 1...

Page 24: ...nter of pipe hole 35 120 180 240 65 23 6 1 50 40 170 132 23 6 5 300 85 2 5 1 5 4 45 0 6 RF 1 2 3 5 6 4 6 6 15 5 4 x 25R 1 2 1 3 2 4 3 0 12 0 01 5 3 6 1 2 02_1124950113_TH indd 7 02_1124950113_TH indd...

Page 25: ...3 1 25L 9 9 3 1 25L 0 15 0 02 10 A B A B 28 22AWG 0 08 0 32 2 4 7 30 4 5 6 7 30 10 1 2 1 1 3 70 5 1 3 2 28 22AWG 0 08 0 32 2 4 7 30 8 9 0 15 0 02 3 1 16L 3 1 25L A B 02_1124950113_TH indd 8 02_112495...

Page 26: ...9 1 1 4 2 43 43 30 80 520 420 43 R 30 2 2 1 2 3 4 1 2 02_1124950113_TH indd 9 02_1124950113_TH indd 9 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 27: ...1 060 38TVBA018 38TVBA024 12 12 1 2 A 90 RIDGID R32 6 35 0 0 5 1 0 1 5 9 52 0 0 5 1 0 1 5 12 70 0 0 5 1 0 1 5 0 8 IMPERIAL R32 6 35 1 5 2 0 9 52 1 5 2 0 12 70 2 0 2 5 0 8 A 1 2 3 4 10 02_1124950113_T...

Page 28: ...6 R32 1 2 3 4 15 20 15 20 27 101 76 5 6 7 8 Hight Low 101 76 6 1 2 3 4 5 6 12 70 A 4 15 88 A 5 H H17 H19 14 18 1 4 1 8 H22 H30 33 42 3 3 4 2 H14 8 12 0 8 1 2 H17 14 18 1 4 1 8 A H 02_1124950113_TH in...

Page 29: ...2 0 12 7 8 42TVBA018 42TVBA024 50Hz 220 V 1 9 05A 10 20A 11 5A 15A H07RN F 60245 IEC66 1 5 2 H07RN F 60245 IEC66 0 75 2 1 2 3 4 5 6 02_1124950113_TH indd 12 02_1124950113_TH indd 12 24 11 2563 BE 16...

Page 30: ...13 1 2 3 1 2 3 3 50 10 70 10 1 2 3 4 5 6 7 8 9 3 02_1124950113_TH indd 13 02_1124950113_TH indd 13 24 11 2563 BE 16 46 24 11 2563 BE 16 46...

Page 31: ...CHECK 00 1 4 MODE CHECK B 00 B 2 1 A 2 A A 3 A 1 2 B A A B TEST RUN COOL RESET 10 OPERATION RESET OPERATION 3 3 5 5 OPERATION 3 3 ON 02_1124950113_TH indd 14 02_1124950113_TH indd 14 24 11 2563 BE 16...

Page 32: ...8 R22 3 4 5 6 7 8 9 Freol S MS HAB Barrel Freeze PVE R32 1 1 30 0 5 MPa R32 1 H H 6 4 9 5 12 7 R32 R410A 17 22 26 R22 24 2 A A 6 4 9 5 12 7 R32 R410A 9 1 13 2 16 6 R22 9 0 13 0 16 2 R32 0 5 MPa 02_11...

Page 33: ...MEMO 00_1124950113_Cover indd 3 00_1124950113_Cover indd 3 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Page 34: ...MEMO 00_1124950113_Cover indd 4 00_1124950113_Cover indd 4 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Page 35: ...00_1124950113_Cover indd 5 00_1124950113_Cover indd 5 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Page 36: ...1124950113 00_1124950113_Cover indd 6 00_1124950113_Cover indd 6 23 11 2563 BE 17 39 23 11 2563 BE 17 39...

Reviews: